Plan Review Details - Permit 03100025
Plan Review Stops For Permit 03100025
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-10-06 Cont ID  
Sent By jgomez Date 2004-10-06 Time 08:59 Rev Time 0.00
Received By dpalmer Date 2005-01-07 Time 11:43 Sent To PC
Notes
2004-09-24 00:00:00REVISION CHECKLIST:
 1-ARCHITECT SUBMITTING REVISION IS NOT
 THE SAME ARCHITECT OF RECORD.ARCHITECT
 NEEDS TO FOLLOW RULE 61G1-18.002 OF FL
 ADMINISTRATIVE CODE WHEN TAKING OVER
 ANOTHER ARCHITECT'S WORK.
 2-ENGINEER'S REPORT: A)PROVIDE 2 COPIES
 WITH ORIGINAL SEAL, SIGNATURE & DATE
 AS REQ'D BY CHAPTER 471 FL STATUTES.
 B)ENGINEER TO PROVIDE ALL INFORMATION
 AS REQUIRED BY SEC. 1606.1.7 FBC 2001.
 3-ARCHITECT AND ENGINEERTO HAVE
 TITLE BLOCK WITH ALL INFORMATION AS
 REQUIRED BY CHAPTER 481 AND 471 OF
 FLORIDA STATUTES. INCLUDING THE
 CERTIFICATE OF AUTHORIZATION.
 4-PROVIDE COMPLETE INFORMATION ON WALL
 SECTIONS:FASTENER TYPE & SPACING
 FOR STUCCO METAL LATH, WALL AND ROOF
 SHEATHING, 2X4 REINFORCING FRAMING,
 FRAMING ANCHOR, ANCHOR TO TOP CHORD
 ETC.
 SEC. 104.2.1.2, TABLE 2306.1 OF CITY
 AMENDMENTS TO FBC 2001.
 5-DRAWINGS TO PROVIDE ALL INFORMATION
 AS REQUIRED BY SEC. 1606.1.7 FBC 2001.
 6-ROOF FRAMING LAYOUT ON MAIN ROOF WAS
 CHANGED FROM ORIGINAL DWGS. SPECIFY
 ROOF TRUSS CONNECTORS FOR MODIFIED
 TRUSSES. SEC. 104.2.1.2 CITY AMENDMENT
 7-CLARIFY WHY IS THE TRUSS MANUFACTURER
 RESPONSIBLE TO VERIFY IF EXISTING
 TRUSSES WILL TAKE THE ADDITIONAL LOAD.
 THE DESIGNER IS THE ONE WHO VERIFIES
 THAT EXISTING STRUCTURE WILL BE ABLE
 TO SUPPORT THE ADDITIONAL LOAD OR
 REINFORCE IT AS REQUIRED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-PROVIDE CERTIFICATE OF AUTHORIZATION
 FOR THE ENGINEERING AND ARCHITECTURAL
 BUSINESS AS REQUIRED BY CHAPTER 471
 AND 481 FLORIDA STATUTES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-05 Cont ID  
Sent By csiegber Date 2004-09-22 Time 15:20 Rev Time 2.00
Received By jgomez Date 2004-03-04 Time 14:52 Sent To PC
Notes
2004-03-04 00:00:00BUILDING REVIEW PROVISO:
 1-PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL UNDER A SEPARATE PERMIT (NO
 FEES, AS PER NEIL MELICK) FOR:
 A)FIXED WINDOWS WITH SIZE AS SHOWN ON
 PLANS AT LIVING AND BREAKFAST AREAS.
 B)GARAGE DOORS WITH DRAWINGS SHOWING
 MODELS TO BE USED.
  
 2-PROVIDE COMPLETE & LEGIBLE INFORMATION
 FOR FIREPLACE. UL LISTING AND COMPLETE
 INTALLATION SPECS.
 3-REVISE ROOF PLANS, EXTERIOR ELEVATIONS
 AND CHIMNEY FRAMING DETAILS/SECTION
 AND PLAN TO MATCH ACTUAL LOCATION OF
 CHIMNEY. SEE FLOOR PLAN FOR EXACT
 LOCATION. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-02-09 Cont ID  
Sent By mmclean Date 2004-03-04 Time 14:42 Rev Time 2.00
Received By jgomez Date 2004-02-09 Time 17:52 Sent To PC
Notes
2004-02-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE FLORIDA PRODUCT APPROVAL OR
 COMPLETE SITE SPECIFIC PRODUCT APPRO-
 VAL FOR ALL DOOR AND WINDOW TYPES (SEE
 PLANS FOR SIZES AND ASSEMBLIES SHOWN),
 ROOF TILE, MULLIONS AND ALL STRUCTURAL
 CONNECTORS.
 2-ARCHITECT TO PROVIDE ALL INFO. REQ'D
 BY CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING DWGS FOR PUBLIC RECORDS.
 SEE COMMENTS BY ELECTRICAL & PLUMBING
 PLAN REVIEWERS.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-ARCHITECT TO PROVIDE ALL INFORMATION
 AS REQUIRED AND LISTED ON SECTION
 1606.1.7 FBC 2001.
 5-PROVIDE COMPLETE INSTALLATION SPECS
 AND LEGIBLE DRAWINGS FOR VENTLESS
 FIREPLACE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT (561)
 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-02 Cont ID  
Sent By pkrauss Date 2004-01-26 Time 16:03 Rev Time 2.50
Received By jgomez Date 2004-01-02 Time 09:30 Sent To PC
Notes
2004-01-02 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT NEED CORRECT AND COMPLETE
 INFORMATION ON TITLE BLOCK AS REQUIRED
 BY CHAPTER 481 FLORIDA STATUTES WHEN
 SUBMITTING INFORMATION FOR PUBLIC
 RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 LISTED ON SEC.1606.1.7 FBC 2001.
 4-DESIGN PARAMETERS TO INCLUDE THE 30PSF
 OR 10PSF ATTIC LIVE LOAD AS REQ'D BY
 TABLE 1604.1 FBC 2001.
 5-PROVIDE FLORIDA PRODUCT APPROVAL OR
 COMPLETE SITE SPECIFIC ENGINEERING FOR
 ALL DOORS, WINDOWS, MULLIONS, ROOF
 TILE, TRUSS CONNECTORS, GARAGE DOORS.
 VISIT WWW.FLORIDABUILDING.ORG FOR
 INFORMATION REQUIRED TO BE SUBMITTED.
 **NOTE: CHECK SIZES AND TYPES OF WINDOWS
 DOORS SHOWN ON PLANS. PRODUCT APPROVAL
 NEED TO MATCH THEM. THIS INCLUDES
 SPECIAL WINDOW AT BREAKFAST AREA.
 6-PROVIDE UL LISTING AND COMPLETE INFO.
 FOR FIREPLACE AND BBQ. SEC. 2806 AND
 2808 FBC 2001.
 7-REVISE TRUSS ANCHOR SCHEDULE TO COMPLY
 WITH SEC. 1609.4.3 FBC 2001.
 **NOTE: SPECIFY FASTENER TYPE/NUMBER AS
 SHOWN ON REVISED CATALOGUE. OTHERWISE,
 PROVIDE ENGINEERING CALCULATIONS FOR
 DIFFERENT SPECIFICATIONS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING INSTALLATION AT ENTRY PORCH
 WHEN USING STUCCO. SEE ASTM C-926 AND
 ASTM C-1063 FOR STUCCO THICKNESS REQ'D
 AND TYPE,SIZE AND SPACING OF FASTENER
 REQUIRED. (INFO.SUBMITTED ON SHEET A-6
 ANDA-7 IS INCORRECT & NOT COMPLETE)
 9-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 10-DRAWINGS NEED TO BE STAMPED BY THE
 COUNTY FOR IMPACT FEES.
 11-PLEASE CLOUD ALL CORRECTIONS/REVISION
 DONE TO NEW DRAWINGS TO EXPEDITE THE
 REVIEW PROCESS.
 12-SHEET A-7:A)CLARIFY WHERE ARE DETAILS
 P AND L SHOWN ON ROOF FRAMING PLAN?.
 B)MISSING SOME CONNECTION DETAILS. EG:
 CONNECTIONS FOR COLS AT ENTRY PORCH.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 C)ROOF FRAMING PLAN IS MISSING CHIMNEY
 LOCATION AND FRAMING AROUND IT. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ @ 805-6712.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-17 Cont ID  
Sent By dpalmer Date 2003-12-12 Time 11:36 Rev Time 4.00
Received By jgomez Date 2003-11-17 Time 14:15 Sent To PC
Notes
2003-11-17 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO PROVIDE ALL INFORMATION
 REQ'D BY CHAPTER 481 FLORIDA STATUTES.
 INCLUDING NAME OF PERSON SIGNING THE
 PLANS. SEE 61G1-16.004 F.A.C.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-ARCHITECT TO PROVIDE ALL INFORMATION
 LISTED ON SEC. 1606.1.7 FBC 2001.
 4-DESIGN PARAMETERS INFORMATION TO
 INCLUDE THE ATTIC LIVE LOAD (10PSF OR
 30PSF) AS REQUIRED BY TABLE 1604.1 FBC
 5-SPECIFY JOINTS IN CONCRETE SLAB AND/OR
 SPECIFY WWM SUPPORTS AND SPACING IN
 CONCRETE SLAB. SEE SEC. 1909.3 FBC2001
 6-AS OF OCT. 1ST 2003 CONTRACTOR NEEDS
 TO PROVIDE FLORIDA PRODUCT APPROVAL OR
 LOCAL PRODUCT APPROVAL. SEE QUESTIONS
 & ANSWERS FOR PRODUCT APPROVAL LAW ON
 WWW.FLORIDABUILDING.ORG FOR PROPER
 INFORMATION TO BE SUBMITTED.
 **NOTE:SEE COMMENTS ON PRODUCT APPROVALS
 SUBMITTED. PROVIDE PRODUCT APPROVAL
 FOR ACTUAL TYPE OF WINDOWS/DOORS TO BE
 INSTALLED.
 **PRODUCT APPROVAL REQ'D FOR: ROOF TILE,
 SINGLE HUNG WINDOWS, FIXED AND ARCHED
 WINDOWS (CHECK SIZES ON PLANS), FRENCH
 DOORS WITH SIDELITES (SEE PLANS),
 ENTRY DOORS, GARAGE DOORS, MULLIONS.
 7-CLARIFY IF USING IMPACT WINDOWS AND
 DOORS OR PROVIDE COMPLETE INFORMATION
 FOR STORM SHUTTERS.
 8-PROVIDE UL LISTING AND COMPLETE SPECS
 FOR FIREPLACE AND BBQ. AS REQUIRED BY
 SEC. 2806 AND 2808 FBC 2001.
 9-PROVIDE COMPLETE DETAIL/SECTION AT
 INSTALLATION OF FIXED WINDOWS TO
 MULLIONS AT BREAKFAST WINDOW. SPECIFY
 ALL MATERIALS AND FASTENERS. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-REVISE/TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC 2001, WHICH DOESN'T ALLOW
 THE STEEL STRESS INCREASE TO BE USED.
 **NOTE: SEE USP 2003 CATALOGUE, WHICH
 IS ALREADY REVISED.PROVIDE ENGINEERING
 CALCS FOR CONNECTORS W/ FASTENER TYPE,
 NUMBER AND VALUES OTHER THAN THOSE
 PUBLISED ON THE CATALOGUE. ALSO, CHECK
 CATALOGUE FOR CORRECT DESCRIPTION OF
 CONNECTORS.
 11-PROVIDE STRUCTURAL BUCK DETAIL FOR
 ENTRY DOORS WHEN REQUIRED BUCK NEEDS
 TO BE 2X AS REQUIRED BY THE PRODUCT
 APPROVAL. SAME FOR ARCHED WINDOWS. SEE
 CORRESPONDING PRODUCT APPROVALS.SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 12-PROVIDE DETAIL/SPECIFICATIONS FOR
 CEILING INSTALLATION AT ENTRY & REAR
 PORCH. SPECIFY MATERIALS/FASTENER SIZE
 SEE ASTM C-926 AND ASTM C-1063.
 SEC. 2504.2 FBC 2001.
 13-SPECIFY ROOF TILE FASTENERS. SEE SEC.
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 14-LIBRARY ROOM MAY BE USED FOR SLEEPING
 PURPOSES. PROVIDE EGRESS FROM THIS RM
 OR ARCHITECT TO CLEARLY WRITE NOTE ON
 THIS ROOM THAT "THIS ROOM IS NOT TO BE
 USED FOR SLEEPING PURPOSES" AS REQ'D
 BY THE BUILDING OFFICIAL AND SECTION
 1005.4 FBC 2001.
 15-SHEET A-1: REVISE/UPDATE ALL NOTES
 AS REQUIRED. SEE COMMENTS ON PLANS AND
 RETURN REVIEWED SET TO EXPEDITE THE
 REVIEW PROCESS.
 16-SHEET A-2: A)SPECIFY COLUMN C-4 SHOWN
 ON FOUNDATION PLAN.
 B)UPDATE NOTES. SEE COMMENTS ON PLANS.
 17-SHEET A-3: SPECIFY SAFETY GLASS WHERE
 REQ'D. SEC. 2405.2 FBC 2001.
 18-SHEET A-7:CONNECTOR J IS FOR WOOD
 TO WOOD CONNECTION, BUT IS SPECIFIED
 FOR MASONRY INSTALLATION. CLARIFY. SEE
 COMMENTS ON ROOF FRAMING PLAN.
 19-SHEET A-8: A)UPDATE NOTES.
 B)CHIMNEY DETAIL. STUCCO TO BE 7/8" MIN.
 AS REQ'D BY ASTM C-926.
 C)CONNECTION DETAIL E IS INCOMPLETE.
 DOESN'T SPECIFY ANCHORS AND SIZES.
 ALSO, IS NOT CLEAR WHICH ONE TO BE
 USED ON ROOF FRAMING PLAN ACCORDING TO
 SPECIFIC LOCATION. CLARIFY AS REQ'D.
 D)CLARIFY ONE STORY WALL SECTION. FOOT'G
 SIZE. NEED 4"MIN. ABOVE GRADE AND 12"
 MIN. BELOW GRADE.
 **SPECIFY FIREBLOCKING. SEC. 2305 FBC.
 **VENTILATION IS FOR ENTIRE ROOF. NOT
 JUST FOR LIVING AREA. SEC 2309.7 FBC
 E)SEE COMMENTS ON SHEET A-7 AND RETURN
 REVIEWED SET TO EXPEDITE REVIEW.
  
 NOTE:
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2005-01-07 Cont ID  
Sent By dpalmer Date 2005-01-07 Time 12:03 Rev Time 0.33
Received By dpalmer Date 2005-01-07 Time 11:43 Sent To  
Notes
2005-01-07 00:00:00REDLINED GROUNDING ELECTRODE TO BE 1/0
 PER 310.15B6, 250.66
 MISSING EQUIPM GRND FROM PANEL "B" TO
 "C". 250.122

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-02-20 Cont ID  
Sent By dpalmer Date 2004-02-20 Time 06:28 Rev Time 0.33
Received By dpalmer Date 2004-02-20 Time 06:28 Sent To P
Notes
2004-02-20 00:00:00** PANEL "B" SHOWS CONDUCTOR SIZE FOR
 PANEL "C" AS #6, REDLINED TO SEE RISER.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-19 Time 16:38 Rev Time 0.50
Received By dpalmer Date 2004-01-20 Time 16:43 Sent To P
Notes
2004-01-20 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE INCLUDE ALL LICENSE #`S
 ON TITLE BLOCK. THIS INCLUDES ANY
 CERTIFICATE OF AUTHORIZATION #'S.
 PLEASE SEE FS 481.219 SUB-SECTION (2),
 IF OPERATING UNDER NAME OTHER THAN
 INDIVIDUAL, A CA# IS REQ'D. TITLE BLOCK
 REFLECTS STENE ASSOCIATES.
 PLEASE SEE ATTACHED LICENSE INFORMATION
 AS PRINTED FROM DBPR.
 PLEASE ALSO NOTE: IN EFFORT TO CONTACT
 OFFICE OF ABOVE MENTIONED. PHONE #
 LISTED ON TITLE BLCOK HAS BEEN DIS-
 -CONNECTED AND NO LONGER IN SERVICE.
 PLEASE PROVIDE ALL CORRECT INFORMATION
 AS REQ`D UNDER FS AND FAC. 61G1-16.004
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-12 Cont ID  
Sent By csiegber Date 2004-01-14 Time 13:06 Rev Time 2.00
Received By dpalmer Date 2003-12-12 Time 11:35 Sent To B
Notes
2003-12-12 00:00:00***************** UNSAT ****************
  
 PLEASE SEE THAT THERE ARE NOW SOME NEW
 COMMENTS DUE TO RISER/PANEL SCHEDULE
 CHANGING, ALSO SOME COMMENT FROM FIRST
 REVIEW NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE PLANS, ARCH'S LICENSE
 # DOES NOT SEEM TOCORRELATE WITH SAID
 SEAL. PLEASE ALSO PLEASE MAKE SURE ALL
 SHEETS CONTAIN A CLEAR AND VISABLE
 IMPRESSION TYPE SEAL.
 ALL ABOVE PER FS 481.221 AND FAC 61G1-16
 .004.
  
 2)NOTE: PLEASE CORRELATE RISER DIAGRAM
 AND PANELS/SCHEDULES.
 PANELS ARE NOW SHOWN AS MCB AND RISER
 INDICATES MLO AND DISC'S.?
  
 3)NOTE: PLEASE SEE THAT AIC RATING(S)
 ARE NOW SHOWN FOR PANELS AND BREAKERS
 HOWEVER, NO AIC RATINGS ARE SHOWN FOR
 MAINS. 110.9/ 215.5
  
 4)NOTE: PLEASE SEE 210.8 FOR RECEPT
 REQ'D TO BE SHOWN AS GFI/GFI PROTECTED
 IN GARAGE.
  
 5)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 BEDROOM #3./BRKFAST AREA WALL.
  
 6)NOTE: PLEASE SEE FS 553.80(2)(B).
 PLEASE SEE ATTACHED COPY AND BE SURE ALL
 COMMENTS ARE ADDRESSED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 561-805-6717

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-12-10 Time 15:21 Rev Time 1.00
Received By dpalmer Date 2003-10-22 Time 06:21 Sent To M
Notes
2003-10-22 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 ,
 PLEASE SEE THAT ALL LICENSE INFORMATION
 IS REQ'D TO BE ON TITLE BLOCK. PLEASE
 INCLUDE FIRM'S # ALONG WITH ARCH'S#.
 PLEASE SEE THAT RAISED SEALED MUST BE
 CLEARLY VISABLE AND FULLY READABLE.
  
 2)NOTE: PLEASE SIZE SEC'S FOR A 400A
 SERVICE PER 310.15(B)(6) 400MCM MIN.
  
 3)NOTE: PLEASE INCLUDE BLDG FOOTER
 STEEL AS PART OF THE GROUNDING ELECTRODE
 SYSTEM AS REQ'D IN 250.50
  
 4)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL SERVICE EQUIPMENT. MAINS, PANELS AND
 BREAKERS ARE ALL REQ'D TO BE RATED FOR
 THE AVAILABLE FAULT CURRENT. 110.9
  
 5)NOTE: PLEASE SEE PLAN, SHOWS ONLY ONE
 DISC AT SERVICE LOCATION.
  
 6)NOTE: PLEASE LIST ALL THE REQ'D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PLEASE SEE THAT WE ARE NOW
 UNDER THE 2002 NEC AND ARC FAULT PROTECT
 -ION IS NO LONGER JUST RTECEPTS.
  
 7)NOTE: PLEASE PROVIDE ROOM DESIGNATION
 FOR ALL ROOMS.
  
 8)NOTE: PLEASE MOVE SD IN MASTER BEDRM?
 INTO SLEEPING AREA. NFPA-72 8-4
  
 9)NOTE: PLEASE SEE THAT RECEPTS ARE TO
 BE W/IN 3' OF LAV/SINKS. (MAST)?
 210.52D
  
 10)NOTE: SD'S ARE REQ'D INSIDE AND OUT-
 -SIDE ALL SLEEPING ROOMS AND ALSO
 ADAPTABLE SLEEPING RMS. THESE RMS THAT
 MAY CONTAIN A CLOSET OR BATH RM.
 NFPA-72
  
 11)NOTE: PLEASE SEE MISSING RECEPT IN-
 FRONT OF DWELLING UNIT. 210.52E
  
 12)NOTE: PLEASE SHOW RECEPT REQ'D FOR
 GARAGE (210.52G) AS GFI. 210.8
  
 13)NOTE: PLEASE SHOW MISSING REQ'D LT
 AND RECEPT FOR ATTIC. 210.70 AND 210.63
  
 14)NOTE: PLEASE SEE 210.52 FOR MISSING
 RECEPTS.
  
 15)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210.8(A)(6)
  
 16)NOTE: PLEASE CLARIFY CIRCUIT #11?
 SHOWN AS 15A/ #14?
  
 17)NOTE: PLEASE SEE THAT AN ADDITIONAL
 RECEPT IS REQ'D AT THE END OF PENINSULAR
 PLEASE SEE 210.52C 1-5
  
 PLEASE SEE THAT ONE SET OF PLANS HAVE
 MOST OF THE ABOVE ITEMS HIGHLIGHTED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-01-05 Cont ID  
Sent By mjacobs Date 2005-01-05 Time 14:34 Rev Time 0.00
Received By mjacobs Date 2005-01-05 Time 14:34 Sent To E
Notes
2005-01-05 00:00:00TO "DP" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-09-22 Cont ID  
Sent By csiegber Date 2004-09-22 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-09-22 Time 15:20 Sent To B
Notes
2004-09-22 00:00:00TO JG DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-02-19 Time 16:38 Rev Time 0.00
Received By csiegber Date 2004-02-19 Time 16:38 Sent To E
Notes
2004-02-19 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 16:17 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 16:17 Sent To P
Notes
2004-02-12 00:00:00TO KS BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-01-14 Cont ID  
Sent By csiegber Date 2004-01-14 Time 13:06 Rev Time 0.00
Received By csiegber Date 2004-01-14 Time 13:06 Sent To E
Notes
2004-01-14 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-01-02 Cont ID  
Sent By csiegber Date 2003-12-10 Time 15:21 Rev Time 0.00
Received By jgomez Date 2003-12-10 Time 15:21 Sent To PC
Notes
2003-12-10 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 16:17 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 12:48 Sent To PC
Notes
2003-11-17 00:00:00CALLED CONTRACTOR. PLANS UNDER "C".
2003-10-16 00:00:0010/03/03TO Z
 10/15/03TO Z RESUB
 10/16/03TO SFD RACK/E

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-26 Cont ID  
Sent By kstevens Date 2004-03-01 Time 07:39 Rev Time 0.33
Received By pkrauss Date 2004-01-26 Time 16:00 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-10-29 Cont ID  
Sent By kstevens Date 2004-01-21 Time 17:15 Rev Time 0.25
Received By hmoser Date 2003-10-29 Time 17:30 Sent To B
Notes
2003-10-29 00:00:00NO MECHANICAL PLANS.10/29/03 H.M.

Review Stop P PLUMBING
Rev No 5 Status P Date 2005-01-22 Cont ID  
Sent By jleech Date 2005-01-22 Time 14:27 Rev Time 0.50
Received By jleech Date 2005-01-22 Time 14:27 Sent To  
Notes
2005-01-22 00:00:00AS BUILTS BY PLUMBER.

Review Stop P PLUMBING
Rev No 4 Status P Date 2004-03-01 Cont ID  
Sent By kstevens Date 2004-03-01 Time 07:38 Rev Time 0.50
Received By kstevens Date 2004-03-01 Time 07:38 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2004-02-18 Cont ID  
Sent By dpalmer Date 2004-02-20 Time 06:28 Rev Time 0.25
Received By kstevens Date 2004-02-18 Time 08:00 Sent To E
Notes
2004-02-18 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) COMMENT FROM PREVIOUS REVIEW NOT
 ADDRESSED. CERTIFICATE OF AUTHORIZATION
 REQUIRED FOR ARCHITECTURAL COMPANY.
 FS 481.219(2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-21 Cont ID  
Sent By csiegber Date 2004-02-12 Time 16:17 Rev Time 0.33
Received By kstevens Date 2004-01-21 Time 17:13 Sent To M
Notes
2004-01-21 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) CERTIFICATE OF AUTHORIZATION REQUIRED
 ON TITLE BLOCK PER FS 481.219 SUBSECTION
 (2).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2004-01-20 Time 16:43 Rev Time 0.50
Received By jleech Date 2003-10-28 Time 18:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2004-03-04 Cont ID  
Sent By mmclean Date 2004-03-04 Time 14:42 Rev Time 0.00
Received By mmclean Date 2004-03-04 Time 14:42 Sent To B
Notes
2004-03-04 00:00:00RE-STAMP SITE PLAN MM

Review Stop Z ZONING
Rev No 2 Status P Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-10-16 Time 11:28 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-15 Time 12:04 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-10-06 00:00:0010/6/03 DENIED, OVER THE HEIGHT
 REQUIREMENT OF 4FT.MAX HEIGHT REQ IS
 30FT WITH 10% ADDT'L OF 3FT. CALLED
 LEFT MSG FOR HENRY FILE C MM