Plan Review Details - Permit 03100528
Plan Review Stops For Permit 03100528
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-21 Cont ID  
Sent By csiegber Date 2003-10-21 Time 15:02 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 15:02 Sent To P
Notes
2003-10-21 00:00:00TO GAS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 15:13 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 15:13 Sent To P
Notes
2003-10-08 00:00:00TO GAS

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-25 Cont ID  
Sent By kstevens Date 2003-10-25 Time 11:34 Rev Time 0.50
Received By kstevens Date 2003-10-25 Time 11:34 Sent To  
Notes
2003-10-25 00:00:00 
  
  
  
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-18 Cont ID  
Sent By csiegber Date 2003-10-21 Time 15:02 Rev Time 0.50
Received By kstevens Date 2003-10-18 Time 07:18 Sent To  
Notes
2003-10-18 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 A) FOLLOWING INFORMATION REQUIRED FOR
 APPLICATION FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. SOME PIPE LENGTHS MISSING
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 SOME PIPE SIZES MISSING.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). AFTER ALL
 PIPE LENGTHS ARE SHOWN ON ISOMETRIC, RE-
 CHECK DISTANCE TO MOST REMOTE APPLIANCE.
 4. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2001 FUEL
 GAS CODE SECTION 304.
 5. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2001 FUEL GAS CODE
 SECS. 502 THRU 506.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved