Plan Review Details - Permit 03100679
Plan Review Stops For Permit 03100679
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-14 Cont ID  
Sent By csiegber Date 2003-10-14 Time 09:03 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 09:03 Sent To P
Notes
2003-10-14 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-18 Cont ID  
Sent By csiegber Date 2003-10-14 Time 09:03 Rev Time 0.50
Received By kstevens Date 2003-10-18 Time 10:15 Sent To  
Notes
2003-10-18 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 INDICATE GALVANIZED OR CSST WHERE IT IS
 APPLICABLE. SUBMIT MANUF. SPECIFICATION
 SHEETS FOR POLYPIPE FOR PRODUCT APPROVAL
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). WATER HEATER BTU'S NOT SHOWN.
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 5) PLUMBING CONTRACTING LICENSE IS REQ-
 UIRED TO PULL A PERMIT FOR NATURAL GAS.
 EITHER A CFC OR RFC LICENSE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]