Plan Review Details - Permit 03100781
Plan Review Stops For Permit 03100781
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-12-29 Cont ID  
Sent By shill Date 2003-12-29 Time 09:07 Rev Time 1.00
Received By shill Date 2003-12-29 Time 09:07 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-10 Cont ID  
Sent By dpalmer Date 2003-12-24 Time 06:51 Rev Time 1.00
Received By shill Date 2003-12-10 Time 16:10 Sent To  
Notes
2003-12-10 00:00:00***CORRECTIONS***
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ADDITIONAL PERMITS REQUIRED.
  
 2.)SEE PREVIOUS LIST, PROVIDE A
 HURRICANE SHUTTER INSTALLATION SCHEDULE.
 IF THIS IS NOT SUBMITTED, A SEPARATE
 PERMIT FOR HURRICANE SHUTTERS WILL BE
 REQUIRED.
  
 3.)OLD PLANS ARE NOT IN THE PACKAGE.
 THE DEMO OF THE STAIRS IS NOT ON THIS
 PLAN.
  
 4.)EFFECTIVE OCTOBER 1, 2003,
 STATEWIDE OR SITE SPECIFIC PRODUCT
 APPROVAL REQUIRED FOR WINDOWS, DOORS,
 ROOF, SHUTTERS.SEE WWW.FLORIDABUILDING
 .ORG FOR MORE INFORMATION.PERMIT WILL
 BE ISSUED WITH A PROVISO TO PROVIDE
 STATEWIDE OR SITE SPECIFIC BEFORE
 INSTALLATION.
  
 5.)ARE ALL OF THE WINDOWS BEING REPLAC
 ED AS SHOWN ON "PROPOSED"?IF THEY
 ARE, ADD TO THE PERMIT APPLICATION.
  
 6.)SEE PREVIOUS LIST; SHOW BEDROOMS
 ON THE PLAN SHOWING COMPLIANCE WITH
 FBC1005.4, EMERGENCY EGRESS.
  
 7.)THE LANDING MUST BE AT LEAST THE
 WIDTH OF THE DOOR, FBC1007.4.
  
 8.)THE STAIR DOES NOT COMPLY WITH
 FBC1007.3.1, TREADS APPEAR TO BE 13",
 RISER APPEARS TO BE 7", 2 RISERS + 1
 TREAD IS TO BE 24"-25" (EXCLUSIVE OF
 NOSING, INDICATE NOSING DISTANCE ON
 PLAN IF APPLICABLE).
  
 9.)SEE PREVIOUS LIST, #14, FRONT DOOR
 TO HAVE A CLEAR OPENING OF 32".A
 32" DOOR DOES NOT COMPLY.
  
 10.) SEE PREVIOUS LIST, ITEM #20,
 THE LANDING DOES NOT COMPLY WITH FBC
 1004.7.2, LANDING SHALL HAVE A MINIMUM D
 DIMENSION MEASURED IN THE DIRECTION OF
 TRAVEL EQUAL TO THE WIDTH OF THE
 STAIRWAY.SEE EXCEPTION (48").
  
 11.)THE RAILING DETAIL DOES NOT SHOW
 THE HEIGHT.SHOW COMPLIANCE WITH FBC
 1015.3, OPENINGS, SEE ATTACHED.
  
 12.)PROVIDE A STRUCTURAL DETAIL OF THE
 ROOF OVERHANG.IT SHOWS LUMBER AND
 REDHEADS; NO CONNECTORS, SHEATHING,ROOF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-08 Cont ID  
Sent By pkrauss Date 2003-12-10 Time 13:40 Rev Time 1.50
Received By sthyng Date 2003-10-30 Time 15:41 Sent To Z
Notes
2003-10-30 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.A NOC WAS NOT
 GIVEN TO THE CITY OF WPB WHEN THE DEMO
 PERMIT WAS ISSUED DUE TO THE VALUE
 BEING LESS THAN $2500.
  
 2.)IMPACT PROTECTION REQUIRED, FBC
 1606.1.4.SUBMIT A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.
  
 3.)SUBMIT TWO COPIES OF PRODUCT
 APPROVALS FOR THE METAL DOOR, WINDOWS,
 IMPACT PROTECTION, ROOF. ANY LEGIBLE,
 CURRENT PRODUCT APPROVALS NOT SUBMITTED
 BEFORE THE PERMIT IS ISSUED WILL NOT
 BE INCLUDED AS PART OF THIS PERMIT AND
 WILL REQUIRE A SEPARATE PERMIT.
  
 4.)THIS IMPROVEMENT IS OVER 50% OF
 VALUE, FBC3401.7.2.6.SOME COMMENTS ON
 THIS LIST ARE AFFECTED BY THIS CODE
 SECTION.
  
 5.)ADDITIONAL PERMITS REQUIRED.
  
 6.)PROVIDE A WALL SECTION FROM
 FOUNDATION THROUGH THE ROOF, FBC104.3.1.
 1., INCLUDING ASSEMBLY AND MATERIALS.
  
 7.)ENERGY CALC REQUIRED, FBC13-101.2.
 "INSULATE" IS A PART OF THE DESCRIPTION
 OF WORK ON THE PERMIT APPLICATION.
 SHOW INSULATION R VALUES ON THE WALL
 SECTION.PLEASE NOTE THAT 600C IS A
 PRESCRIPTIVE METHOD; WALL SECTION MUST
 MEET MINIMUMS ON THE ENERGY CALC.
  
 8.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-101.2.
  
 9.)PROVIDE A SURVEY OF THIS PROPERTY.
 ALSO PROVIDE A SITE PLAN, SHOWING ALL
 DIMENSIONS TO SCALE.YOU ARE ADDING A
 PORCH; ZONING APPROVAL REQUIRED.
  
 10.) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN (EACH
 PAGE) FBC104.2.1.
  
 11.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SHEDULE, SEE ATTACHED.
  
 12.)THE WINDOW IN THE BATHROOM (ABOVE
 THE TUB) IS TO COMPLY WITH FBC2405.2
 (SAFETY GLASS); SHOW ON PLAN.
  
 13.)SHOW WINDOW TYPE, SIZE AND SILL
 HEIGHT FOR BEDROOM WINDOWS TO COMPLY
 WITH FBC1005.4.
  
 14.)SHOW FRONT DOOR SIZE.THE FRONT
 DOOR IS TO COMPLY WITH TABLE 1004 (32"
 MIN. CLEAR OPENING).
  
 15.) SMOKE DETECTORS REQUIRED FOR
 BEDROOMS, FBC905.2.2.
  
 16.) STAIRS ARE BEING REMOVED, WAS THIS
 TO ACCESS THE ATTIC?THE BUILDING
 APPEARS TO BE A ONE STORY (ELEVATION).
 ATTIC ACCESS REQUIRED, FBC2309.IF YOU
 ARE REPLACING THE STAIRS WITH AN ATTIC
 ACCESS THE SIZE MUST COMPLY WITH
 FBC2309, SHOW SIZE ON FLOOR PLAN.
  
 17.) SPECIFY ALL CONNECTORS; BRAND AND
 MODEL NUMBER WITH MAX UPLIFT.
  
 18.)THE LAMINATED BEAM APPEARS TO BE
 A DOUBLE FROM THE SIDE VIEW, BUT IS
 SPECIFIED AS A SINGLE ON THE FRONT VIEW.
  
 19.)SHOW A FRAMING DETAIL FOR THE ROOF
 OF THE FRONT PORCH.
  
 20.)A LANDING TO COMPLY WITH FBC1007.4
 .2 IS REQUIRED AT THE FRONT DOOR.
  
 21.)PROVIDE A DETAIL OF THE LANDING
 AND STAIRS, WITH DIMENSIONS.THE SIDE
 ELEVATION SHOWS FOUR STEPS, FRONT
 ELEVATION SHOWS THREE.HANDRAIL MAY
 BE REQUIRED FBC1007.5.1.IF A HANDRAIL
 IS REQUIRED, PROVIDE A DETAIL TO COMPLY
 WITH FBC1007, FBC1608.
  
 WHEN RESUBMITTING, CLOUD ALL REVISIONS.
 CHANGE ONLY AFFECTED SHEETS AND SUBMIT
 OLD SHEETS SEPARATELY.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-24 Cont ID  
Sent By dpalmer Date 2003-12-24 Time 06:49 Rev Time 0.33
Received By dpalmer Date 2003-12-24 Time 06:41 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-19 Time 15:23 Rev Time 0.75
Received By dpalmer Date 2003-12-05 Time 06:29 Sent To M
Notes
2003-12-05 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT PLANS DRAWN TO
 MEET 104.2 OF THE FAC. BOTH SETS OF PLAN
 -S NEED TO VERY CLEAR AND READABLE.
  
 2)NOTE: PLEASE CORRELATE BOTH SETS. MANY
 ITEMS ARE NOT THE SAME ON EACT SET.
  
 3)NOTE: PLEASE CLARIFY MEANS OF EGRESS
 LIGHTING CONTROL FOR ROOMS. APPEARS TO
 SHOW FANS? OR ARE THESE FANS/LT COMBO?
 210.70
  
 4)NOTE: PLEASE LIST REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANELSCEDULE.
 210.12
  
 5)NOTE: PLEASE SHOW A/C LOCATIONS AND
 REQ'D DISC'S PER 440.11. SHOW RECEPT/GFI
 PER 210.63 AND IF AHU IS IN ATTIC.210.70
 LT.
  
 6)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 ED. PER 210.8A-6
  
 7)NOTE: PLEASE CORRELATE LOADS SHOWN ON
 PANEL SCHEDULE AND ON LOAD CALCAULATIONS
  
 PLEASE ATTACH AND MAKE TWO COMPLETE SETS
 FOR REVIEW. PLEASE DO THIS WITH PLANS
 FOR ALL TRADES.
 PLEASESUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-12-04 Time 14:05 Rev Time 0.33
Received By dpalmer Date 2003-10-20 Time 11:06 Sent To P
Notes
2003-10-20 00:00:00************ UNSAT *******************
  
 1)NOTE: PLEASE SUBMIT PLANS INCLUDING
 RISER DIAGRAM FOR NEW SERVICE AND
 LOCATION OF PANEL ETC.
 PLEASE SUBMIT PLANS SHOWING ALL MIN
 ELECTRICAL PER NEC 2002.
 RECEPTS/LTS/SD'S/PANEL SCHEDULE/CONDUCT-
 -OR SIZES AND OCP.
 215.5 ETC.
  
 2)NOTE: PLEASE SEE FBC 104.2 FOR MIN
 REQ'D FOR PLANS AND CLARITY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-19 Cont ID  
Sent By csiegber Date 2003-12-17 Time 15:25 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 15:25 Sent To E
Notes
2003-12-19 00:00:00TO DP DESK/RESUB
2003-12-17 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-04 Cont ID  
Sent By mmclean Date 2003-12-05 Time 08:05 Rev Time 0.00
Received By csiegber Date 2003-12-03 Time 16:27 Sent To E
Notes
2003-12-03 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-25 Cont ID  
Sent By mmclean Date 2003-12-03 Time 12:44 Rev Time 0.00
Received By sthyng Date 2003-11-25 Time 13:58 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-15 Time 08:37 Rev Time 0.00
Received By csiegber Date 2003-10-15 Time 08:37 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-12-10 Cont ID  
Sent By pkrauss Date 2003-12-10 Time 13:39 Rev Time 0.33
Received By pkrauss Date 2003-12-10 Time 13:39 Sent To B
Notes
2003-12-10 00:00:00CONTRACTOR FAXED FORM 600C & PLAN WITH
 TRANSFER AIR TO BEDROOM SIZED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-12-09 Cont ID  
Sent By pkrauss Date 2003-12-09 Time 12:53 Rev Time 0.33
Received By pkrauss Date 2003-12-09 Time 12:45 Sent To  
Notes
2003-12-09 00:00:00DENIED:2ND REQUEST
 PLAN SUBMITTED DOES NOT INDICATE RETURN
 AIR FROM THE BEDROOM AREAS.SEE COMMENT
 #3 FROM 1ST REVIEW (ATTACHED) FOR SIZE
 REQUIREMENTS.
  
 PROVIDE A COMPLETED FORM 600C OR ENERGY
 AND MANUAL J CALCULATIONS PER 2001 FBC
 CHAPTER 13 SUB-SECTION 101.4.1.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-29 Cont ID  
Sent By dpalmer Date 2003-12-05 Time 06:59 Rev Time 0.25
Received By pkrauss Date 2003-10-29 Time 06:41 Sent To B
Notes
2003-10-29 00:00:00DENIED:
 1.PROVIDE COMPLETED FORM 600C AS PER
 2001 FBC CHAPTER 13 SECTION 600.1.C.
  
 2.PLEASE NOTE, NO PLANS SUBMITTED FOR
 REVIEW AND WILL BE SUBJECT TO FIELD
 INSPECTORS APPROVAL.
  
 3.RETURN AIR REQUIRED FROM ROOMS WITH
 CLOSING DOORS (EXAMPLE: BEDROOMS).
 RETURN AIR TO COMPLY WITH REVISION TO
 THE 2001 FBC(M) 601.4 EFFECTIVE 6-30-03:
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 4.OVERFLOW PROTECTION REQUIRED AS PER
 2001 FBC(M) 307.2.3, AUXILIARY DRAIN PAN
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-22 Cont ID  
Sent By dpalmer Date 2003-10-20 Time 11:06 Rev Time 0.25
Received By jleech Date 2003-10-22 Time 19:08 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-17 Time 15:25 Rev Time 0.00
Received By mmclean Date 2003-12-05 Time 08:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-12-03 Cont ID  
Sent By csiegber Date 2003-12-03 Time 16:27 Rev Time 0.00
Received By mmclean Date 2003-12-03 Time 12:44 Sent To I
Notes
2003-12-03 00:00:0012/3/03 NEED NEW DRAWING FOR PORCH, WITH
 NO POST, 3FT ATTACHED TO WALL,
 CANTILEVER (THE FIRST DRAWING IS
 ENCROACH IS THE FRONT SETBACK) CALLED
 OWNER WILL PROVIDE MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-11-10 Cont ID  
Sent By sthyng Date 2003-11-25 Time 13:58 Rev Time 0.00
Received By mmclean Date 2003-11-10 Time 15:31 Sent To  
Notes
2003-11-10 00:00:0011/10/03 DENIED, NEED 2 COPY OF SURVEY
 SHOWING WORK & SITE PLAN CALLED CONTR
 FILE H MM