Plan Review Details - Permit 03100195
Plan Review Stops For Permit 03100195
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By nmccray Date 2003-11-24 Time 10:13 Rev Time 0.00
Received By nmccray Date 2003-11-24 Time 10:13 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-10-08 Cont ID  
Sent By pkrauss Date 2003-11-20 Time 07:23 Rev Time 0.00
Received By nmccray Date 2003-10-08 Time 15:39 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-07 Cont ID  
Sent By csiegber Date 2003-11-07 Time 16:11 Rev Time 0.00
Received By csiegber Date 2003-11-07 Time 16:11 Sent To M
Notes
2003-11-07 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 15:47 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 15:47 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-20 Cont ID  
Sent By pkrauss Date 2003-11-20 Time 07:23 Rev Time 0.40
Received By pkrauss Date 2003-11-20 Time 06:41 Sent To FIRE
Notes
2003-11-20 00:00:00PROVISO:
 DETAIL 1 ON PLAN 2 OF 3 IS NOT EXCEPTED.
 PLAN VIEW INDICATES GREASE DUCT LOUVER
 TERMINATING IN THE "ATTIC" SPACE INSTEAD
 OF AN OUTSIDE WALL PER 501.3.PLAN DOES
 NOT REFLECT THE SAME TERMIANTION POINTS
 AS DETAIL 2 ON PAGE 2, FLOOR PLAN ON
 SHEET 1 OR 3.
  
 PLEASE NOTE CLEANOUTS REQUIRED IN
 ACCORDANCE WITH 506.3.11.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-11-07 Time 16:11 Rev Time 0.45
Received By pkrauss Date 2003-10-08 Time 14:46 Sent To FIRE
Notes
2003-10-08 00:00:00DENIED:
 1.PROVIDE SUBMITTAL ON THE "IN-LINE"
 FAN.
  
 2. INDICATE ROOF HEIGHT WHERE THE
 EXHAUST TERMINATES.HOW WILL THIS
 BE CLEANED?
  
 3.CLARIFY DETAIL ON PLAN SHEET 2 OF 3,
 BUILDING SECTION DETAIL 2 OF 2. EXHAUST
 DUCT APPEARS TO RUN IN FRONT OF THE
 INTAKE.WHAT IS THE HEIGHT OF THE
 CLEAN OUT?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.