Plan Review Details - Permit 03091739
Plan Review Stops For Permit 03091739
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-15 Cont ID  
Sent By lsmith Date 2003-10-15 Time 07:27 Rev Time 0.50
Received By lsmith Date 2003-10-15 Time 07:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-30 Cont ID  
Sent By btrobaug Date 2003-10-10 Time 15:00 Rev Time 0.50
Received By lsmith Date 2003-09-30 Time 07:55 Sent To  
Notes
2003-09-30 00:00:00BUIDING FAILED:
 SUBMIT PRODUCT APPROVALS FOR WINDOWS
  
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By btrobaug Date 2003-10-10 Time 14:59 Rev Time 0.50
Received By btrobaug Date 2003-10-10 Time 14:02 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-10-02 Time 10:57 Rev Time 0.50
Received By btrobaug Date 2003-09-29 Time 10:15 Sent To B
Notes
2003-09-29 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATIONMAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 2} PLEASE DRAW A RISER DIAGRAM SHOWING
 CONDUCTOR AND CONDUIT SIZES PER 215.5.
  
 3} SHOW GROUNDING EELCTRODE SYSTEM PER
 250.52.
  
 3} THE GROUND ROD MUST BE A MINIMUM OF
 8' PER 250.52(A)(5).
  
 4} THE GROUNDING ELECTRODE CONDUCTOR
 MUST BE A MINIMUM OF #4 PER 250.66.
  
 5} INDICATE ON THE RISER WHETHER THE
 SERVICE IS OVERHEAD OR UNDERGROUND.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH.
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-02 Cont ID  
Sent By csiegber Date 2003-10-02 Time 10:57 Rev Time 0.00
Received By csiegber Date 2003-10-02 Time 10:57 Sent To E
Notes
2003-10-02 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-25 Cont ID  
Sent By csiegber Date 2003-09-25 Time 10:59 Rev Time 0.00
Received By csiegber Date 2003-09-25 Time 10:58 Sent To E
Notes
***NONE***