Plan Review Details - Permit 03100195
| Plan Review Stops For Permit 03100195 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-11-24 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-11-24 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-11-24 |
Time |
10:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-10-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-11-20 |
Time |
07:23 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-10-08 |
Time |
15:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-11-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-07 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-07 |
Time |
16:11 |
Sent To |
M |
|
| Notes |
| 2003-11-07 00:00:00 | TO PK BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-03 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-03 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-03 |
Time |
15:47 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-11-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-11-20 |
Time |
07:23 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-11-20 |
Time |
06:41 |
Sent To |
FIRE |
|
| Notes |
| 2003-11-20 00:00:00 | PROVISO: | | | DETAIL 1 ON PLAN 2 OF 3 IS NOT EXCEPTED. | | | PLAN VIEW INDICATES GREASE DUCT LOUVER | | | TERMINATING IN THE "ATTIC" SPACE INSTEAD | | | OF AN OUTSIDE WALL PER 501.3.PLAN DOES | | | NOT REFLECT THE SAME TERMIANTION POINTS | | | AS DETAIL 2 ON PAGE 2, FLOOR PLAN ON | | | SHEET 1 OR 3. | | | | | | PLEASE NOTE CLEANOUTS REQUIRED IN | | | ACCORDANCE WITH 506.3.11. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-07 |
Time |
16:11 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-10-08 |
Time |
14:46 |
Sent To |
FIRE |
|
| Notes |
| 2003-10-08 00:00:00 | DENIED: | | | 1.PROVIDE SUBMITTAL ON THE "IN-LINE" | | | FAN. | | | | | | 2. INDICATE ROOF HEIGHT WHERE THE | | | EXHAUST TERMINATES.HOW WILL THIS | | | BE CLEANED? | | | | | | 3.CLARIFY DETAIL ON PLAN SHEET 2 OF 3, | | | BUILDING SECTION DETAIL 2 OF 2. EXHAUST | | | DUCT APPEARS TO RUN IN FRONT OF THE | | | INTAKE.WHAT IS THE HEIGHT OF THE | | | CLEAN OUT? | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|