Plan Review Details - Permit 03100683
Plan Review Stops For Permit 03100683
Review Stop P PLUMBING
Rev No 2 Status F Date 2004-12-28 Cont ID  
Sent By kstevens Date 2004-12-28 Time 08:30 Rev Time 1.25
Received By kstevens Date 2004-12-28 Time 08:30 Sent To  
Notes
2004-12-28 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 CITY CODE
  
 1) SHT 1 SANITARY RISER DIAGRAM DOES
 NOT
 MEET THE CODE REQUIREMENTS.
 A) WASH MACHINE AND LAUNDRY SINK SHALL
 DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET-VENT FOR THE BATHROOM FIXTURES.
 SECTION 909.1
 B) ROOF DRAIN SHALL NOT DRAIN INTO THE
 SANITARY SYSTEM PER CITY CODE SECTION
 90-125(5)
  
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-10-14 Cont ID  
Sent By shernand Date 2003-10-14 Time 09:49 Rev Time 0.00
Received By shernand Date 2003-10-14 Time 09:49 Sent To  
Notes
***NONE***