Plan Review Details - Permit 03091654
Plan Review Stops For Permit 03091654
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-04-08 Cont ID  
Sent By pkrauss Date 2003-12-31 Time 12:22 Rev Time 2.00
Received By jgomez Date 2003-12-31 Time 09:16 Sent To PC
Notes
2004-04-08 00:00:00CONTRACTOR BROUGHT BACK PLANS ON 4-8-04.
2003-12-31 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 DETAILS TO COMPLY WITH SEC. 1609.4.3
 FBC 2001, WHICH DOESN'T ALLOW THE
 STEEL STRESS TO BE INCREASED. USE THE
 HIGH WIND RESISTANT CONSTRUCTION
 CATALOGUE BY SIMPSON WHICH IS THE
 CATALOGUE THAT WAS ALREADY REVISED.
 **NOTE: PROVIDE ENGINEERING CALCULATIONS
 FOR VALUES OTHER THAN THOSE PUBLISHED
 ON CATALOGUE. SECTION 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 2-REVISE SPECIFICATIONS FOR CEILING
 INSTALLATION AT PORCHES. SEE ASTM
 C-1063. NEED FASTENER THAT PENETRATES
 1 3/4" INTO WOOD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By btrobaug Date 2003-12-17 Time 12:04 Rev Time 2.50
Received By jgomez Date 2003-10-28 Time 09:20 Sent To PC
Notes
2003-10-28 00:00:00BULDING REVIEW CHECKLIST:
 1-PROVIDE ALL INFORMATION LISTED ON SEC.
 1606.1.7 FBC 2001.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS & PAID RECEIPT.
 3-NEED RECORDED NOTICE OF COMMENCEMENT.
 4-PROVIDE SPECIFICATIONS FOR POOL DECK.
 SEE SECTION 424.1.3 FBC 2001. SPECIFY,
 DECK SLOPE. MATERIALS , ETC.
 5-PROVIDE ATTIC ACCESS AS REQUIRED BY
 SEC. 2309.6 FBC 2001.
 6-PROVIDE COMPLETE WINDOW & DOOR BUCK
 DETAILS. SEE SEC. 1707.4.4.2 FOR
 SPECIFIC BUCK INSTALLATION.
 7-NEED LANDING IN FRONT OF FRENCH DOORS.
 SEC. 1012.1.5 FBC 2001.
 8-PROVIDE COMPLETE DETAIL/SPECS FOR INS-
 TALLATION OF CEILING AT OPEN PORCH.
 SPECIFY FASTENERS AND SPACING. SEE
 ASTM C-926 AND ASTM C-1063. SECTION
 2504.2 FBC 2001.
 9-NEED TO INCLUDE ATTIC LIVE LOAD FOR
 PROPER TRUSS DESIGN. TABLE 1604.1 FBC.
 10-PROVIDE SOIL TEST REPORT.
 11-ENERGY CALCULATIONS: A)COMPLETE ALL
 INFORMATION ON TOP OF FORM.
 B)REVISE A/C AREA. SEE PLANS.
 C)REVISE UNDER ATTIC AREA. SEE SECTION
 602.1ABC.1.2 CHAPTER 13 FBC 2001.
 D)OWNER/AGENT TO SIGN AND DATE FORM ALSO
 E)REVISE SEER FOR A/C. SEE A/C PLANS.
 F)WALL TYPES: CLARIFY WHERE IS ADJACENT
 WOOD FRAMED WALL LOCATED ON PLANS. SEE
 ITEM 9. A) OF ENERGY CALCS.
  
 12-REVISE AREA CALCULATIONS SHOWN ON DWG
 A.O. SEE CALCS ON SHEET A.1.
 13-SHEET A.4: A)CLARIFY CONNECTOR SPECI-
 FIED. SEE COMMENTS ON PLAN.
 B)SPECIFY FIREBLOCKING. SEE PLANS AND
 SEC. 2305 FBC 2001.
 C)SPECIFY STUCCO THICKNESS. ASTM C-926.
  
 14-SHEET S.1: UPDATE GENERAL NOTES. SEE
 COMMENTS ON SHEET.
 15-SPECIFY WWM SUPPORTS AND SPACING. SEE
 SEC. 1909.3 FBC 2001.
 16-UPDATE TRUSS ANCHOR SCHEDULE TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001
 WHICH DOESN'T ALLOW THE STEEL STRESS
 TO BE INCREASED. USE SIMPSON HIGH WIND
 RESISTANT CONSTRUCTION CATALOGUE OR
 USP 2003 CATALOGUE THAT ARE THE ONLY
 CATALOGUES UPDATED FOR THIS SECTION.
 17-PROVIDE COMPLETE DETAIL/SECTION FOR
 CONNECTION OF STEEL COLUMN TO WOOD BM
 AT TRELLIS AREA. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-12-10 Cont ID  
Sent By btrobaug Date 2003-12-17 Time 12:03 Rev Time 0.50
Received By btrobaug Date 2003-12-10 Time 14:19 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 08:36 Rev Time 1.00
Received By btrobaug Date 2003-10-10 Time 17:23 Sent To P
Notes
2003-10-10 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CHANGES TO
 THE PLAN FOR CODE COMPLIANCE AND
 RESUBMIT FOR REVIEW.
  
 1} USE THE CORRECT LOAD CALCULATION. IF
 USING 220.30,SEE(B)(3) "NAMEPLARE
 RATING OF ALL APPLIANCES". ALSO SEE
 220.16,17 & 18.
  
 2} PROVIDE A PANEL SCHEDULE FOR THE NEW
 PANEL.
  
 3} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210.11-C-3
 MUST BE 20A AND #12AWG.
  
 4} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE OR NOTE ON PLANS FOR BRANCH
 CIRCUIT PROTECTION. PER 210.12
  
 5} VERIFY 2/0 FEEDER SIZE FROM THE
 EXISTING PANEL TO 100 AMP DISCONNECT.
  
 6} THE "EXISTING" GEC IS TO SMALL FOR
 THE SERVICE,SHOULD BE 1/0 PER 250.66.
  
 7} VERIFY THAT THE CONDUIT FROM THE
 EXISTING PANEL TO THE 100 AMP
 DISCONNECT DOES NOT NEED AN EQUIPMENT
 GROUND.
  
 8} ADD SMOKE DETECTOR IN THE MASTER
 BEDROOM PER 8-1.4.1.6.2(1),NFPA-72.
  
 9} THE HALL NEEDS A RECEPTACLE PER 210.
 52(H).
  
 10} ADD RECEPTACLES TO THE EXERCISE ROOM
 PER 210.52(A)(1) & (2).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 08:36 Rev Time 0.00
Received By csiegber Date 2003-12-10 Time 08:36 Sent To E
Notes
2003-12-10 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 10:01 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 10:01 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-24 Cont ID  
Sent By sgraham Date 2003-09-29 Time 10:17 Rev Time 0.00
Received By csiegber Date 2003-09-24 Time 14:55 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-31 Cont ID  
Sent By pkrauss Date 2003-12-31 Time 12:22 Rev Time 0.25
Received By pkrauss Date 2003-12-31 Time 12:15 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-16 Cont ID  
Sent By jleech Date 2003-10-14 Time 18:13 Rev Time 0.25
Received By pkrauss Date 2003-10-16 Time 09:26 Sent To B
Notes
2003-10-16 00:00:00PROVISO:
 PLEASE REVISE THE MASTER BEDROOM RETURN
 AIR TO COMPLY WITH THE FOLLOWING:
  
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-14 Cont ID  
Sent By btrobaug Date 2003-10-10 Time 18:00 Rev Time 0.25
Received By jleech Date 2003-10-14 Time 18:12 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-24 Time 14:55 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***