| 2003-11-09 00:00:00 | *****CORRECTIONS***** |
| | |
| | SAMANTHA THYNG, BUILDING PLANS EXAMINER |
| | 561-805-6724 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE |
| | STAMPED AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.233-5025 |
| | |
| | 3.)THE SURVEY SHOWS A SCREEN |
| | ENCLOSURE.YOU ARE BUILDING THROUGH |
| | HALF OF IT.ARE YOU DEMOLISHING THE |
| | ENTIRE SCREEN ROOM?SHOW ON THE PLAN. |
| | |
| | 4.)THE NAME AND SIGNATURE TO THE |
| | PERSON RESPONSIBLE FOR THE DESIGN IS |
| | REQUIRED TO BE ON THE PLAN (EACH SHEET), |
| | FBC104.2. |
| | |
| | 5.)SEPARATE PERMITS REQUIRED. |
| | |
| | 6.)SHOW AREA CALCULATIONS ON THE PLAN, |
| | EXISTING, PROPOSED, NEW TOTAL. ADDITIONS |
| | OF OVER 25% OF EXISTING BUILDING AREA |
| | ARE REQUIRED TO COMPLY WITH FBC3401.7.2 |
| | (SMOKE DETECTORS AND GFCIS IN EXISTING |
| | HOUSE), SHOW COMPLIANCE ON THE PLAN IF |
| | APPLICABLE. |
| | |
| | 7.)ENERGY CALCS REQUIRED, FBC13-103.1. |
| | 2.SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC. |
| | |
| | 8.)AN EXISTING SLAB IS IN THE AREA |
| | WHERE YOU ARE PROPOSING AN ADDITION.IT |
| | IS NOT SHOWN OR ADDRESSED ON THE PLAN. |
| | PROVIDE A FOUNDATION PLAN. |
| | |
| | 9.)THE WALL SECTION SHOWS A PITCHED |
| | ROOF, THE ELEVATIONS SHOW A FLAT ROOF. |
| | IF IT IS PITCHED, SPECIFY THE PITCH. |
| | THE WALL SECTION MUST MATCH THE |
| | ELEVATIONS. |
| | |
| | 10.) ALL DRAWINGS ARE TO BE TO SCALE |
| | FBC104.2.SHOW SCALE ON THE PLAN. |
| | |
| | 11.)ADDITIONAL FEES (RADON), $5.12, |
| | SEE ATTACHED BZ233266. |
| | |
| | 12.)THE ELEVATIONS DO NOT MATCH THE |
| | SITE/FLOOR PLANS, APPEARS THAT EAST AND |
| | WEST ARE LABELED INCORRECTLY. |
| | |
| | 13.)MARK ROOMS BY USE (EX: BEDROOM, |
| | KITCHEN). |
| | |
| | 14.)ON THE EXISTING FLOOR PLAN, YOU |
| | ARE BLOCKING ALL WINDOWS AND DOORS TO A |
| | ROOM WHICH APPEARS TO BE A BEDROOM. |
| | BEDROOMS ARE REQUIRED TO HAVE EMERGENCY |
| | EGRESS TO COMPLY WITH FBC1005.4. |
| | |
| | 15.)IMPACT PROTECTION REQUIRED FOR |
| | GLAZING, FBC1606.1.7.PROVIDE A |
| | HURRICANE SHUTTER INSTALLATION SCHEDULE |
| | PER WPB POLICY. |
| | |
| | 16.)THE WALL SECTION IS TO INCLUDE |
| | ASSEMBLY AND MATERIALS.IT REFERS TO A |
| | ROOF PLAN WHICH IS NOT ON THE PLAN. |
| | PROVIDE A ROOF FRAMING PLAN.SHOW |
| | ALL CONNECTIONS. |
| | |
| | 17.)THE BOTTOM OF THE FOOTER IS |
| | REQUIRED TO BE A MINIMUM OF 12" BELOW |
| | GRADE, FBC1804.1.3. |
| | |
| | 18.)THE CONNECTOR SPECIFIED "SIMPSON |
| | ETA16" IS NOT IN THE SIMPSON 2003 |
| | CATALOG. |
| | |
| | 19.)THE FRAMING DETAIL AT THE WINDOW |
| | SPECIFIES A HUGHES STRAP, NO LONGER IN |
| | BUSINESS.IT ALSO SPECIFIES "USP RTPGA |
| | 824", NOT IN THE USP 2003 CATALOG. |
| | REVISE. |
| | |
| | 20.)THE WINDOW/DOOR BUCK DETAIL IS FOR |
| | MASONRY, THE WALL SECTION IS WOOD FRAME. |
| | CLARIFY. |
| | |
| | 21.)PROVIDE DESIGN INFORMATION ON THE |
| | PLAN FBC1606.1.7, 2003 AMENDMENT. |
| | |
| | 22.)SMOKE DETECTORS REQUIRED FOR |
| | BEDROOMS, FBC905.2.2. |
| | |
| | 23.)PROVIDE A FOUNDATION PLAN. |
| | |
| | 24.)STATEWIDE OR LOCAL PRODUCT |
| | APPROVALS ARE REQUIRED.ANY PRODUCT |
| | APPROVALS NOT SUBMITTED AT THE TIME OF |
| | PERMIT ISSUANCE WILL NOT INCLUDE THOSE |
| | ITEMS AS PART OF THIS PERMIT AND WILL |
| | REQUIRE A SEPARATE APPLICATION WITH |
| | ADDITIONAL FEES.THIS DOES NOT APPLY |
| | TO STRUCTURAL COMPONENTS, WHICH ARE |
| | REQUIRED FOR THIS PERMIT.SEE THE |
| | DCA WEBSITE FOR MORE INFORMATION: |
| | |
| | WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/ |
| | PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM |
| | |
| | FAC9B-72.050, EFFECTIVE OCTOBER 1, 2003 |