Plan Review Details - Permit 03100570
Plan Review Stops For Permit 03100570
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-06-21 Cont ID  
Sent By rbrown Date 2004-06-21 Time 11:19 Rev Time 0.00
Received By rbrown Date 2004-06-21 Time 11:19 Sent To  
Notes
2004-06-21 00:00:00REVISION SUBMITTED 6/3/04 FOR SHEETS
 A-1, A-4, A-6 AND A-7.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-03-16 Cont ID  
Sent By rbrown Date 2004-03-16 Time 09:03 Rev Time 0.00
Received By rbrown Date 2004-03-16 Time 09:03 Sent To  
Notes
2004-03-16 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 SEPARATE PERMIT APPLICATION IS REQUIRED
 FOR DOORS AND WINDOWS (EXCEPT THE
 ROLL-UP DOORS FOR WHICH VALID PRODUCT
 APPROVAL HAS ALREADY BEEN SUBMITTED).

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-02-02 Cont ID  
Sent By rbrown Date 2004-02-02 Time 12:54 Rev Time 0.00
Received By rbrown Date 2004-01-30 Time 14:02 Sent To  
Notes
2004-01-30 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 12/19/03:
  
 1) THIS COMMENT HAS NOT BEEN ADDRESSED.
 THE RESPONSE LETTER DATED 1/15/04 IS
 FROM R.C.T. ENGINEERING.THE COMMENT IS
 ABOUT THE ARCHITECTURAL PLANS SEALED BY
 THE ARCHITECT AND SHOULD HAVE BEEN
 ADDRESSED BY STEPHEN BORUFF, ARCHITECT'S
 AND PLANNERS INC.THE LICENSE NUMBER
 PRINTED ON SHEETS A-1 THROUGH A-11 IS
 THAT OF THE ARCHITECTURAL BUSINESS ONLY.
 PLANS PREPARED BY A REGISTERED ARCHITECT
 SHALL INCLUDE THE PRINTED NAME AND
 LICENSE NUMBER OF THE ARCHITECT SEALING
 THE PLANS, NOT JUST THE ARCHITECTURAL
 BUSINESS.FOR YOUR REFERENCE THE
 FOLLOWING IS A SUMMARY EXTRACT FROM THE
 FLORIDA ADMINISTRATIVE CODE:
 61G1-16.004FL. ADMIN. CODE. - PLANS
 PREPARED BY A REGISTERED ARCHITECT
 SHALL INCLUDE A TITLE BLOCK WHICH MUST:
 - STATE THE FIRM NAME, ADDRESS AND
 TELEPHONE NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND
 DATED SEAL
 - INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS
 ADD THE PRINTED NAME AND LICENSE NUMBER
 OF THE ARCHITECT ON SHEETS A-1 THRU A-11
  
 8) PRODUCT APPROVALS.
 (A) WALL/ROOF PANELS, A VALID PRODUCT
 APPROVAL OR SITE SPECIFIC ENGINEERING IS
 REQUIRED FOR THE PANEL SYSTEM BEFORE A
 PERMIT IS ISSUED.
 (B) WINDOWS AND DOORS, SUBMITTAL OF A
 PRODUCT APPROVAL FOR ROLL-UP DOORS IS
 ACKNOWLEDGED BUT NO VALID PRODUCT
 APPROVAL HAS BEEN SUBMITTED FOR THE
 WINDOWS AND EXTERIOR DOORS.SEPARATE
 PERMIT APPLICATIONS WILL BE REQUIRED.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-12-19 Cont ID  
Sent By rbrown Date 2003-12-19 Time 19:39 Rev Time 0.00
Received By rbrown Date 2003-12-18 Time 12:29 Sent To  
Notes
2003-12-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) 61G1-16.004FL. ADMIN. CODE.PLANS
 PREPARED BY A REGISTERED ARCHITECT SHALL
 INCLUDE THE PRINTED NAME OF THE
 ARCHITECT SEALING THE PLANS.
  
 2) FBC 1005.7.1EGRESS FROM THE
 MEZZANINE.THE TRAVEL DISTANCE FROM THE
 MOST REMOTE POINT ON THE MEZZANINE TO
 THE CLOSEST BUILDING EXIT EXCEEDS 75 FT
 (FBC TABLE 1005.7) SO TWO MEANS OF
 EGRESS ARE REQUIRED FROM THE MEZZANINE.
 AMEND THE PLANS.
  
 3) FBC 704.1.4MATERIALS STORAGE ROOM.
 ANNOTATE SHEET A-1 TO SPECIFY THE
 REQUIRED 2-HOUR FIRE-RATED WALLS AND
 CEILING/ROOF TO THIS ROOM.
  
 4) FBC 705.1.3SHEET A-7, DETAIL 10.
 FIRE DOOR JAMB.WHERE DOES THIS DETAIL
 APPLY?IT SPECIFIES A 1-HOUR FIRE-RATED
 DOOR FRAME AND 45-MINUTE FIRE-RATED DOOR
 WHICH DO NOT CORRELATE WITH ANY DOOR ON
 THE DOOR SCHEDULE.
  
 5) FBC 1608.2SHEET S-3 AND S-5.AMEND
 THE PLANS TO SPECIFY THE CODE
 REQUIREMENT FOR THE HANDRAILS AND
 GUARDRAIL TO SUPPORT A 200LB
 CONCENTRATED LOAD AND 50 PLF LINE LOAD
 (APPLIED AS PER THE CODE) ACTING IN ANY
 DIRECTION.
  
 6) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 7) A SEPARATE PERMIT APPLICATION WILL BE
 REQUIRED FOR THE AWNINGS.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE
 WINDOWS, EXTERIOR DOORS, ROLL-UP DOORS
 AND WALL/ROOF PANELS.
 NOTE: FL. ADMIN CODE RULE 9B-72 (IN
 EFFECT SINCE OCTOBER 1, 2003) REQUIRES
 THAT PRODUCTS HAVE STATEWIDE, LOCAL OR
 SITE-SPECIFIC PRODUCT APPROVAL.THE
 SUBMITTAL SHOULD INCLUDE THE STATEWIDE
 PRODUCT APPROVAL NUMBER (FL###),
 AVAILABLE FROM THE DEPT OF COMMUNITY
 AFFAIRS PRODUCT APPROVAL WEBSITE
 WWW.FLORIDABUILDING.ORG/PR/PR_SRCH.ASP
  
 9) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-06-15 Cont ID  
Sent By dpalmer Date 2004-06-15 Time 14:51 Rev Time 0.50
Received By dpalmer Date 2004-06-15 Time 14:50 Sent To  
Notes
2004-06-15 00:00:00*** NOTES REDLINED ****
  
 SOME SORT OF LIGHTNING PROTECTION SHOWN
 ON PLANS.
 THIS IS NOT PART OF THIS PERMIT AND MUST
 BE SUBMITTED UNDER SEPARATE PERMIT APPL.
  
 ALL LIGHTNING PROTECTION SYSTEMS TO BE
 SUBMITTED UNDER SEPARATE PERMIT AND
 MUST MEET NFPA-780

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By dpalmer Date 2004-01-26 Time 11:23 Rev Time 1.00
Received By dpalmer Date 2004-01-26 Time 11:23 Sent To  
Notes
2004-06-15 00:00:00NOT ENOUGH INFORMATION ON LIGHTNING
 PROTECTION, UNDER SEPARATE PERMIT.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-16 Cont ID  
Sent By dpalmer Date 2003-10-15 Time 19:36 Rev Time 2.00
Received By dpalmer Date 2003-10-15 Time 19:30 Sent To  
Notes
2003-10-16 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE CORRELATE PLANS AND
 RISER/PANEL DIAGRAM. PLANS SHOW CIRCUITS
 FOR A PANEL "H". PLEASE SEE RISER, SHOWS
 WHAT APPEARS TO BE A PANEL "M"?
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE CLARIFY LOCATION OF PANEL
 "LA" AND PANEL "H/M" ON PLANS. PANEL LB
 WAS LOCATED.
  
 3)NOTE: PLEASE SEE 61G15-23.002 FOR ALL
 REQ'D LICENSE INFORMATION ON TITLE BLOCK
 FAC,FS 471.
 THIS WOULD INCLUDE CA#'S.
 PLEASE SEE THAT THIS REQ'D ON ALL SHEETS
 FOR ALL TRADES EVEN A COMMENT IS NOT
 MADE BY ADDTIONAL PLAN REVIEWERS.
  
 PLEASE SEE OTHER REVIEWERS COMMENTS,AS
 THEY MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS FOR REVIEW AND STAMP-
 -ING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE SEE THAT WE ARE NOW UNDER THE
 2002 NEC AS OF 7/1/03
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2003-10-15 00:00:00REVIEW IN PROGRESS, NOTES TO FOLLOW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-10-21 Cont ID  
Sent By mamini Date 2003-10-21 Time 09:45 Rev Time 0.50
Received By mamini Date 2003-10-21 Time 09:45 Sent To  
Notes
2003-10-21 00:00:00PASSED:
 1. SEE PERMIT # 03090886 FOR UNDERGROUND
 UTILITIES AND SITE WORK.
 IF ANY QUESTION PLEASE CONTACT 895-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-06-21 Cont ID  
Sent By rbrown Date 2004-06-21 Time 11:30 Rev Time 0.00
Received By rbrown Date 2004-06-21 Time 11:30 Sent To  
Notes
2004-06-21 00:00:00REVISION O.K. PER M. CARSILLO.SIGNED
 OFF 6/4/04 ON RESUBMITTAL SHEET.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-22 Cont ID  
Sent By mcarsill Date 2004-01-22 Time 16:07 Rev Time 0.00
Received By mcarsill Date 2004-01-22 Time 16:07 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-31 Cont ID  
Sent By mcarsill Date 2003-10-31 Time 16:44 Rev Time 0.00
Received By mcarsill Date 2003-10-31 Time 16:44 Sent To  
Notes
2003-10-31 00:00:001) A HAZARDOUS MATERIALS KNOX-BOX
 WILL BE REQUIRED. PLEASE SEE CITY
 ORDINANCE 3206-99 FOR FURTHER DETAILS.
  
 2) EXIT SIGN SYMBOL APPEARS IN THE
 WRONG LOCATION FOR EXTERIOR DOOR OF
 LAB 116.
  
 3) PLEASE EXPLAIN PURPOSE OF HOLD-OPEN
 DEVICES ON DOUBLE DOORS FOR MATERIALS
 STORAGE ROOM 118. SHOULD THESE DOORS
 REMAIN CLOSED DUE TO THE MATERIALS
 BEING STORED WITHIN IT.
  
 4) NO EXIT SIGNAGE OR EMERGENCY LIGHTING
 SHOWN FOR THE MEZZANINE.
  
 5) WHAT WILL THE FUME HOOD BE USED FOR.
  
 6) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM SYSTEM.
  
 7) NO FIRE SPRINKLER DRAWINGS PROVIDED
 WITH PLANS.
  
 8) BUILDING ADDRESS REQUIRED ON
 PROPER ELEVATION.
  
 9) PLEASE PROVIDE PRODUCT APPROVALS
 FOR THE FIRE SHUTTERS ON PAGE A-6.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-03 Cont ID  
Sent By csiegber Date 2004-06-03 Time 14:31 Rev Time 0.00
Received By csiegber Date 2004-06-03 Time 14:30 Sent To  
Notes
2004-06-03 00:00:00TO COMM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-10 Cont ID  
Sent By rbrown Date 2004-03-10 Time 10:04 Rev Time 0.00
Received By rbrown Date 2004-03-10 Time 10:04 Sent To  
Notes
2004-03-10 00:00:00TO RB DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-01-21 Time 11:28 Rev Time 0.00
Received By csiegber Date 2004-01-21 Time 11:28 Sent To  
Notes
2004-01-21 00:00:00TO COMM BD#37

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-19 Cont ID  
Sent By mmclean Date 2003-10-14 Time 12:27 Rev Time 0.00
Received By rbrown Date 2003-10-14 Time 14:54 Sent To  
Notes
2003-10-14 00:00:00TO COMM BD#39
2003-10-10 00:00:00TO Z

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-02-03 Cont ID  
Sent By pkrauss Date 2004-02-03 Time 07:25 Rev Time 1.00
Received By pkrauss Date 2004-02-03 Time 07:25 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-14 Cont ID  
Sent By pkrauss Date 2003-11-14 Time 07:21 Rev Time 1.20
Received By pkrauss Date 2003-11-14 Time 07:21 Sent To  
Notes
2003-11-14 00:00:00DENIED:
 1.PLEASE NOTE PLAN SHEET AC-2 NOTE 6
 E REFERS TO PLAN SHEET FP-2. PLAN NOT
 SUBMITTED.
  
 2.PLEASE PROVIDE ELEVATION FOR THE
 TERMINATION OF THE EXHAUST HOOD THROUGH
 THE SIDE WALL.TERMINATION SHALL COMPLY
 WITH 2001 FBC(M) 506.3.14.2 & 506.3.14.3
  
 3.PLANS DO NOT INCLUDE ANY INFORMATION
 ON THE HOOD OR FIRE SUPPRESSION SYSTEM.
 PLEASE PROVIDE MANUFACTURER SUBMITTAL
 DATA AND ALL PERTINENT INFORMATION WITH
 PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-06-17 Cont ID  
Sent By kstevens Date 2004-06-17 Time 08:25 Rev Time 0.75
Received By kstevens Date 2004-06-17 Time 08:25 Sent To  
Notes
2004-06-17 00:00:00REVISION OK - ADDED A LAV IN TOILET ROOM
 SHEETS P-1, P-2, P-3, P-4.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-03-16 Cont ID  
Sent By kstevens Date 2004-03-16 Time 09:53 Rev Time 0.25
Received By kstevens Date 2004-03-16 Time 09:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-02-02 Cont ID  
Sent By kstevens Date 2004-02-02 Time 18:41 Rev Time 1.50
Received By kstevens Date 2004-02-02 Time 18:41 Sent To  
Notes
2004-02-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) FROM PREVIOUS REVIEW: AN RPZ BACKFLOW
 IS REQUIRED ON THE WATER SERVICE FOR THE
 BUILDING. SECTION 608.13.2. - COMMENT
 RESPONSE NOTED, BUT A BACKFLOW IS STILL
 REQUIRED FOR THIS BUILDING.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-21 Time 09:55 Rev Time 1.50
Received By mamini Date 2003-10-21 Time 09:55 Sent To  
Notes
2003-10-21 00:00:00DENIED
 REFERENCE: FLORIDA ADMINISTRATIVE CODE
  
 1) G6G15-23.002(2) SEE ATTACHED SHEET
 CONCERNING INFORMATION REQUIRED ON TITLE
 BLOCK.
 2) SHT P-4 SANITARY RISER DIAGRAM, THE
 TRAPS ON MANY FIXTURES SHOW "S" TRAPS.
 TRAPS SHALL BE VENTED AS SHOWN BY RED
 LINE CORRECTIONS. PLEASE SHOW PROPER
 VENTS. 1002.3(5)
 3) WATER SERVICE TO BLDG SHALL HAVE
 BACKFLOW PREVENTIONS. 608.13.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-14 Cont ID  
Sent By mmclean Date 2003-10-14 Time 12:27 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-10-14 00:00:0010/14/03 PASS ZONING MM