| 2003-10-27 00:00:00 | DENIED |
| | |
| | 1) SUBMIT A COPY OF THE PAID RECIEPT FOR |
| | THE COUNTY IMPACT FEES. |
| | |
| | 2) A CORRECTED SURVEY WITH SET BACKS |
| | APPROVED BY ZONING IS REQUIRED BEFORE A |
| | PERMIT WILL BE ISSUED. |
| | |
| | 3) SPECIFY THE SIZE OF THE BATHROOM DOOR |
| | ON THE FLOOR PLAN. |
| | |
| | 4) SPECIFY THE SIZE OF THE GLASS BLOCK |
| | OPENING AT THE MASTER BATHROOM. |
| | |
| | 5) PROVIDE A DETAIL OF THE STEP DOWN |
| | SLAB FOUNDATION AT THE GARAGE. INDICATE |
| | THE LOCATION AND SIZE OF THESTEEL |
| | REINFORCEMENT. |
| | |
| | 6) ON SHEET 4 THERE ARE NO VERTICAL |
| | REINFORCED FILLED CELLS SHOWN AT THE |
| | MASTER BEDROOM WINDOW, DOOR, NOOK WINDOW |
| | AND AT THE CORNERS IN THIS AREA. PLEASE |
| | CORRECT. |
| | |
| | 7) IDENTIFY THE LINTELS AT THE ENTRY |
| | PORCH ON SHEET A4. |
| | |
| | 8) SUBMIT TECHNICAL BULLETIN FROM USP |
| | FOR INVERTED INSTALLATION OF SHA 424 |
| | CONNECTOR. |
| | |
| | 9) FBC 1609 DOES NOT ALLOW A ONE-THIRD |
| | INCREASE IN THE STEEL CALCULATIONS FOR |
| | LOAD COMBINATIONS. PLEASE REVISE THE |
| | UPLIFT VALUE FOR THE HETA 20 ON SHEET 5 |
| | TO 1240#(SEE SIMPSON HIGH WIND-RESISTANT |
| | CATALOG) AND ADJUST THE VALUES OF THE |
| | COMBINED CONNECTORS USING THIS STRAP. |
| | |
| | 10) THE UPLIFT VALUE FOR THE RT24 |
| | CONNECTOR SPECIFIED FOR THE 4X4 POST IS |
| | 1125#. THE VALUE FOR TWO IS 2250#, NOT |
| | 2600#. PLEASE REVISE. |
| | |
| | 11) SPECIFY THE FASTENERS, ANCHOR BOLT |
| | SIZE AND EMBEDMENT AND MANUFACTURER FOR |
| | THE MTT 28B CONNECTOR AT THE 4X4 POST ON |
| | SHEET 5. |
| | |
| | 12) THE ENERGY CALCULATIONS ARE REQUIRED |
| | TO BE SIGNED AND DATED BY THE OWNER/ |
| | AGENT PER FBC CHAPTER 13. |
| | |
| | 13) THE ADDENDUM TO THE SOIL REPORT |
| | LETTER FROM ALLTERRA IS REQUIRED TO BE |
| | SEALED BY THE ENGINEER. |
| | |
| | 14) SUBMIT A KEY PLAN AND INSTALLATION |
| | SCHEDULE FOR THE STORM PANELS. |
| | |
| | 15) REVISE THE GARAGE DOOR BUCK FASTER |
| | SPACING ON SHEET D1 TO CONCUR WITH THE |
| | PRODUCT APPROVAL FOR THE CLOPAY GARAGE |
| | DOOR. |
| | |
| | 16) PROVIDE (2) CURRENT AND COMPLETE |
| | COPIES OF SBCCI OR METRO-DADE PRODUCT |
| | APPROVALS FOR: |
| | - GLASS BLOCK |
| | - GLAZED OUTSWING FRENCH DOORS |
| | - FIXED GLASS EYEBROW WINDOW |
| | - STRUCTURAL MULLIONS |
| | - SLIDING GLASS DOORS |
| | - DOUBLE OUTSWING OPAQUE DOORS AT ENTRY |
| | |
| | 17) THE GLASS BLOCK AT THE MASTER BATH |
| | IS IN A HAZARDOUS LOCATION AND IS |
| | REQUIRED TO HAVE A MINIMUM UNIFORM FACE |
| | THICKNESS OF 0.25" PER FBC 2405.2.2. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |