Plan Review Details - Permit 03100659
Plan Review Stops For Permit 03100659
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-06-02 Cont ID  
Sent By shill Date 2004-06-02 Time 14:33 Rev Time 0.50
Received By shill Date 2004-06-02 Time 14:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-05-25 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 10:34 Rev Time 1.00
Received By shill Date 2004-05-25 Time 13:17 Sent To  
Notes
2004-05-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ONLY ONE SEALED SET SUBMITTED.
 SUBMIT A SECOND SIGNED AND SEALED SET
 OF PLANS FOR THE PERMIT TO BE ISSUED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-05-14 Cont ID  
Sent By shill Date 2004-05-14 Time 10:20 Rev Time 3.00
Received By shill Date 2004-05-14 Time 10:20 Sent To  
Notes
2004-05-14 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE THE SOILS ENGINEER'S
 RECOMMENDATIONS IN REGARDS TO FOOTINGS.
 ALSO THE SOILS REPORT IS FOR SINGLE
 STORY ADDITIONS; REVISE THE SOILS
 REPORT TO CORRECTLY REFLECT THE SCOPE
 OF WORK.REVISE WALL SECTIONS/FOUND.
 PLAN AS NECESSARY.
  
 2.)THE NOTICE OF COMMENCEMENT IS FOR
 A GARAGE ADDITION.REVISE TO MORE
 ACCURATELY REFLECT THE SCOPE OF WORK.
  
 3.)PROVIDE A MORE COMPLETE TRAY
 CEILING DETAIL.THE FRAMING APPEARS
 SUSPENDED; WHERE IS THE OUTSIDE WALL?
 IT IS NOT CLEAR HOW THE FIRESTOPS SHOWN
 WILL PERFORM AS FIRESTOPS.SEE ATTACHED
 AS AN EXAMPLE OF ONE WAY TO SHOW
 COMPLIANCE FOR FRAMED WALLS.
  
 4.)HANDRAIL REQUIRED AT STAIRS FBC
 1007.5, PROVIDE DETAILS; SHOW COMPLIANCE
 WITH FBC CHAPTER 10 AND FBC 1608.
  
 5.)THE 7/8 STUCCO (WALL SECTION) IS
 TO BE A 3 COAT VERTICAL, NOT A 2 COAT
 HORIZONTAL, APPLICATION FBC2504.2.2,
 ASTM C926.THIS APPLIES ONLY TO STUCCO
 IN A VERTICAL APPLICATION OVER WIRE
 LATH.
  
 6.)SEE PREVIOUS LISTS, FLORIDA STATE,
 LOCAL OR SITE SPECIFIC PRODUCT APPROVALS
 REQUIRED IN ADDITION TO THE TEST REPORTS
 PROVIDED.WWW.FLORIDABUILDING.ORG
 (PRODUCT APPROVAL, SEARCH PRODUCT
 APPROVALS).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-24 Cont ID  
Sent By shill Date 2004-02-24 Time 08:20 Rev Time 3.00
Received By shill Date 2004-02-24 Time 08:20 Sent To M
Notes
2004-02-24 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, ITEM #1, PROVIDE
 A SURVEY FOR THIS JOB.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 4.)THE ENGINEER IS TO DATE THE SEAL,
 FAC61G-23.002.
  
 5.)ADDITIONAL FEES DUE (VALUE
 INCREASE), $660.11.BZ235302
  
 6.)SEE PREVIOUS LIST, ITEM 6, STILL
 REFERS TO SBC, BUT NOW THE SHEET IS A15.
  
 7.)SEE PREVIOUS LIST, ITEM #9.DESIGN
 IS FOR A SIMPLE DIAPHRAGM WHICH SHOULD
 BE SYMMETRICAL.THIS STRUCTURE IS NOT
 SYMMETRICAL.ADDRESS.
  
 8.)PROVIDE A DETAIL FOR THE TRAY
 CEILING INCLUDING FIREBLOCKING.
  
 9.)SEE PREVIOUS LIST, ITEM #13,
 PROVIDE A GUARDRAIL DETAIL TO COMPLY
 WITH FBC1608.2.2 AND FBC1015.
  
 10.)STAIR RAIL IS TO COMPLY WITH
 FBC1608 AND 1007.
  
 11.)SEE PREVIOUS LIST, PROVIDE A SOILS
 INVESTIGATION REPORT.
  
 12.)SEE PREVIOUS LIST, ITEM #18, IN
 REGARDS TO WALL SECTIONS TO COMPLY WITH
 FBC1804.1.3 AND FBC1804.1.7 CITY OF
 WEST PALM BEACH AMENDMENTS.
  
 13.)SEE PREVIOUS LIST, ITEM #21,
 PROVIDE STATEWIDE PRODUCT APPROVALS IN
 ADDITION TO THE TEST REPORTS PROVIDED.
  
 14.)SEE PREVIOUS LIST, ITEM #27,
 STUCCO IS REQUIRED TO BE 7/8"VERTICAL
 APPLICATION, FBC2504.2.2, ASTM C926.
 THIS APPEARS IN SEVERAL PLACES; CHECK
 ALL DETAILS.
  
 15.)PROVIDE MULLION PRODUCT APPROVALS,
 AS WELL AS ANY OTHER PRODUCT APPROVALS
 REQUIRED.ANY PRODUCT APPROVALS
 REQUIRED BUT NOT SUBMITTED WILL REQUIRE
 SEPARATE PERMITS.
  
 16.)THERE ARE TWO 2-STORY WALL
 SECTIONS, ONE BLOCK AND ONE FRAME ON
 THE 2ND FLOOR.IT APPEARS THAT THE
 2ND FLOOR IS TO BE FRAME (FLOOR PLAN),
 BUT THE HURRICANE SHUTTER SCHEDULE
 INDICATES BLOCK FASTENING FOR ALL
 OPENINGS.PLEASE CLARIFY.
  
 17.)STORM SHUTTER PRODUCT APPROVAL IS
 ILLEGIBLE.
  
 18.)WHEN RESUBMITTING, REPLACE SHEETS
 WHICH HAVE CHANGED AND SUBMIT OLD
 SHEETS SEPARATELY.INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED TO EXPEDITE PLAN
 REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-09 Cont ID  
Sent By pkrauss Date 2004-02-12 Time 11:05 Rev Time 3.00
Received By sthyng Date 2003-11-09 Time 11:00 Sent To  
Notes
2003-11-09 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE A SURVEY FOR THIS JOB.
  
 2.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 4.)THIS IS AN ADDITION OF GREATER
 THAN 25% AND MUST COMPLY WITH 3401.7.2.
 FBC, 2003 AMENDMENT (GFCI AND SMOKE
 DETECTORS IN EXISTING HOUSE).
  
 5.)SHEET A1, SITE PLAN, PROVIDE
 DIMENSIONS.
  
 6.)SHEET C1, SITE PLAN NOTE #14,
 REFERS TO SBC103.THE GOVERNING CODE
 IS FBC; SECTION 103 REFERS TO POWERS &
 DUTIES OF THE BUILDING OFFICIAL.
  
 7.)SHEET C1, TRUSS NOTES #9, ROOF
 SHEATHING SCHEDULE MUST COMPLY WITH
 CITY OF WEST PALM BEACH AMENDMENTS TO
 THE FBC, TABLE 2306.1.
  
 8.)SHEET C1, WINDOW AND DOOR NOTES,
 THE MIN DESIGN PRESSURE IS +-34;
 CONFLICTS WITH DESIGN PRESSURES ON
 DOOR AND WINDOW SCHEDULES.
  
 9.)SHEET A2, WIND DESIGN INFORMATION
 INDICATES THAT THE DESIGN OF THE
 BUILDING IS BASED ON THE SIMPLIFIED
 PROVISIONS OF FBC1606.2.THIS IS FOR
 A SIMPLE DIAPHRAGM BUILDING.THE
 BREEZEWAY IS NOT ALLOWED PER ZONING;
 THE BUILDING NO LONGER QUALIFIES AS A
 SIMPLE DIAPHRAGM.
  
 10.) FIRESTOP REQUIRED FOR STAIRS,
 FBC2305.1.4.
  
 11.) WIND DESIGN INFORMATION IS
 INCOMPLETE, SEE FBC1606.1.7 2003
 AMENDMENT, SHEET A2.
  
 12.) PROVIDE A STRUCTURAL DETAIL FOR
 THE STAIRS.
  
 13.) PROVIDE A GUARDRAIL DETAIL, COMPLY
 WITH FBC1015, 1608.
  
 14.) STAIR RAIL TO COMPLY WITH FBC1608.
  
 15.) DESIGN GRAVITY LOADS, A3 & A7(UNDER
 THE WALL SCHEDULE), REQUIRES A BOTTOM
 CHORD LIVE LOAD OF 10 FOR ATTICS WITHOUT
 STORAGE, 30 FOR ATTICS WITH STORAGE,
 FBC TABLE 1604.1.
  
 16.) WINDOW G, 2ND FLOOR OF DETACHED
 BUILDING, A3, TO COMPLY WITH FBC2405.1
 (SAFETY GLASS).
  
 17.) PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 18.) SHEETS A4, A5, A6, WALL SECTION
 REQUIRES THE FINISHED FLOOR TO BE MIN
 4" ABOVE FINISHED GRADE, CITY OF WEST
 PALM BEACH AMEND. TO THE FBC1804.1.7.
 12" MIN BELOW GRADE REQUIRED FOR THE
 FOOTER, FBC1804.1.3.
  
 19.)SHEET A10, HEAD AND SILL DETAILS
 FOR WINDOWS, NOTE THAT HURRICANE
 SHUTTERS MUST BE INSTALLED HORIZONTALLY
 FOR THOSE OPENINGS BASED ON THIS DETAIL.
  
 20.)PROVIDE A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED,
 PER CITY OF WEST PALM BEACH POLICY.
  
 21.) STATEWIDE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED FOR ALL PRODUCTS,
 INCLUDING STRUCTURAL, FAC 9B-72.050,
 EFFECTIVE OCTOBER 1, 2003.FOR MORE
 INFORMATION, SEE THE DCA WEBSITE AT
 WWW.DCA.STATE.FL.US/FHCD/FBC/COMMITTEES/
 PRODUCT_APPROVAL/1_PRODUCT_APPROVAL.HTM
  
 22.) THE PRODUCT APPROVAL FOR THE PGT
 SINGLE HUNG WINDOW IS ILLEGIBLE.THE
 CASEMENT PRODUCT APPROVAL IS FOR A
 DOUBLE (OPERABLE MULLED TO FIXED),SINGLE
 WINDOW IS NOT COVERED BY THIS PRODUCT
 APPROVAL.THE 6'X6' PICTURE WINDOW
 EXCEEDS THE MAXIMUM RECTANGULAR WINDOW
 SIZE COVERED BY THE PRODUCT APPROVAL
 SUBMITTED (OK FOR ARCHED WINDOW).
  
 23.)THE FOLLOWING PRODUCT APPROVALS
 ARE NEEDED:
 STATEWIDE PRODUCT APPROVAL FOR ALL
 DADE COUNTY NOAS SUBMITTED AND
 CONDITIONALLY APPROVED (SPANISH S,
 16X8 GAR DOOR, STORM PANELS, PGT
 OUTSWING FR DOOR,STANLEY OUTSWING
 GLAZED DOOR, ALUM FG WINDOW)
 INSWING FRENCH DOOR
 SINGLE HUNG WINDOW
 MULLION
 OUTSWING METAL DOOR
 6'X6' FIXED GLASS WINDOW
 CASEMENT WINDOW
  
 24.)PROVIDE A DRAFTSTOP DETAIL AND
 SCHEDULE, BOTH BUILDINGS, FBC705.3.
  
 25.)WALL SECTION, SHEETS A4, A5, A6,
 FIRESTOP REQUIRED FBC705.3.
  
 26.) WALL SCHEDULES, A3, A7, A8,
 SPECIFIES R30 INSULATION FOR A 4"OR6"
 WALL.IS THIS CORRECT?CONFLICTS WITH
 WALL SECTION.
  
 27.) WALL SECTION, A6, STUCCO IS
 REQUIRED TO BE 7/8" HORIZONTAL
 APPLICATION OVER WIRE LATH, FBC2504.2.2,
 ASTM C926.
  
 28.) ADDITIONAL FEES DUE (VALUE
 ADJUSTMENT, RADON), $125.18, SEE
 ATTACHED BZ233272.

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2004-06-02 Cont ID  
Sent By dpalmer Date 2004-06-02 Time 10:34 Rev Time 0.00
Received By dpalmer Date 2004-06-02 Time 10:34 Sent To B
Notes
2004-06-02 00:00:00LETTER FAXED IN FROM OWNER.
 NO ELECTRICAL REVIEW TO BE DONE ON THESE
 PLANS. WILL SUBMIT SEPARATE PLANS,
 PERMIT APPLICATION AND FEES AT A LATER
 DATE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-27 Time 13:05 Rev Time 1.50
Received By dpalmer Date 2004-05-05 Time 19:29 Sent To P
Notes
2004-05-05 00:00:00************* UNSAT **************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002,
 FS 471.023. PLEASE SEE MISSING REQ'D
 LICENSE #'S ON TITLE BLOCKS. THIS IS
 REQ'D FOR ALL TRADES WEATHER OR NOT
 COMMENT IS MADE FROM OTHER REVIEWERS
 THIS HAS BEEN REQUESTED ON PREVIOUS
 REVIEW.
 THE STATE DOES NOT HAVE ANY LISTING OF
 A REQ'D LICENSE / CA#??
 PLEASE VERIFY LICENSING W/ FBPE'S, DBPR.
  
  
 2)NOTE: PLEASE SEE AN "ALUMINUM" EQUIP-
 -MENT GROUNDING CONDUCTOR HAS NOW BEEN
 ADDED. PLEASE SEE ALUM GRNDING CONDUCTOR
 -S ARE NOT PERMITTED.
  
 3)NOTE: PLEASE CORRELATE RISER DIAGRAM,
 PANEL SCHEDULE AND LOAD CALCULATIONS.
 RISER SHOWS 200A SERVICE ALONG WITH
 PANEL SCHEDULE, YET PANEL SCHEDULE
 ALSO INDICATES A 150 MCB????
  
 4)NOTE: PLEASE PROVIDE LOAD CALCULATIONS
 TO MEET NEC 220.
  
 5)NOTE: PLEASE CORRELATE LOAD CALCULAT-
 -IONS WITH PANEL SCHEDULE. THERE ARE
 MANY ITEMS THAT DO NOT CORRELATE.
 PLEASE SEE ONE SET REDLINED.
  
 6)NOTE: PLEASE SEE 220.18 FOR MIN 5KW
 FOR DRYER.
  
 7)NOTE: PLEASE SEE OCP SHOWN FOR AHU'S
 7.5KW W/ 60A BRKRS. PLEASE VERIFY OCP.
 TOO HIGH.
  
 8)NOTE: PLEASE SEE 110.26, DISC FOR A/C
 UNIT DOES NOT MEET ABOVE.
  
 9)NOTE: PLEASE SEE WALKWAY/HALL BETWEEN
 NEW AND ADDITION. MEANS OF EGRESS
 CONTROL FOR LTS. 210.70 FROM MAIN HOUSE.
  
 10)NOTE:PLEASE SEE NFPA-72 8-1.4.2, NO
 SD'S TO BE W/IN 3' FROM BATH DOOR.
  
 11)NOTE: PLEASE SEE PREVIOUS COMMENT
 ABOUT CHAPTER 34 FBC. 3401.7.2.6
 SHOW EXSITING LAYOUT OF EXIST HOUSE,
 ITEMS MUST BE SHOWN FOR BRING UP TO
 2002 NEC.
 BLDG IS OVER 50%.
  
 12)NOTE: PLEASE SHOW CONDUCTORS AND
 CONDUIT SIZE FROM MAIN DISC TO PANEL.
 215.5, 310.15B6
  
 13)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN. 110.9,215.5
  
 PLEASE SEE COPY OF FS 553.80(2)(B)
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-02-10 Cont ID  
Sent By csiegber Date 2004-05-05 Time 08:17 Rev Time 2.00
Received By dpalmer Date 2004-02-10 Time 07:22 Sent To P
Notes
2004-02-10 00:00:00************** UNSAT *****************
  
 **** PLEASE SEE ZONING NOTES, AS THEY
 WILL HAVE A DIRECT AFFECT ON ELETCRICAL,
 MECHANICAL, AND PLUMB PLANS***********
  
 *PLEASE SEE ELECTRICAL NOTE FROM FRIST
 REVIEW. PLEASE SEE MOST NOTES STILL
 NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE 230.2,230.70,230.72,
 TWO SERVICES ARE NOT PERMITTED AND MAINS
 MUST BE GROUPED PER 230.72
  
 2)NOTE: PLEASE SHOW LOCATIONS OF ALL
 ELECTRICAL SERVICE EQUIPMENT ON PLANS.
  
 3)NOTE: PLANS SHOW TWO SEPARATE RISERS,
 HOWEVER THESE ITEMS ARE NOT SHOWN ON
 PLANS? IF INDEED THIS IS ONLY ONE SERV-
 -ICE, PLEASE CORRELATE LOAD CALCS.
 PLEASE SEE THAT A/C SYSTEMS ARE SHOWN ON
 EACH SERVICE AND DO NOT COME FROM ONE.
 SMALL APPL, DRYERS, WASHER ETC.
 PANEL SCHEDULES WERE NOT SUBMITTED AS
 REQUESTED ON FIRST REVIEW, UNABLE TO
 VERIFY.
  
 4)NOTE: PLEASE SEE 310.15B6/310.16 FOR
 SIZING OF SERVICE ENTRANCE CONDUCTORS
 AND FEEDERS. PLANS SHOW 1/0'S, THESE
 ARE NOT OF SUFF SIZE FOR 200A SERVICE.
 RISER IS MISSING CONDUCTORS FROM MAIN(S)
 TO PANELS.
 PLEASE ALSO SEE MISSING EQUIPMENT GROUND
 -ING CONDUCTOR FROM MAIN TO PANEL. PER
 250.110,250.24, SIZE PER 250.122
  
 5)NOTE: PLEASE SEE MISSING COLD WATER
 PIPE TO BE PART OF THE GROUNDING ELECT-
 -RODE SYSTEM. 250.50
  
 6)NOTE: PLEASE SEE RISER, INDICATES
 MAIN, YET 200A PANEL IS ALSO SHOWN AS
 MCB? PLEASE NOTE, THIS IS PERMITTED,
 HOWEVER NOT REQUIRED. IF PLANS SHOW,
 THEN THEY WILL BE REQ'D TO BE INSTALLED,
 UNLESS PLANS ARE REVISED.
  
 7)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 MISSING SOME.
 SD'S ARE ALSO REQ'D TO BE A MIN OF 3'
 FROM BATHROOM DOORS AND KITCHENS. SD'S
 ARE ALSO NOT PEMITTED IN KITCHENS.
  
 8)NOTE: PLEASE SEE COMMENTS FROM FIST
 REVIEW, PANEL SCHEDULE(S)OCP,AWG, ETC
 ALONG WITH ALL MIN REQ'D DEDICATED
 CIRCUITS MUST BE SUBMITTED. 210.52D,
 210.11C3,210.11, 210.12ETC.
  
 9)NOTE: PLEASE SHOW/INDICATE ALL ROOM
 DESIGNATIONS ON ELECTRICAL PLANS. 1ST
 REVIEW.
  
 10)NOTE: PLEASE SEE FAC 61G15-23.002,
 FS 471.023. PLEASE INCLUDE ALL INFORMAT-
 -ION AS REQUIRED FOR TITLE BLOCK.
 PLEASE INCLUDE ALL LICENSE #'S.
 PLEASE SEE ADDRESS DOES NOT CORRELATE
 WITH FILE OF ACTUAL ADDRESS. PLANS SHOW
 257 AND PROPERTY IS LISTED AS 253.
  
 11)NOTE: PLEASE SEE COPY OF FS 553.80(2)
 (B) WITH RESPECT TO DESIGN PROFESSIONAL.
  
 12)NOTE: UNABLE TO DUE A COMPLETE REVIEW
 FOR CODE COMPLIANCE TO 2002NEC DUE TO
 MISSING REQUIRED INFORMATION.
  
 13)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDITIONS TO EXSITNG BLDGS.
 PLEASE SEE THAT MORE THAN 25% IS BEING
 ADDED AND WILL REQUIRE EXISTING ELECTRIC
 -AL TO BE UPGRADED TO MEET 2002 NEC
 PLEASE PROVIDE PLANS/ LAYOUT FOR EXSIT-
 -ING ELECTRICAL AND LOCATION OF ALL
 DEVICES. PLEASE ALSO SEE THAT SD'S WILL
 BE REQUIREDFOR EXISTING, DEDICATED
 CIRCUITS, GFI'S, ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:49 Rev Time 0.25
Received By dpalmer Date 2003-10-27 Time 10:11 Sent To P
Notes
2003-10-27 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE SEE ZONING COMMENTS THAT
 WILL AFFECT ELECTRICAL PLANS.
  
 2)NOTE: PLEASE SEE THAT SEPARATE SERVICE
 IS NOT PERMITTED. 230.2, 230.72, 230.70
  
 3)NOTE: PLEASE SEE 210.52C1-5
  
 4)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 ON ELECTRICAL PLANS.
  
 5)NOTE: PLEASE CLARIFY IF RISER DIAGRAM
 SHOWN FOR MAIN HOUSE IS NEW OR EXISTING?
  
 6)NOTE: PLEASE PROVIDE PANEL SCHEDULE(S)
 WITH AWG/ OCP ETC.
 PLEASE LIST ALL THE MIN REQ'D CIRCUITS
 PLEASE LIST THE ARC FAULT PROETCTED
 CIRCUITS PER 210.12.
 2002 NEC
  
 PLEASE SEE THAT A FULL REVIEW FOR
 ELECTRICAL CODE COMPLIANCE CAN NOT BE
 DONE AT THIS TIME DUE TO MAJOR ELECTRIC-
 -AL CHANGES.
  
 PLEASE SUBMIT FOR REVIEW .IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 11 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:11 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 17:11 Sent To P
Notes
2004-10-20 00:00:00TO KS BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-05-27 Cont ID  
Sent By csiegber Date 2004-05-27 Time 13:05 Rev Time 0.00
Received By csiegber Date 2004-05-27 Time 13:05 Sent To E
Notes
2004-05-27 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-05-24 Cont ID  
Sent By alange Date 2004-05-24 Time 11:10 Rev Time 0.00
Received By alange Date 2004-05-24 Time 11:10 Sent To  
Notes
2004-05-24 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-05-05 Cont ID  
Sent By csiegber Date 2004-05-05 Time 08:17 Rev Time 0.00
Received By csiegber Date 2004-05-05 Time 08:16 Sent To E
Notes
2004-05-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-04-30 Cont ID  
Sent By mmclean Date 2004-05-04 Time 15:29 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 14:50 Sent To Z
Notes
2004-04-30 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-05 Cont ID  
Sent By csiegber Date 2004-02-05 Time 10:49 Rev Time 0.00
Received By csiegber Date 2004-02-05 Time 10:49 Sent To E
Notes
2004-02-05 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-02 Cont ID  
Sent By mmclean Date 2004-02-04 Time 16:36 Rev Time 0.00
Received By csiegber Date 2004-02-02 Time 10:48 Sent To Z
Notes
2004-02-02 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-27 Cont ID  
Sent By csiegber Date 2004-01-27 Time 10:26 Rev Time 0.00
Received By csiegber Date 2004-01-27 Time 10:25 Sent To E
Notes
2004-01-27 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 12:39 Rev Time 0.00
Received By csiegber Date 2003-10-22 Time 12:39 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-14 Cont ID  
Sent By mmclean Date 2003-10-22 Time 12:22 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 09:00 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-03-02 Cont ID  
Sent By shill Date 2004-05-07 Time 10:37 Rev Time 0.35
Received By pkrauss Date 2004-03-02 Time 12:24 Sent To  
Notes
2004-03-02 00:00:00NO CHANGES FROM 2-12-04 SUBMITTAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-12 Cont ID  
Sent By shill Date 2004-02-24 Time 10:28 Rev Time 0.25
Received By pkrauss Date 2004-02-12 Time 10:40 Sent To B
Notes
2004-02-12 00:00:00PLAN WAS APPROVED NOV 5, 2003

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-05 Cont ID  
Sent By jleech Date 2004-02-10 Time 14:56 Rev Time 0.33
Received By pkrauss Date 2003-11-05 Time 11:38 Sent To B
Notes
2003-11-05 00:00:00PLEASE NOTE RETURN AIR REQUIREMENTS AS
 REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30,2003.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-11-02 Cont ID  
Sent By kstevens Date 2004-11-02 Time 15:44 Rev Time 0.75
Received By kstevens Date 2004-11-02 Time 15:44 Sent To  
Notes
2004-11-02 00:00:00REVISION OK - ADD SHOWER - CHANGE TUB
 TO JACUZZI

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-02-10 Cont ID  
Sent By csiegber Date 2004-10-20 Time 17:12 Rev Time 0.33
Received By jleech Date 2004-02-10 Time 14:56 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2004-02-10 Time 12:41 Rev Time 0.50
Received By kstevens Date 2003-10-28 Time 13:35 Sent To M
Notes
2003-10-28 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DOES NOT RE-
 FLECT THE FLOOR PLAN, NOR DOES IT MEET
 CODE REQUIREMENTS. THE LAUNDRY ROOM
 HAS A W/M AND A LAUNDRY SINK. NO SINK
 IS SHOWN ON RISER. 104.2.1 - THE WASH
 MACHINE REQUIRES A STANDPIPE. SECTION
 1002.1 & 802.4. - A CLEANOUT IS REQUIRED
 4' ABOVE THE FLOOR AT THE WASH MACHINE
 SECTION 708.10. - THE RISER SHOWS SHOW-
 ERS AND THE FLOOR PLAN SHOWS TUBS. SECT-
 ION 104.2. SEE RED LINE CORRECTIONS TO
 BE MADE TO RISER AND RESUBMIT FOR REVIEW
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2004-05-04 Cont ID  
Sent By mmclean Date 2004-05-04 Time 15:29 Rev Time 0.00
Received By mmclean Date 2004-05-04 Time 15:29 Sent To I
Notes
2004-05-04 00:00:00NO KITCHEN ALLOWED IN PHASE "B" MM

Review Stop Z ZONING
Rev No 2 Status F Date 2004-02-04 Cont ID  
Sent By csiegber Date 2004-04-30 Time 14:50 Rev Time 0.00
Received By mmclean Date 2004-02-04 Time 16:35 Sent To I
Notes
2004-02-04 00:00:00DENIED, CANNOT HAVE PHASE B CONNECT TO
 HOUSE WITH KITCHEN.CAN REMOVE KITCHEN.
 MAX FOR 1 UNIT IS 800SQ FT AND 200SQ FT
 FOR GARAGE.CALLED MIKE GARRISON MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-10-22 Cont ID  
Sent By csiegber Date 2004-02-02 Time 12:02 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-10-15 00:00:0010/14/03 DENIED CANNOT HAVE A BREEZEWAY
 NEED TO BE 5FT SEPERATION/GARAGE APT
 CAN ONLY BE 750SQ FT & CAN ONLY BE BUILT
 BEHIND THE MAIN STRUCTURE.SEE SEC 94-
 74 & SEC 94-146 OF ZONING CODE CALLED
 OWNER FILE Z MM