| Plan Review Stops For Permit 03100871 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-01-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2004-01-09 |
Time |
10:24 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
2004-01-09 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2004-01-23 00:00:00 | 01/23/04 NEW STATE APPROVED APPROVED | | | TESTING REPORT OK TO ISSUEJW | | 2004-01-09 00:00:00 | OVERHEAD GARAGE DOOR NOT ON THE STATE | | | WEB SITE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | 01-23-04 OK TO ISSUE, NEW STATEWIDE | | | PRODUCT TESTING REPORTJW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-12-31 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-12-31 |
Time |
10:11 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2003-12-31 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2003-12-31 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03100871 | | | ADD: 2275 PALM BEACH LAKES BLVD | | | CONT: HALLMARK BUILDERS | | | TEL: (561)512-5512 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | SECOND REVIEW: DENIED | | | | | | 1) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: | | | 1) NEW OVERHEAD DOORS | | | | | | 2) 1707.4.3 EACH EXTERIOR DOOR | | | ASSEMBLY NOT COVERED BY 1707.4.2 | | | (GLAZED DOORS) SHALL BE LISTED AND TEST- | | | ED FOR A PERIOD EQUAL TO THE QUANITY | | | 3600/ V WHERE THE TIME PERIOD IS IN | | | SECTIONS AND V IS IN MILES PER HR TAKEN | | | FROM FIGURE 1606. THE TIME PERIOD SHALL | | | ALSO INCLUDE A 10 SECOND PERIOD AT A | | | LOAD EQUAL TO 1.5 TIMES THE DESIGN | | | PRESSURE. | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. WWW.FLORIDABUILDING.ORG | | | ARE ACCEPTED. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-12-01 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-12-01 |
Time |
14:48 |
Rev Time |
2.50 |
| Received By |
jwitmer |
Date |
2003-12-01 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2003-12-01 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 03100871 | | | ADD: 2275 PALM BEACH LAKES BLVD | | | CONT: HALLMARK BUILDERS | | | TEL: (561)512-5517 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | ACTION: DENIED | | | | | | 1) FL BLD CODE 1606.1.5: COMPONENTS & | | | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- | | | OLD OR RESIDENT INSPECTOR) OF PRODUCT | | | TESTING REPORTS,MISSING REPORTS ARE AS | | | FOLLOWS: OVERHEAD DOOR | | | | | | PRODUCT APPROVALS SUBMITTED WITH | | | PERMIT APPLICATION AFTER OCTOBER 1, 2003 | | | ARE REQUIRED TO COMPLY WITH THE FLORIDA | | | PRODUCT APPROVAL SYSTEM. FOR INFORMATION | | | PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH | | | STATEWIDE APPROVAL ARE REQUIRED TO BE | | | SUBMITTED WITH A COVER SHEET THAT LISTS | | | THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE | | | STATEWIDE APPROVAL, SUBMIT AN APPLICA- | | | TION FOR LOCAL PRODUCT APPROVAL OR SITE | | | SPECIFIC FORM PER RULE 9B-72. SEE | | | ATTACHMENT. | | | | | | 2) WHAT TYPE OF OCCUPANCY WILL THE NEW | | | AREA BE USED FOR? THERE IS NEW PROPOSED | | | 10'X10' DOORS BUT BALLARDS TO STOP | | | AUTO ENTRY? | | | | | | 3) SHEET A-3 INDICATES A 2HR WALL DETAIL | | | U-411, THE DETAIL NEGLETES TO INDICATE | | | THE REQUIRED INSULATION(3, 3A OR 3B). | | | | | | 4) PROVIDE THE TYPE OF SEALENT SYSTEM TO | | | BE USED TO PROVIDE A 2 HR RATING FOR THE | | | WALL METAL ROOF DECK ASSEMBLY. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-05-14 |
Time |
06:13 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-05-14 |
Time |
06:13 |
Sent To |
|
|
| Notes |
| 2004-05-14 00:00:00 | EXHAUST FAN(S) STILL SHOWN W/OUT DISC. | | | REDLINED. | | | PLANS WILL BE REQ'D TO HAVE ALL CIRCUIT- | | | ING ON PLANS AND CORRELATE WITH PANEL | | | SCHEDULE BEFORE FINAL. | | | ALL DISCONNECTING MEANS TO BESHOWN. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-12-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-17 |
Time |
11:30 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-12-17 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2003-12-17 00:00:00 | ***REDLINED DISC REQ'D FOR ROOFTOP | | | EXHAUST FANS. SHOWS J-BOX | | | NEC 440 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-10-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-22 |
Time |
18:17 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-10-22 |
Time |
17:57 |
Sent To |
|
|
| Notes |
| 2003-10-22 00:00:00 | ******** UNSAT *********** | | | | | | 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS | | | AT 125%. 215.3,230.42,ETC. | | | | | | 2)NOTE: PLEASE SHOW LOAD ON EXISTING | | | MDP. PLANS DO SHOW DELETION OF EXSITING | | | PANELS, BUT LOAD ON THOSE PANELS AND | | | MDP IS UNCLEAR. | | | 215.5 | | | | | | 3)NOTE: PLEASE CLARIFY DISTANCE FOR | | | TAPPED CONDUCTORS FOR A/C. PER 240.21 | | | | | | 4)NOTE: PLEASE CLARIFY, PLAN SHOWS A | | | "KEY NOTE" #5 BELOW PANEL "A" AND KEY | | | NOTES DO NOT HAVE A #5? | | | | | | PLEASE SEE COMMENTS FROM OTHER REVIEWERS | | | THAT MAY OR MAY NOT HAVE AN AFFEACT ON | | | ELECTRICAL SHEETS. | | | PLEASE BE SURE TO REMOVE ALL OLD/VOIDED | | | SHEETSA AND INSERT NEW SHEETS INTO SETS | | | FOR REVIEW AND STAMPING. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2004-05-14 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2004-05-14 |
Time |
10:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-12-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-24 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-24 |
Time |
15:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-11-06 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-11-06 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-11-06 |
Time |
14:28 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-05-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-13 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-13 |
Time |
15:58 |
Sent To |
|
|
| Notes |
| 2004-05-13 00:00:00 | TO COMM BD#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-07 |
Time |
11:47 |
Sent To |
M |
|
| Notes |
| 2004-04-07 00:00:00 | TO PK BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-12-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-08 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-08 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2003-12-08 00:00:00 | TO COMM BD#21 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-15 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-15 |
Time |
11:53 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-15 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2003-10-15 00:00:00 | TO COMM BD#45 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2004-05-14 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-05-14 |
Time |
14:46 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2004-05-14 |
Time |
14:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-04-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-04-13 |
Time |
07:44 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-04-13 |
Time |
07:24 |
Sent To |
|
|
| Notes |
| 2004-04-13 00:00:00 | DENIED: | | | NEW WORK ROOM EXHAUST WAS REMOVED IT | | | WAS NOT EFFECTIVE.DOUBLE LOUVERED | | | DOORS WERE INSTALLED. | | | | | | THE WOMENS RESTROOM & ROOM OUTSIDE | | | RESTROOM ARE SUPPLIED WITH AN EXISTING | | | SYSTEM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
11:47 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-12-19 |
Time |
10:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-11-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-11-18 |
Time |
07:27 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-11-18 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2003-11-18 00:00:00 | DENIED: | | | 1.PLAN SHEET M-1 INDICATES OA LOUVER | | | ON OUTSIDE WALL AND DOES NOT INDICATE | | | ANY DUCTWORK TO MIX OA WITH THE A/C | | | SYSTEM.PLEASE SHOW COMPLIANCE WITH | | | ASHRAE 62-89 SECTION 6.1.3.2 & 6.1.3.3. | | | | | | 2.PLEASE NOTE LOCATION OF OA.PLAN | | | SHEETS A-1 & A-2 INDICATE OVERHEAD DOORS | | | IN THE SAME AREA AS THE OA LOUVER.WILL | | | THIS BE AN AREA FOR DELIVERIES & P/U? | | | OA SHALL NOT BE LOCATED WHERE NOXIOUS | | | CONTAMINANTS ARE PRESENT PER 2001 FBC(M) | | | 401.5.1. | | | | | | 3.PLEASE NOTE THE HEIGHT REQUIREMENT | | | FOR THE STAND FOR THE CONDENSING UNIT | | | SHALL COMPLY WITH 2001 FBC 1511.7 | | | (SEE ATTACHED). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-12-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-19 |
Time |
16:21 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-12-19 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-11-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-11-04 |
Time |
08:40 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-11-04 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2003-11-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | | | | 1) SHT A2 FLOOR PLAN, INDICATE THE LOCA- | | | TION OF THE ACCESSIBLE TOILET ROOM FOR | | | THE SOUND ADVISE STORE. 104.2.1 | | | 2) SHT A2 NO DRINKING FOUNTAINS SHOWN ON | | | FLOOR PLAN. 104.2.1 | | | 3) SHT A2 ACCESSIBLE TOILET ROOMS. PRO- | | | VIDE A DETAIL FOR ALL ACCESSIBLE TOILET | | | ROOMS PER SECTIONS 11-4.22, 11-4.16, | | | 11-4.19, AND 11-4.18 AND ALL SUBSECTIONS | | | 4) SHTS P1 & P2 WET VENT, ONLY THE FIX- | | | TURES WITHIN THE BATHROOM GROUPS SHALL | | | CONNECT TO THE WET-VENTED HORIZONTAL | | | BRANCH DRAIN. 909.1 THE DRINKING FOUNT- | | | AIN SHALL TIE IN DOWNSTREAM OF THE BATH- | | | ROOM FIXTURES. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|