Plan Review Details - Permit 03092021
Plan Review Stops For Permit 03092021
Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2005-06-13 Cont ID  
Sent By lmartine Date 2005-06-13 Time 15:36 Rev Time 0.00
Received By lmartine Date 2005-06-13 Time 15:35 Sent To  
Notes
2005-06-13 00:00:00SITE SPECIFIC FOR ENTRY DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2005-06-01 Cont ID  
Sent By shill Date 2005-06-01 Time 15:53 Rev Time 0.50
Received By shill Date 2005-06-01 Time 15:53 Sent To  
Notes
2005-06-01 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST.CERTIFICATE OF
 AUTHORIZATION NUMBER FOR CATEGORY 5
 ENGINEERING SERVICES, INC. IS TO BE ON
 THE TITLE BLOCK FAC61G15-23.002.
  
 2.)SUBMITTAL INCOMPLETE.THE TEST
 REPORTS FOR THE FRAME AND HARDWARE IS
 NOT INCLUDED.
  
 3.)HAVE THE COMPLETE PACKAGE REVIEWED
 BY DOR.
  
 4.)IN ADDRESSING QUALITY ASSURANCE,
 PLEASE SUBMIT A SIGNED AND SEALED
 LETTER.THE DOOR ASSEMBLY AS WELL AS
 THE INSTALLED ASSEMBLY REQUIRE QUALITY
 ASSURANCE.PLEASE ADDRESS BOTH IN THE
 LETTER.

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2005-04-25 Cont ID  
Sent By shill Date 2005-04-25 Time 08:52 Rev Time 0.45
Received By shill Date 2005-04-25 Time 08:17 Sent To PC
Notes
2005-04-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL,BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLEASE COMPLETE THE ATTACHED
 APPLICATION FOR SITE SPECIFIC PRODUCT
 APPROVAL.
  
 2.)SEE ATTACHED VALIDATION CHECKLIST
 TO ASSIST YOU IN FILLING OUT THIS
 APPLICATION FORM.MORE INFORMATION IS
 AVAILABLE AT WWW.FLORIDABUILDING.ORG,
 PRODUCT APPROVAL.
  
 3.)THE ENGINEERING FOR THE DOOR
 SPECIFICALLY EXCLUDES THE FRAME.PLEASE
 INCLUDE IN THE ENGINEERING.THE
 ENGINEER IS TO CERTIFY THAT THE ENTIRE
 ASSEMBLY IS CODE COMPLIANT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2005-03-02 Cont ID  
Sent By shill Date 2005-03-02 Time 15:49 Rev Time 1.00
Received By shill Date 2005-03-02 Time 15:49 Sent To PC
Notes
2005-03-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.) THE CERTIFICATE OF AUTHORIZATION
 NUMBER IS TO BE ON ENGINEERING
 DOCUMENTS, FAC61G15-23.002.
  
 2.)THE ENGINEERING FOR THE DOOR
 INCLUDES THE DOOR ITSELF, BUT NOT THE
 OTHER COMPONENTS (FRAME, HARDWARE).
 PROVIDE TEST REPORTS FOR THE OTHER
 COMPONENTS OF THE DOOR ASSEMBLY.IF THE
 TEST REPORTS DO NOT GIVE GUIDELINES FOR
 THE DOOR ASSEMBLY (PLACEMENT AND NUMBER
 OF HINGES, HOW THE HINGES WILL BE
 ATTACHED, ETC.) PROVIDE AN ENGINEERED
 SPECIFICATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-01-12 Cont ID  
Sent By shill Date 2005-01-12 Time 11:18 Rev Time 0.00
Received By SHILL Date 2005-01-12 Time 14:46 Sent To PC
Notes
2005-01-12 00:00:00LETTER REVISING DP FOR GARAGE DOORS
 +35/-48
 PREPARED BY BIJAN PARSSI, PE

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-12-23 Cont ID  
Sent By shill Date 2004-12-23 Time 12:21 Rev Time 0.00
Received By shill Date 2004-12-23 Time 11:18 Sent To PC
Notes
2004-12-23 00:00:00PRODUCT APPROVALS, DOORS & WINDOWS
 REVISED A.0, A.01, A1.1, A4

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-12-23 Cont ID  
Sent By shill Date 2004-12-23 Time 10:15 Rev Time 0.00
Received By shill Date 2004-12-23 Time 10:15 Sent To PC
Notes
2004-12-23 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOA SUBMITTED FOR THE DOUBLE
 OUTSWING DOOR WITH SIDELITES
 (01-0314.28) DOES NOT COMPLY WITH THE
 DESIGN PRESSURES DETERMINED BY THE
 ENGINEER (NOA HAS A LIMITATION OF
 +-55).
 ALSO IS NOT APPROVED FOR USE WHERE
 WATER
 INFILTRATION REQUIREMENT IS NEEDED.
 THE
 SIDELITES REQUIRE IMPACT PROTECTION.A
 NOTE AT THE TOP OF THE NOA STATES
 "GARAGE 3'0" ENTRY".IF THIS NOA IS
 FOR
 THE DOOR FROM THE INSIDE OF THE GARAGE
 TO THE HALLWAY, A TEST REPORT IS NOT
 REQUIRED AS IT IS CONSIDERED AN
 INTERIOR
 DOOR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-09-21 Cont ID  
Sent By mmclean Date 2004-10-12 Time 14:32 Rev Time 2.00
Received By shill Date 2004-09-21 Time 17:14 Sent To Z
Notes
2004-09-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IT APPEARS ON A4 THAT YOU ARE
 ENCLOSING SOME OF THE GARAGE AREA TO BE
 A HALLWAY AND LAUNDRY ROOM.PLEASE
 REVISE THE AREA CALCS.IMPACT FEES
 MAY BE DUE; 233-5025.THE PLANS MUST
 BE STAMPED AND THE RECEIPT ATTACHED TO
 THE APPLICATION.
  
 2.)THE SCOPE OF WORK ON THIS PERMIT
 HAS CHANGED.THE DECLARED VALUE ON
 THE APPLICATION OF $50K APPEARS LOW.
 PROVIDE A NEW VALUE FOR THE WORK TO
 BE DONE, INCLUDING THE NEW GARAGE DOOR
 AND THE ROOF.IF THE VALUE DECLARED
 IS NOT REASONABLE, AN ESTIMATE WILL BE
 DONE FOR YOU USING MARSHALL & SWIFT.
  
 3.)THE PRODUCT APPROVALS PREVIOUSLY
 REQUESTED, CUSTOM DOOR, IMPACT AWNING
 WINDOW, IMPACT FIXED WINDOW WERE NOT
 SUBMITTED.
  
 4.)THE PLAN SHOWS THAT THE GARAGE DOOR
 IS TO BE REPLACED.PROVIDE DESIGN
 PRESSURES FOR THE DOOR(OPTIONAL) AND
 SUBMIT COMPLIANT PRODUCT APPROVALS. IF A
 NEW DESIGN PRESSURE FOR THE GARAGE DOOR
 IS NOT SUBMITTED, THE DP OF +45/-62
 STATED ON THE LETTER FROM B.PARSI, PE
 DATED 8/19/04 WILL BE APPLICABLE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-07-29 Cont ID  
Sent By shill Date 2004-07-29 Time 11:42 Rev Time 1.50
Received By shill Date 2004-07-29 Time 11:32 Sent To M
Notes
2004-07-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)IN THE FUTURE, PLEASE CLOUD ALL
 CHANGES.FOR THIS REVISION, HOWEVER,
 FOR THE A&S SHEETS PLEASE DO NOT CHANGE
 OUT UNLESS AFFECTED BY THIS CORRECTION
 LIST AS THESE SHEETS HAVE ALREADY
 BEEN REVIEWED AND STAMPED.
  
 2.)SUBMIT PRODUCT APPROVALS FOR THE
 CUSTOM DOOR.
  
 3.)1-A5, FIREBLOCKING REQUIRED FBC
 705.3.1.1.
  
 4.)A7 SPECIFIES TO ATTACH THE LUCITE
 RODS "AS REQUIRED".THE LUCITE RODS
 SERVE AS A GUARDRAIL AND ARE TO COMPLY
 WITH FBC1606.2.2, FBC1015.SHOW
 DIMENSIONS, DESIGN CRITERIA(FBC1606.2.2)
 AND ATTACHMENT COMPLYING WITH THIS
 DESIGN CRITERIA.DO NOT JUST GIVE
 CODE SECTIONS PLEASE.
  
 5.)SPECIFY ATTACHMENT FOR THE BRACKETS
 FOR THE HANDRAIL, TO COMPLY WITH
 FBC1606.2.1, 5-A7.
  
 6.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR THE AWNING AND FIXED
 WINDOWS.IF THEY ARE NOT IMPACT,
 PROVIDE TWO COPIES OF THE SHUTTER
 PRODUCT APPROVALS.
  
 7.)TO EXPEDITE PLAN REVIEW, PLEASE
 PROVIDE DESIGN PRESSURES ON THE
 WINDOW AND DOOR SCHEDULES.IT APPEARS
 THAT SOME OF THE PRODUCTS ARE NON
 COMPLIANT FROM THE TABLE ON S5.WHAT
 ARE THE NUMBERS +45/-62 (DESIGN WIND
 PRESSURE) FOR; THIS IS WHERE THE
 COMPONENTS & CLADDING PRESSURES NORMALLY
 ARE STATED PER FBC1606.1.7.SINCE IT
 UNCLEAR WHAT THE DESIGN PRESSURES ARE,
 PLEASE INCLUDE ON A TABLE AND SUBMIT
 PRODUCT APPROVALS WHICH ARE COMPLIANT.
  
 8.)THE STRUCTURAL DETAILS SUBMITTED
 WITH THIS REVISION HAVE BEEN REVIEWED
 AND A COPY RETAINED.DO NOT RESUBMIT
 WITH THE PLANS; THIS IS YOUR APPROVED
 JOB COPY.
  
 WHEN RESUBMITTING, PLEASE REPLACE ONLY
 SHEETS WHICH HAVE CHANGED.SUBMIT OLD
 SHEETS SEPARATELY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-14 Cont ID  
Sent By jleech Date 2004-07-27 Time 16:21 Rev Time 1.50
Received By shill Date 2003-12-14 Time 17:21 Sent To  
Notes
2003-12-14 00:00:00PROVISO - ARCHITECT TO SUBMIT AN
 ENERGY CALC COVER SHEET SEALED (SIGNATUR
 NO SEAL) - MAILED HIM A COPY TO SEAL &
 RETURN

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-11-13 Cont ID  
Sent By kstevens Date 2003-11-05 Time 18:58 Rev Time 2.50
Received By sthyng Date 2003-11-13 Time 17:04 Sent To Z
Notes
2003-11-13 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG (HILL)
 BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 2.)THE WINDOW F (SHOWER), A3, IS TO
 COMPLY WITH FBC2405.1 (SAFETY GLASS).
  
 3.)FIREBLOCK REQUIRED AT STAIRS (TOP
 AND BOTTOM OF RUN), FBC2305.1.4(3).
  
 4.) DETAIL 1-A.4, TWO RISERS AND A
 TREAD TO COMPLY WITH FBC1007.3(1).
  
 5.)SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC, FBC13-101.2.
  
 6.)PROVIDE TWO LEGIBLE COPIES OF
 PRODUCT APPROVALS FOR:
 CASEMENT WINDOWS
 SLIDING GLASS DOORS
 CIRCULAR SKYLIGHTS
 FRENCH DOORS

Review Stop E ELECTRICAL
Rev No 7 Status P Date 2005-03-21 Cont ID  
Sent By btrobaug Date 2005-03-21 Time 13:18 Rev Time 0.50
Received By btrobaug Date 2005-03-21 Time 13:18 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2005-02-22 Cont ID  
Sent By btrobaug Date 2005-02-22 Time 14:08 Rev Time 0.50
Received By btrobaug Date 2005-02-22 Time 13:36 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2005-01-20 Cont ID  
Sent By btrobaug Date 2005-01-20 Time 12:47 Rev Time 0.50
Received By btrobaug Date 2005-01-13 Time 14:46 Sent To  
Notes
2005-01-20 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE "PVC BOX" ON THE RISER MUST
 COMPLY WITH ARTICLE 314.28(A), PLEASE
 SIZE ACCORDINGLY.
  
 2} EQUIPMENT GROUNDING CONDUCTORS MUST
 BE RAN WITH APPROPRIATE FEEDERS. SEE
 REVIEWED RISER.
  
 3} PLEASE NOTE 3/0 FEEDERS SHOWN FROM
 THE 200 AMP DISCONNECT TO THE 100 AMP
 SUB PANEL ON RISER, BUT #3 FEEDERS SHOWN
 ON THE PANEL SCHEDULE. PLEASE
 CORRELATE.
  
 4} PLEASE SEE CIRCUIT #32 IN THE 200 AMP
 PANEL IS A BATH CIRCUIT, BUT SHOWN AS
 "EXERCISE" ON THE SCEDULE . PLEASE CHECK
 ALL CIRCUIT NUMBERS ON THE SCHEDULE WITH
 NUMBERS ON PLAN.
  
 5} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 6} THE GARAGE RECEPTACLE(S) MUST COMPLY
 WITH 210.8(A)(2) FOR GFCI PROTECTION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-09-20 Cont ID  
Sent By btrobaug Date 2004-09-20 Time 14:51 Rev Time 0.75
Received By btrobaug Date 2004-09-01 Time 07:51 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-07-21 Cont ID  
Sent By btrobaug Date 2004-07-21 Time 15:05 Rev Time 0.75
Received By btrobaug Date 2004-07-20 Time 14:12 Sent To P
Notes
2004-07-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE USE SOME RECOGNIZED
 IDENTIFICATION METHOD TO INDICATE
 CHANGES ON THE PLAN. THE REVISION BLOCK
 INDICATES A TRIANGLE BUT NOTHING ON THE
 PLAN.
  
 INDICATE THE SIZE OF THE
 CONDUIT,GUTTERS,RACEWAYS AND ALL FEEDER
 CONDUTOR SIZES INSTALLED IN SAME. ALSO
 SHOW THE LOCATION OF ALL THE SERVICE
 EQUIPMENT SHOWN ON THE RISER DIAGRAM,
 ON THE PLAN IN THE INTENDED LOCATION.
  
 INDICATE THE INTENDED USE OF THE 15 KW
 TRANSFORMER SHOWN ON THE RISER.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-05 Cont ID  
Sent By csiegber Date 2004-07-12 Time 15:20 Rev Time 1.00
Received By btrobaug Date 2003-12-05 Time 12:21 Sent To P
Notes
2003-12-05 00:00:00 
 PROVISO
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE REVISE THE PLANS TO ADDRESS THE
 FOLLOWING COMMENTS AND RESUBMIT FOR
 REVIEW PRIOR TO CALLING ELECTRICAL
 INSPECTIONS.
  
 1} THE FEEDER FROM THE DISCONNECT TO
 THEPANEL IS SHOWN AS CARRYING THE HIGH
 LEG TO THE GUTTER,PLEASE VERIFY.IT
 APPEARS
 TO TERMINATE THERE.
  
 2} THERE MUST BE AN EQUIPMENT GROUND
 RANTO THE PANEL FROM THE DISCONNECT PER
 250.122.
  
 3} PLEASE SHOW HOW THE 60 AMP
 DISCONNECT AT THE GUTTER IS BEING FED.IT
 IS NOT LISTED IN THE THE PANEL SCHEDULE
 FROM THE 200 AMP IF IT IS TAPPED IN THE
 GUTTER PLEASE SHOW TAP CONDUCTOR SIZE.
  
 4} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210-12
  
 6} THE RANGE IN THE LOAD CALC SHOULD BE
 LISTED AT 8000 VA TO COMPLY WITH 220.19.
  
 7} SMOKE DETECTOR MUST BE INSTALLED IN
 THE UPPER LEVEL PER 905.2.2 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 11:03 Rev Time 1.00
Received By btrobaug Date 2003-11-04 Time 10:09 Sent To M
Notes
2003-11-04 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 THE PLAN AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.PLEASE SEE FAC
 FOR INFORMATION REQUIRED (FIRM LICENSE
 NUMBER).
  
 2} PLEASE REVISE THE RISER DIAGRAM TO
 INCLUDE ANY EXISTING PANELS AND SUPPLY
 SCHEDULES OF SAME.ALL EQUIPMENT IN
 CALCS NOT SHOWN ON NEW PANEL.
  
 3} NOTE THE #3 FEEDERS TO THE 200 AMP
 DISCONNECT ARE INCORRECT FOR THE LOAD
 SERVED PER 310.15(B)(6),OR 310.16.ALSO
 NOTE THERE IS NO NEUTRAL INDICATED,AND
 THE #4 GROUND TO THE FIRST MEANS OF
 DISCONNECT PROVIDES A PARALLEL PATH
 WITH THE NEUTRAL(IF THERE WAS ONE). SEE
 250.6(B).
  
 4} THE 200 AMP DISCONNECT ON THE RISER
 SHOWS TWO SETS OF 200 AMP FUSES,THREE
 PHASE? SEE COMMENT #2.
  
 5} SHEET E.1 SHOWS A METER AND TWO
 DISCONNECTS,PLEASE LABEL INTENDED USE.
  
 6} PLEASE CONFIRM THE SERVICE BEING
 THREE PHASE AND THAT A HIGH LEG EXISTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2005-06-01 Cont ID  
Sent By adarroug Date 2005-06-01 Time 09:14 Rev Time 0.00
Received By adarroug Date 2005-06-01 Time 09:14 Sent To B
Notes
2005-06-01 00:00:00TO "SHILL" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2005-04-21 Cont ID  
Sent By adarroug Date 2005-04-21 Time 16:59 Rev Time 0.00
Received By adarroug Date 2005-04-21 Time 16:59 Sent To B
Notes
2005-04-21 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2005-04-15 Cont ID  
Sent By adarroug Date 2005-04-15 Time 11:30 Rev Time 0.00
Received By adarroug Date 2005-04-15 Time 11:30 Sent To Z
Notes
2005-04-15 00:00:00TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2005-03-16 Cont ID  
Sent By adarroug Date 2005-03-16 Time 13:46 Rev Time 0.00
Received By adarroug Date 2005-03-16 Time 13:46 Sent To M
Notes
2005-03-16 00:00:00TO "PKRAUSS" BOX/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2005-03-14 Cont ID  
Sent By adarroug Date 2005-03-14 Time 10:36 Rev Time 0.00
Received By adarroug Date 2005-03-14 Time 10:36 Sent To E
Notes
2005-03-14 00:00:00TO "BTROBAUG" DESK/REVISION

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2005-02-11 Cont ID  
Sent By mjacobs Date 2005-02-11 Time 14:02 Rev Time 0.00
Received By mjacobs Date 2005-02-11 Time 14:02 Sent To E
Notes
2005-02-11 00:00:00TO "BT" DESK/REV.

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 11:44 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 11:44 Sent To E
Notes
2005-01-11 00:00:00TO "BT" DESK./REVISION

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2005-01-11 Time 11:39 Rev Time 0.00
Received By mjacobs Date 2005-01-11 Time 11:39 Sent To B
Notes
2005-01-11 00:00:00TO "SH" DESK/SUBMITTAL. SUBMITTAL CAME
 IN ON 1-6-05, BUT WAS PLACED IN
 INCOMMING ON 1-11-05

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-01-11 Cont ID  
Sent By mjacobs Date 2004-12-07 Time 09:24 Rev Time 0.00
Received By mjacobs Date 2004-12-07 Time 09:24 Sent To M
Notes
2004-12-07 00:00:00SENT TO "M/AC" BOX./REV.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-10-04 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:46 Rev Time 0.00
Received By csiegber Date 2004-10-04 Time 11:46 Sent To Z
Notes
2004-10-04 00:00:00TO Z/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 12:13 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 12:13 Sent To M
Notes
2004-08-31 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-08-23 Cont ID  
Sent By csiegber Date 2004-08-23 Time 09:40 Rev Time 0.00
Received By csiegber Date 2004-08-23 Time 09:40 Sent To  
Notes
2004-08-23 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-12 Cont ID  
Sent By csiegber Date 2004-07-12 Time 15:20 Rev Time 0.00
Received By csiegber Date 2004-07-12 Time 15:20 Sent To E
Notes
2004-07-12 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-04 Cont ID  
Sent By csiegber Date 2003-12-04 Time 11:03 Rev Time 0.00
Received By csiegber Date 2003-12-04 Time 11:02 Sent To E
Notes
2003-12-04 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-12-01 Cont ID  
Sent By mmclean Date 2003-12-03 Time 13:04 Rev Time 0.00
Received By csiegber Date 2003-12-01 Time 16:52 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-12-14 Cont ID  
Sent By csiegber Date 2003-12-14 Time 17:23 Rev Time 0.00
Received By shill Date 2003-09-30 Time 14:18 Sent To  
Notes
2003-10-24 00:00:009/30/03TO Z
 10/24/03TO E

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2005-03-22 Cont ID  
Sent By pkrauss Date 2005-03-22 Time 16:36 Rev Time 0.35
Received By pkrauss Date 2005-03-22 Time 16:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2004-12-17 Cont ID  
Sent By prafter Date 2004-12-17 Time 10:52 Rev Time 0.45
Received By prafter Date 2004-12-17 Time 10:49 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status F Date 2004-09-21 Cont ID  
Sent By pkrauss Date 2004-09-21 Time 06:50 Rev Time 0.00
Received By hmoser Date 2004-09-21 Time 07:23 Sent To  
Notes
2004-09-21 00:00:00DENIED:
 PLAN SHEET M.2 INDICATES "FREE RETURN
 CLOSET".THIS WILL BE CONSIDERED A
 PLENUM AND SHALL BE CONSTRUCTED IN
 ACCORDANCE WITH 2001 FBC CHAPTER 13
 SUB-SECTION 610.1.ABC.3.7, MECHANICAL
 CLOSETS.PLEASE NOTE, PLAN SHEET A.3,
 INDICATES THE AREA FOR A "FREE RETURN"
 HAVING "NEW BUILT-IN CABINETS",RETURN
 AIR PLENUMS CANNOT BE USED AS STORAGE
 AREAS.PLEASE CLARIFY.
  
 PLAN SHEET M.2 HAS THE EXHAUST DUCT &
 IN-LINE FANS IN THE RETURN PLENUM.THIS
 IS NOT PERMITTED AS PER 2001 FBC(M)
 601.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2004-09-17 Cont ID  
Sent By btrobaug Date 2004-09-20 Time 14:52 Rev Time 0.30
Received By pkrauss Date 2004-09-17 Time 10:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-08-31 Time 12:13 Rev Time 0.75
Received By hmoser Date 2004-07-30 Time 14:14 Sent To  
Notes
2004-07-30 00:00:00PLAN DENIED
 1) NEED RETURN AIR DUCT SIZES.
 SIZES MUST MEET 2001FLORIDA BUILDING
 CODE (M) SECTION 601.4
 2) NEED CFM ON DUCT.
 3) NEED RETURN AIR IN LIBRARY ROOM 101
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-15 Cont ID  
Sent By shill Date 2004-07-29 Time 15:23 Rev Time 0.40
Received By pkrauss Date 2003-12-08 Time 14:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-11-05 Cont ID  
Sent By jleech Date 2003-12-06 Time 13:47 Rev Time 0.45
Received By pkrauss Date 2003-11-05 Time 07:33 Sent To P
Notes
2003-11-05 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN AIR SHALL
 BE 1 1/2 TIMES THE CROSS SECTIONAL AREA
 (SQ INCHES) OF THE SUPPLY DUCT ENTERING
 THE ROOM ITS SERVING & THE DOOR HAVING
 UNRESTRICTED 1" UNDERCUT. ALL SUPPLY AIR
 INTO THE MASTER SUITE SHALL BE INCLUDED.
  
 SIZING FOR THRU THE WALL TRANSFER
 GRILLES SHALL USE 50 SQUARE INCHES TO
 100 CFM OF SUPPLY AIR WITH UNRESTRICTED
 1" DOOR UNDERCUT.
  
 DUCTS SHALL NOT BE INSTALLED IN OR
 WITHIN 6" OF THE GROUND PER 2001 FBC(M)
 603.12.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-07-27 Cont ID  
Sent By jleech Date 2004-07-27 Time 16:21 Rev Time 0.33
Received By jleech Date 2004-07-27 Time 16:21 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-06 Cont ID  
Sent By btrobaug Date 2004-07-21 Time 15:05 Rev Time 0.33
Received By jleech Date 2003-12-06 Time 13:46 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-11-05 Cont ID  
Sent By btrobaug Date 2003-12-05 Time 14:11 Rev Time 0.50
Received By kstevens Date 2003-11-05 Time 18:58 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 5 Status P Date 2004-12-30 Cont ID  
Sent By mmclean Date 2004-12-30 Time 14:34 Rev Time 0.00
Received By mmclean Date 2004-12-30 Time 14:34 Sent To B
Notes
2004-12-30 00:00:00APPROVE REVISION PAVERS DRIVEWAY,
 RETURNED TO SAMANTHA HILL

Review Stop Z ZONING
Rev No 4 Status P Date 2004-10-12 Cont ID  
Sent By mmclean Date 2004-10-12 Time 14:32 Rev Time 0.00
Received By mmclean Date 2004-10-12 Time 14:32 Sent To B
Notes
2004-10-12 00:00:00NOTE: MUST PULL A SEPARATE PERMIT FOR
 WALL & DRAWINGS TO SCALE.MUST SPECIFY
 HEIGHT OF WALL AND PROVIDE UTILITY
 EASEMENT APPROVAL.APPROVING RENOVATION
 & ADDITION OF EXISITING SFR MM.RETURN
 PLANS TO SAMANTHA HILL, BLDG PLAN
 REVIEWER.

Review Stop Z ZONING
Rev No 3 Status P Date 2003-12-03 Cont ID  
Sent By csiegber Date 2004-10-04 Time 11:46 Rev Time 0.00
Received By mmclean Date 2003-12-03 Time 13:04 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-12-01 Time 16:52 Rev Time 0.00
Received By mmclean Date 2003-11-17 Time 15:52 Sent To  
Notes
2003-11-17 00:00:0011/17/03 DENIED, NEW SITE PLAN MUST
 SHOW ONLY 3630 N FLAGLER DR ADDITIONS
 (WORK) CALLED CONTR FILE H MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-10-03 Cont ID  
Sent By sthyng Date 2003-11-13 Time 17:13 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-10-03 00:00:0010/03/03 DENIED, NEED TO SHOW THE ADD'T
 ON SURVEY WITH SETBACKS CALLED CONTR
 FILE H MM