Plan Review Details - Permit 03100679
| Plan Review Stops For Permit 03100679 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-14 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-14 |
Time |
09:03 |
Sent To |
P |
|
| Notes |
| 2003-10-14 00:00:00 | TO GAS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-10-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-14 |
Time |
09:03 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-18 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2003-10-18 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2001 | | | FUEL GAS CODE. | | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | INDICATE GALVANIZED OR CSST WHERE IT IS | | | APPLICABLE. SUBMIT MANUF. SPECIFICATION | | | SHEETS FOR POLYPIPE FOR PRODUCT APPROVAL | | | 3. BTU LOAD OF EACH APPLIANCE AND THE | | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | | THE FBC-2001 FUEL GAS CODE SECS. 401.8 | | | THRU 402.5.2 AND TABLES 402(1) THRU | | | 402(34). WATER HEATER BTU'S NOT SHOWN. | | | 4. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2001 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | 5) PLUMBING CONTRACTING LICENSE IS REQ- | | | UIRED TO PULL A PERMIT FOR NATURAL GAS. | | | EITHER A CFC OR RFC LICENSE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |