Plan Review Details - Permit 03091366
| Plan Review Stops For Permit 03091366 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-10-20 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-10-20 00:00:00 | ***************BUILDING FAILED******** | | | 1. ALL PAGES WITH ARCHITECT SEAL MUST | | | HAVE TITLE BLOCK PER STATE STATUTE. | | | | | | 2.THE DOORS EXITING THE RESTROOMS DO | | | NOT MEET THE MINIMUM OF 18" APPROACH PER | | | FIGURE #25 CHAPTER 11 OF THE FBC. | | | | | | 3. PAGE A6 SHOWS INSTALLATION OF NEW | | | PLUMBING FIXTURES. | | | | | | 4.PLUMBING, MECHANICAL & ELECTRIC | | | CONTRACTOR SHALL APPLY FOR PERMITS | | | SEPARATELY PAY PERMIT FEES. | | | | | | ANY QUESTIONS PLEASE CALL: | | | LEA SMITH, BUILDING PLANS EXAMINER | | | 805-6713 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-10-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-10 |
Time |
07:52 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-10-10 |
Time |
07:45 |
Sent To |
|
|
| Notes |
| 2003-10-10 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE VERFIY EXISTING | | | EQUIPMENT GROUNDING CONDUCTORS FROM | | | 8HA TO TANSFORMER AND FROM TRANSFORMER | | | TO 8LA. 250.110 250.110? | | | | | | 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS | | | AT 125%. 230.42,215.3 ETC. | | | | | | 3)NOTE:PLEASE SEE FIRE REVIEW COMMENTS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-10-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-10-03 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-10-03 |
Time |
15:35 |
Sent To |
|
|
| Notes |
| 2003-10-03 00:00:00 | 1) DOOR LATCH RELEASE BUTTON AND | | | MAGNETIC DOOR LATCHES ARE MENTIONED | | | ON THE PLANS. PLEASE INDICATE HOW THEY | | | EFFECT EXITING. NOTES BELOW DOOR | | | SCHEDULE INDICATE FAIL SAFE MODE. | | | PLEASE ELABORATE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-22 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-22 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2003-09-22 00:00:00 | TO COMM BD #11 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-10-24 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-10-24 |
Time |
13:30 |
Rev Time |
0.50 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-10-24 00:00:00 | SEE PATTY'S APPROVAL STAMP ON SHEET M1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-10-21 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-21 |
Time |
13:02 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2003-10-21 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2003-10-21 00:00:00 | DENIED | | | REFERENCE: FBC-2001 CHAPTER 1 | | | | | | 1) A SANITARY AND A WATER RISER DIAGRAM | | | ARE REQUIRED. SECTION 104.3.1.1 | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
|