Plan Review Details - Permit 03091366
Plan Review Stops For Permit 03091366
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By lsmith Date 2003-10-20 Time 16:14 Rev Time 0.00
Received By lsmith Date   Time   Sent To  
Notes
2003-10-20 00:00:00***************BUILDING FAILED********
 1. ALL PAGES WITH ARCHITECT SEAL MUST
 HAVE TITLE BLOCK PER STATE STATUTE.
  
 2.THE DOORS EXITING THE RESTROOMS DO
 NOT MEET THE MINIMUM OF 18" APPROACH PER
 FIGURE #25 CHAPTER 11 OF THE FBC.
  
 3. PAGE A6 SHOWS INSTALLATION OF NEW
 PLUMBING FIXTURES.
  
 4.PLUMBING, MECHANICAL & ELECTRIC
 CONTRACTOR SHALL APPLY FOR PERMITS
 SEPARATELY PAY PERMIT FEES.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-10 Cont ID  
Sent By dpalmer Date 2003-10-10 Time 07:52 Rev Time 0.75
Received By dpalmer Date 2003-10-10 Time 07:45 Sent To  
Notes
2003-10-10 00:00:00***************** UNSAT ****************
  
 1)NOTE: PLEASE VERFIY EXISTING
 EQUIPMENT GROUNDING CONDUCTORS FROM
 8HA TO TANSFORMER AND FROM TRANSFORMER
 TO 8LA. 250.110 250.110?
  
 2)NOTE: PLEASE SHOW ALL CONTINOUS LOADS
 AT 125%. 230.42,215.3 ETC.
  
 3)NOTE:PLEASE SEE FIRE REVIEW COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 15:35 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 15:35 Sent To  
Notes
2003-10-03 00:00:001) DOOR LATCH RELEASE BUTTON AND
 MAGNETIC DOOR LATCHES ARE MENTIONED
 ON THE PLANS. PLEASE INDICATE HOW THEY
 EFFECT EXITING. NOTES BELOW DOOR
 SCHEDULE INDICATE FAIL SAFE MODE.
 PLEASE ELABORATE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-22 Time 16:34 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 16:34 Sent To  
Notes
2003-09-22 00:00:00TO COMM BD #11

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-24 Cont ID  
Sent By lmartine Date 2003-10-24 Time 13:30 Rev Time 0.50
Received By lmartine Date   Time   Sent To  
Notes
2003-10-24 00:00:00SEE PATTY'S APPROVAL STAMP ON SHEET M1

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-21 Time 13:02 Rev Time 0.33
Received By kstevens Date 2003-10-21 Time 13:02 Sent To  
Notes
2003-10-21 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
  
 1) A SANITARY AND A WATER RISER DIAGRAM
 ARE REQUIRED. SECTION 104.3.1.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]