Plan Review Details - Permit 03091329
Plan Review Stops For Permit 03091329
Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status F Date 2004-11-15 Cont ID  
Sent By shill Date 2004-11-15 Time 13:18 Rev Time 0.50
Received By shill Date 2004-11-15 Time 13:18 Sent To PC
Notes
2004-11-15 00:00:00****CORRECTIONS****
 BAR JOIST SUBMITTAL, PREPARED BY AMIN
 FARES, PE DATED 11/9/4
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PROVIDE A TITLE BLOCK INCLUDING AN
 ADDRESS, TELEPHONE, PRINTED NAME AND
 LICENSE NUMBER ON EACH SHEET,
 FAC61G15-23.002.
  
 2.)EACH SHEET IS TO BE SIGNED AND
 SEALED BY THE ENGINEER.
  
 3.)REVIEW BY DESIGNER OF RECORD IS TO
 BE DONE BEFORE RESUBMITTAL.
  
 4.)THE ADDRESS ON THE SUBMITTAL IS
 NOT FOR THIS JOB.
  
 5.)CHANGES TO THE PLAN REQUIRE A
 REVISION; WHEN RESUBMITTING PLEASE
 BRING IN AS A REVISION.
  
 6.)FOR THE MECHANICAL EQUIPMENT
 HANGING FROM THE BOTTOM CHORD OF THE
 BAR
 JOISTS, CONFIRM THAT LATERAL RESTRAINTS
 HAVE BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2004-11-09 Cont ID  
Sent By shill Date 2004-11-09 Time 13:22 Rev Time 1.00
Received By shill Date 2004-11-09 Time 13:22 Sent To PC
Notes
2004-11-09 00:00:00ROOFING SUBMITTAL, STAIR SHOPS, LIGHT
 POLE

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status F Date 2004-08-20 Cont ID  
Sent By shill Date 2004-08-20 Time 15:58 Rev Time 0.50
Received By shill Date 2004-08-20 Time 15:58 Sent To  
Notes
2004-08-20 00:00:00****CORRECTIONS****
 ROOFING SUBMITTALS
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SUBMITTALS/REVISIONS ARE TO BE
 REVIEWED BY THE DESIGNER OF RECORD.
  
 2.)ORIGINAL SIGNED, SEALED CALCS
 REQUIRED FAC61G15-23.002.THE CA NUMBER
 FOR THE ENGINEERING FIRM IS TO BE ON
 THE TITLE BLOCK.
  
 3.)NO FEE FOR RESUB (BRING IN AS A
 SUBMITTAL AS IT HAS ALREADY BEEN
 REVIEWED).
  
 CC:DON NEELY

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status P Date 2004-08-17 Cont ID  
Sent By csiegber Date 2004-08-20 Time 14:39 Rev Time 0.50
Received By shill Date 2004-08-17 Time 09:35 Sent To PC
Notes
2004-08-17 00:00:00REVISION - ARCH ALUM PROD APPROVAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status P Date 2004-07-28 Cont ID  
Sent By csiegber Date 2004-08-11 Time 11:49 Rev Time 0.50
Received By shill Date 2004-07-28 Time 11:31 Sent To  
Notes
2004-07-28 00:00:00LETTER FROM MARK DUCKETT, PE RE: FIELD
 ISSUES, REQUEST OF HP DATED 7/12/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status P Date 2004-07-27 Cont ID  
Sent By shill Date 2004-07-27 Time 13:58 Rev Time 1.00
Received By shill Date 2004-07-27 Time 13:58 Sent To  
Notes
2004-07-27 00:00:00LETTERS FROM MARK DUCKETT, PE AND
 MANUEL R. LINARES, III, PE REGARDING
 SLAB BRACING OF TILT WALLS

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status P Date 2004-06-23 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:41 Rev Time 0.50
Received By shill Date 2004-06-23 Time 14:04 Sent To  
Notes
2004-06-23 00:00:00STEEL SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status P Date 2004-06-17 Cont ID  
Sent By csiegber Date 2004-06-21 Time 15:06 Rev Time 0.50
Received By shill Date 2004-06-17 Time 11:45 Sent To  
Notes
2004-06-17 00:00:00TILT PANEL REINFORCING SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status P Date 2004-06-17 Cont ID  
Sent By shill Date 2004-06-17 Time 07:22 Rev Time 0.50
Received By shill Date 2004-06-17 Time 07:22 Sent To  
Notes
2004-06-17 00:00:00REVISION - DETAIL BY DUCKETT ENGINEERING
 DATED 5/17/04

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status P Date 2004-06-10 Cont ID  
Sent By csiegber Date 2004-06-16 Time 11:26 Rev Time 0.50
Received By shill Date 2004-06-10 Time 17:14 Sent To  
Notes
2004-06-10 00:00:00WEST FOOTING REVISION
 PROVISO - REVISE FOUNDATION PLAN TO
 REFLECT CHANGE IN SIZE

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status P Date 2004-06-10 Cont ID  
Sent By shill Date 2004-06-10 Time 16:56 Rev Time 0.75
Received By shill Date 2004-06-10 Time 16:56 Sent To  
Notes
2004-06-10 00:00:00SUBMITTALS
  
 FORM BOARD SURVEY
 FOUNDATION SHOPS
 ANCHOR BOLTS
 PANEL WALL LAYOUT SHOPS

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2004-05-11 Cont ID  
Sent By csiegber Date 2004-06-04 Time 14:36 Rev Time 1.00
Received By shill Date 2004-05-11 Time 11:12 Sent To  
Notes
2004-05-11 00:00:00RESTAMP FOR RESIDENT INSPECTOR SET -
 ORIGINAL SIGNATURES & SEALS SUBMITTED
 OVER PHOTOCOPIED CITY APPROVED SET

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2004-04-26 Cont ID  
Sent By shill Date 2004-04-26 Time 14:07 Rev Time 1.00
Received By shill Date 2004-04-26 Time 14:07 Sent To E
Notes
2004-04-26 00:00:00****CORRECTIONS****
 RESIDENT INSPECTOR SET SUBMITTED
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.) ORIGINAL SIGNATURE REQUIRED, NOT
 PHOTOCOPY.
  
 2.) FOR THE MEP SHEETS, PLEASE CLARIFY
 AS TO WHY THE SIGNATURE ON THE CITY
 SET OF PLANS IS DIFFERENT FROM THE
 SIGNATURE ON THE NEW SHEETS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2004-03-16 Cont ID  
Sent By shill Date 2004-03-16 Time 09:13 Rev Time 1.00
Received By shill Date 2004-03-16 Time 09:13 Sent To  
Notes
2004-03-16 00:00:00SEE PROVISOS ON REVIEW #4

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-03-05 Cont ID  
Sent By shill Date 2004-03-05 Time 15:58 Rev Time 0.00
Received By shill Date 2004-03-05 Time 15:58 Sent To  
Notes
2004-03-05 00:00:00SEE LETTER FROM ENGINEERING

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2004-03-02 Cont ID  
Sent By shill Date 2004-03-02 Time 07:27 Rev Time 2.00
Received By shill Date 2004-03-02 Time 07:27 Sent To  
Notes
2004-03-02 00:00:00***PROVISO***
  
 PROVIDE SIGNED & SEALED WIND LOAD CALCS
 FOR THE LIGHT POLES ASCE7-98 PER FBC16.
  
 GUARDRAIL TO COMPLY WITH FBC1015.3 AND
 1608, SHOP DRAWINGS TO BE SUBMITTED
 BEFORE INSTALLATION.
  
 NOTICE OF COMMENCEMENT TO BE PROVIDED
 TO CONSTRUCTION SERVICES BEFORE
 COMMENCING WORK.
  
 RESIDENT INSPECTOR TO BE APPROVED BY
 CITY OFFICIALS BEFORE COMMENCING WORK.
  
 THIRD SET OF PLANS, SIGNED & SEALED,
 SUBMITTED TO THE CITY BEFORE COMMENCING
 WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-02-19 Cont ID  
Sent By csiegber Date 2004-03-01 Time 12:20 Rev Time 5.00
Received By shill Date 2004-02-11 Time 15:00 Sent To  
Notes
2004-02-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE WIND LOAD CALCS, PREPARED BY
 PCSI, APPEAR TO HAVE A PHOTOCOPY OF A
 SEAL AND SIGNATURE.TITLE BLOCK
 REQUIRED, CALCULATIONS TO BE SEALED ON
 THE FIRST PAGE FAC61G.
  
 2.)SEE THE PREVIOUS LIST, ITEM #1.
 THE ENERGY CALCS STILL DECLARES "STORAGE
 & WAREHOUSE" OCCUPANCY, SEE HIGHLIGHT.
  
 3.)DELETED 2/19.
  
 4.)DELETED 2/19.
  
 5.)SEE PREVIOUS LIST, ELECTRICAL
 COMMENT #1, 12/29/03.
 TITLE BLOCKS ARE REQUIRED TO
 CONTAIN AN AUTHORIZATION NUMBER FOR
 THE COMPANY AND A SPACE FOR THE PRINTED
 NAME AND LICENSE NUMBER OF THE PERSON
 SEALING THE PLAN, FAC61G15-23.002,
 FAC61G1-16.004.CHECK ALL SHEETS FOR
 COMPLIANCE.
  
 6.)SEE PREVIOUS LIST, ITEM #1.THE
 SHEETS A1 AND A2 PREPARED BY ZPR STILL
 DECLARE A FLEX/WAREHOUSE USE.THE
 ELEVATIONS ARE NOT CONSISTENT WITH THE
 PLAN.WHY HAS THIS INFORMATION NOT
 BEEN PREPARED BY THE DESIGNER OF RECORD?
 ADDRESS.
  
 7.)THE UNITY OF TITLE STATES THE
 INCORRECT USAGE OF THE PROPERTY "FLEX
 SPACE".ALSO, THE ACKNOWLEDGEMENT IS
 BY ANDREW AIKEN ON BEHALF OF JUPITER
 TRADE CENTER PARTNERS.ADDRESS.SUBMIT
 AN ORIGINAL CORRECTED UNITY OF TITLE.
  
 8.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 9.)SEPARATE PERMITS REQUIRED.
  
 10.) SEE PREVIOUS ELECTRICAL COMMENT,
 REMOVE VOIDED SHEETS.
  
 11.) PROVISO - GUARDRAIL TO COMPLY WITH
 FBC1015.3, SHOP DRAWINGS TO BE SUBMITTED
 BEFORE INSTALLATION.
  
 12.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 13.)ANY PRODUCT APPROVALS REQUIRED BUT
 NOT SUBMITTED BEFORE ISSUANCE WILL
 REQUIRE A SEPARATE PERMIT FOR THOSE
 ITEMS.
  
 **NO RESUB FEE PER LM/SMH**
  
 NOTE 2/19/3 - CONTACT R.PITTMAN UPON
 RESUBMITTAL; NEEDS COPY OF SURVEY

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-01-06 Cont ID  
Sent By gjoyce Date 2004-02-02 Time 08:58 Rev Time 2.00
Received By shill Date 2004-01-03 Time 21:06 Sent To  
Notes
2004-01-06 00:00:00******CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, FIRST
 CORRECTION.THE PERMIT APPLICATION WAS
 CHANGED TO "BUSINESS OCCUPANCY" (FROM
 WAREHOUSE), BUT THE ENERGY CALCS AND
 THE PLANS (ZPR) STATE FLEX OFFICE/IND/
 WAREHOUSE.
  
 2.)SEE PREVIOUS LIST IN REGARDS TO
 THE REQUEST FOR FIRE PROTECTION
 DESIGN.THE TRANSMITTAL LETTER STATES
 THAT DRAWINGS WERE SUBMITTED BUT THEY
 ARE NOT IN THE PACKAGE.FBC104.3.1.1.
  
 3.)BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 4.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.
  
 5.)SEPARATE PERMITS REQUIRED.
  
 6.)IMPACT PROTECTION REQUIRED FOR
 GLAZING FBC1606.1.4.THE PRODUCT
 APPROVALS FOR THE STOREFRONT GLASS WAS
 FOR IMPACT BUT THE DOORS WERE NON
 IMPACT.
  
 7.)UNITY OF TITLE REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-27 Cont ID  
Sent By mmclean Date 2003-12-22 Time 13:37 Rev Time 0.00
Received By hpiskura Date 2003-10-27 Time 14:40 Sent To  
Notes
2003-10-27 00:00:00SHEET A1 DECLARES THE OCCUPANCY GROUP
 AS"B" OFFICE USE.THE PERMIT
 APPLICATION DECLARES WAREHOUSE USE.
 PLEASE CLARIFY THE DESIGN INTENT, EVEN
 IF MIXED OCCUPANCY, SHOW THE
 PROPORTIONS.NOTE THE QUANTITIES,
 NATURE AND CHARCTERISTICS OF THE
 COMMODITIES TO BE STORED IN ANY GROUP
 "S" OCCUPANCIES.
  
 THE FIRE PROTECTION DESIGN IS REQUIRED
 TO BE ON THE PERMIT PLANS.SEE FBC 104.
 3.1.1 #5.
  
 ARE THE THREE MEZZANINES SHOWN TO BE
 CONSTRUCTED WITH THIS PERMIT?IF SO,
 INCLUDE THE FLOOR AREA IN THE DATA ON
 SHEET A1.ALSO, SHOW THE VERTICAL
 ACCESSIBILITY AS PROVIDED FOR IN FBC
 11-4.1.3 (5).
  
 PLEASE PROVIDE A DETAIL FOR THE
 EXTERIOR RUSTICATIONS SHOWN IN SEVERAL
 PLACES ON THE PLANS.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
 ALSO, SEE THE NOTE ABOVE RE: OCCUPANCY U
 SE GROUPS AND AREAS.

Review Stop E ELECTRICAL
Rev No 8 Status P Date 2004-10-23 Cont ID  
Sent By dpalmer Date 2004-10-23 Time 09:07 Rev Time 0.25
Received By dpalmer Date 2004-10-23 Time 09:07 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2004-10-06 Cont ID  
Sent By dpalmer Date 2004-10-06 Time 17:07 Rev Time 0.33
Received By dpalmer Date 2004-10-06 Time 17:07 Sent To  
Notes
2004-10-06 00:00:00********** UNSAT ************
  
 1)NOTE: PLEASE SEE A REVISION #2 IS
 INDICATED ON TITLE BLOCK, YET PLANS DO
 NOT SHOW THIS REV #2 WITH CLOUDS/TRI-
 -ANGLES?
  
 2)NOTE: PLEASE SEE FS 471.025, PLANS
 REQUIRED TO BE SIGNED WITH SIGNATURE.
 SIGNATURE MUST BE LEGAL SIGNATURE AND
 CORRELATE WITH SIGNATURE ON FILE PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status F Date 2004-09-17 Cont ID  
Sent By dpalmer Date 2004-09-17 Time 13:09 Rev Time 0.33
Received By dpalmer Date 2004-09-16 Time 20:18 Sent To  
Notes
2004-09-17 00:00:00******** UNSAT *****
  
 1)NOTE: PLEASE SEE PLANS ARE NOW BEING
 SUBMITTED FOR A TEANT BUILD OUT.
 ANY REVISIONS TO ORIGINAL PLANS, MUST BE
 DONE BY THE ENGINEER OF RECORD.
 SPACE CAN BE DONE UNDER SEPARATE PERMIT.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-05-11 Cont ID  
Sent By dpalmer Date 2004-05-11 Time 09:14 Rev Time 0.25
Received By dpalmer Date 2004-05-11 Time 09:14 Sent To  
Notes
2004-05-11 00:00:00COPY OF ORG SET ONLY, NO REVISION.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2004-04-28 Cont ID  
Sent By shill Date 2004-05-10 Time 13:34 Rev Time 0.33
Received By dpalmer Date 2004-04-28 Time 07:26 Sent To P
Notes
2004-04-28 00:00:00********** UNSAT **********
  
 1)NOTE: PLANS ARE REQ'D TO BE SIAGNED
 W/ COMPLETE SIGNATURE PER FS 471.025
 PLANS APPEAR TO HAVE INITIALS WHICH ARE
 NOT ACCEPTABLE PER FS/ FAC .
 DO NOT CORRELATE WITH PLANS ON FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-06 Cont ID  
Sent By shill Date 2004-04-26 Time 14:39 Rev Time 2.00
Received By dpalmer Date 2004-02-05 Time 16:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-29 Cont ID  
Sent By dpalmer Date 2003-12-29 Time 13:13 Rev Time 1.00
Received By dpalmer Date 2003-12-29 Time 12:54 Sent To  
Notes
2003-12-29 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT ALL LICENSE #`S
 ARE REQ'D ON PLANS/TITLE BLOCK.
 PER FS 471 AND FAC 61G15-23.002
 PLEASE SEE THAT THIS WAS ADDED ON ONLY
 TWO OF THE ELECTRICAL SHEETS. OTHER OLD
 SHEETS WERE NOT CORRECTED.
 PLEASE NOTE, THIS IS REQ'D ON ALL SHEETS
 AND FOR ALL TRADES, WEATHER OR NOT
 COMMENT IS MADE FROM OTHER REVIEWERS.
  
 2)NOTE: PLEASE SHOW WIND LOADING FOR
 POLES. THIS IS REQ'D AT THIS TIME AND ON
 THESE PLANS.
  
 3)NOTE: PLEASE TAKE OUT ALL OLD/VOIDED
 SHEETS AND ONLY HAVE NEW SHEETS INTO
 SETS FOR REVIEW AND STAMPING.
  
 4)NOTE: PLEASE HAVE PLANS "SIGNED" WITH
 A COMPLETE SIGNATURE PER FS 471.025 AND
 FAC 61G15-23.002.
 PLEASE NOTE, SINCE DATE OF LAST REVIEW
 WE HAVE BEEN NOTIFIED FROM THE FBPE'S
 THAT INITIALS ARE NOT ACCEPTABLE AND
 SHOULD BE SIGNED HOW SIGNATURE ON
 LICENSE WAS SIGNED W/ FBPE'S.
 IF THIS IS ACTUAL SIGNATURE, PLEASE
 PROVIDE COPY OF LICENSE WITH SIGNATURE
 SHOWN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 09:46 Rev Time 1.00
Received By dpalmer Date 2003-10-14 Time 07:31 Sent To  
Notes
2003-10-14 00:00:00************* UNSAT ****************
  
 1)NOTE: PLEASE CIRCUIT EM/ EXT LTS PER
 700.12E AND CORRELATE.
  
 2)NOTE: PLEASE CORRELATE A/C SYSTEMS
 AND PANEL SCHEDULES, CIRCUITING SHOWN ON
 PLANS DIFER FROM PANELS.
  
 3)NOTE: PLEASE INCLUDE ALL LICENSE
 INFORMATION ON TITLE BLOCK(CA#) REQ'D
 UNDERFAC 61G15-23.002, FS 471
  
 4)NOTE: PLEASE LABEL ALL DISC MEANS
 AT MAIN.600A,400A,300A ETC. WHICH ONE
 DOES WHICH.? 215.5
  
 5)NOTE: PLEASE PROVIDE AIC RATINGS FOR
 ALL MAINS. 110.9/215.5
  
 6)NOTE: PLEASE PROVIDE LOAD CALCAULTIONS
 WITH ALL CONTINUOUS LOADS AT 125%.
 215.3/230.42 ETC.
  
 7)NOTE: PLEASE PROVIDE INFORMATION FOR
 WIND LOADS ON LIGHT POLES. REQ'D AT THIS
 TIME.
  
 8)NOTE: PLEASE SEE THAT ADDRESS IS REQ`D
 ON PLANS FOR LOCATION OF JOB/SITE.
 61G1-16.004.
  
 PLEASE PROVIDE THE ABOVE INFORMATION FOR
 REVIEW.IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2004-03-01 Cont ID  
Sent By shill Date 2004-03-01 Time 16:21 Rev Time 0.50
Received By mamini Date 2004-03-01 Time 16:33 Sent To  
Notes
2004-03-01 00:00:00M.A. TO ADD PROVISO
 PASSED WITH PROVISOS:
 1. WORK WITHIN PUBLIC R.O.W REQUIRES
 PERMIT FROM CITY ENGINEER, MR. RICHARD
 PITTMAN.PROPOSED SIDEWALK AND THE
 APPRACHES MUST BE APPROVED AND PERMITTED
 BY THE CITY ENGINEER, 659-8040.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2003-12-30 Cont ID  
Sent By mamini Date 2003-12-30 Time 09:55 Rev Time 0.50
Received By mamini Date 2003-12-30 Time 09:55 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-10-06 Cont ID  
Sent By mamini Date 2003-10-06 Time 08:38 Rev Time 0.50
Received By mamini Date 2003-10-06 Time 08:38 Sent To  
Notes
2003-10-06 00:00:00FAILED:
 1. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW AND APPROVAL,
 CALCULATION MUST INCLUDE TOTAL SITE,
 PERVIOUS AND IMPERVIOUS AREA.
 2. PARKING STALLS MUST BE DIMENSIONED
 PER ZONING DEPARTMENT REQUIREMENT.
 3. PLEASE CONTACT JIM WITMER FOR
 ADDRESSING THE FACILITIY AND FOR PROPER
 PROPERTY CONTROL NUMBER, 805-6715
 4.PLEASE SUBMIT TWO COPIES OF CIVIL PLAN
 ONLY TO PUBLIC UTILITIES AND ENGINEERING
 FOR THEIR REVIEW AND RECORD.659-8040,
 EXT. 2306 MANNY GONZALEZ
 5. PLEAE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED,
 PLEASE SUBMIT TWO SETS OF CIVIL PLANS
 SIGNED AND SEALED AND WITH THE
 INFORMATION REQUESTED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-11-05 Cont ID  
Sent By mcarsill Date 2004-11-05 Time 14:33 Rev Time 0.00
Received By mcarsill Date 2004-11-05 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-02-10 Cont ID  
Sent By mcarsill Date 2004-02-10 Time 14:27 Rev Time 0.00
Received By mcarsill Date 2004-02-10 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2004-01-02 Cont ID  
Sent By mcarsill Date 2004-01-02 Time 15:18 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 15:18 Sent To  
Notes
2004-01-02 00:00:00APPROVED PROVISO:
  
 1) DUCT SMOKE DETECTORS SHALL CAUSE
 A GENERAL ALARM NOT A SUPERVISORY
 SIGNAL AS LISTED AS # 13, FIRE CONTROL
 COMMUNICATOR SYSTEM NOTES.
  
 2) FIRE ALARM SYSTEM SHALL BE UL LISTED
 FOR CENTRAL STATION SERVICE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-08 Cont ID  
Sent By mcarsill Date 2003-10-08 Time 17:08 Rev Time 0.00
Received By mcarsill Date 2003-10-08 Time 17:08 Sent To  
Notes
2003-10-08 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING, AND AFTER CONSTRUCTION.
  
 2) BUILDING ADDRESS IS REQUIRED.
  
 3) THE FIRE ALARM SYSTEM IS TO BE UL
 CERTIFICATED FOR CENTRAL STATION
 SERVICE. NOTES ON PAGE E-1 SUGGESTS
 FLOW AND TAMPER SWITCHES, HOWEVER NO
 FIRE SPRINKLER PLANS WERE PROVIDED.
 LIMITED FIRE SPRINKLER INFORMATION
 WAS PROVIDED ON PAGES A-1 AND A-3.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2004-11-17 Cont ID  
Sent By mjacobs Date 2004-11-17 Time 16:14 Rev Time 0.00
Received By mjacobs Date 2004-11-17 Time 16:14 Sent To M
Notes
2004-11-17 00:00:00SENT TO "M" BOX

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2004-11-09 Cont ID  
Sent By csiegber Date 2004-11-09 Time 10:12 Rev Time 0.00
Received By csiegber Date 2004-11-09 Time 10:12 Sent To B
Notes
2004-11-09 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2004-11-04 Cont ID  
Sent By csiegber Date 2004-11-04 Time 13:13 Rev Time 0.00
Received By csiegber Date 2004-11-04 Time 13:13 Sent To B
Notes
2004-11-04 00:00:00TO SH DESK/SUBMITTALS/PA

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2004-10-20 Cont ID  
Sent By csiegber Date 2004-10-20 Time 12:32 Rev Time 0.00
Received By csiegber Date 2004-10-20 Time 12:32 Sent To  
Notes
2004-10-20 00:00:00TO COMM BD#31

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2004-10-05 Cont ID  
Sent By csiegber Date 2004-10-05 Time 15:19 Rev Time 0.00
Received By csiegber Date 2004-10-05 Time 15:19 Sent To  
Notes
2004-10-05 00:00:00TO COMM BD#61

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2004-08-31 Cont ID  
Sent By csiegber Date 2004-08-31 Time 12:11 Rev Time 0.00
Received By csiegber Date 2004-08-31 Time 12:11 Sent To  
Notes
2004-08-31 00:00:00TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2004-08-20 Cont ID  
Sent By csiegber Date 2004-08-20 Time 14:39 Rev Time 0.00
Received By csiegber Date 2004-08-20 Time 14:39 Sent To B
Notes
2004-08-20 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2004-08-11 Cont ID  
Sent By csiegber Date 2004-08-11 Time 11:49 Rev Time 0.00
Received By csiegber Date 2004-08-11 Time 11:49 Sent To B
Notes
2004-08-11 00:00:00TO SH DESK/SUBMITTAL/PA

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:41 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 16:41 Sent To B
Notes
2004-07-26 00:00:00TO SH DESK/SUBMITTAL
 CONNECTION SYSTEM

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2004-07-21 Cont ID  
Sent By csiegber Date 2004-07-21 Time 09:36 Rev Time 0.00
Received By csiegber Date 2004-07-21 Time 09:36 Sent To B
Notes
2004-07-21 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-06-21 Cont ID  
Sent By csiegber Date 2004-06-21 Time 15:06 Rev Time 0.00
Received By csiegber Date 2004-06-21 Time 15:06 Sent To B
Notes
2004-06-21 00:00:00TO SH DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-06-16 Cont ID  
Sent By csiegber Date 2004-06-16 Time 11:26 Rev Time 0.00
Received By csiegber Date 2004-06-16 Time 11:26 Sent To B
Notes
2004-06-16 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-06-04 Cont ID  
Sent By csiegber Date 2004-06-04 Time 14:36 Rev Time 0.00
Received By csiegber Date 2004-06-04 Time 14:36 Sent To B
Notes
2004-06-04 00:00:00TO SH DESK/SUBMITTAL/3-FORM BOARD SURVEY
 FOUNDATION STEEL DRAWINGS,ANCHOR BOLT
 DRAWINGS,PAN LAYOUT DRAWINGS

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-05-10 Cont ID  
Sent By shill Date 2004-05-10 Time 13:34 Rev Time 0.00
Received By shill Date 2004-05-10 Time 13:34 Sent To E
Notes
2004-05-10 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-03-01 Cont ID  
Sent By csiegber Date 2004-03-01 Time 12:20 Rev Time 0.00
Received By csiegber Date 2004-03-01 Time 12:20 Sent To B
Notes
2004-03-01 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-02-02 Time 11:54 Rev Time 0.00
Received By csiegber Date 2004-02-02 Time 14:42 Sent To  
Notes
2004-02-02 00:00:00TO COMM BD#63

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-23 Cont ID  
Sent By csiegber Date 2004-01-23 Time 15:25 Rev Time 0.00
Received By csiegber Date 2004-01-23 Time 15:25 Sent To Z
Notes
2004-01-23 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-23 Cont ID  
Sent By csiegber Date 2003-12-23 Time 09:16 Rev Time 0.00
Received By csiegber Date 2003-12-23 Time 09:16 Sent To  
Notes
2003-12-23 00:00:00TO COMM BD#54

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:33 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 16:33 Sent To Z
Notes
2003-12-17 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 11:42 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 11:42 Sent To  
Notes
2003-10-03 00:00:00TO COMM BD#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2003-09-22 Cont ID  
Sent By csiegber Date 2003-09-22 Time 16:05 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 16:05 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 8 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pkrauss Date 2004-11-18 Time 17:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2004-11-05 Cont ID  
Sent By pkrauss Date 2004-11-05 Time 11:24 Rev Time 0.00
Received By pkrauss Date 2004-11-05 Time 09:48 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 6 Status F Date 2004-10-07 Cont ID  
Sent By pkrauss Date 2004-10-07 Time 07:37 Rev Time 0.40
Received By pkrauss Date 2004-10-07 Time 07:25 Sent To  
Notes
2004-10-07 00:00:00DENIED:
 1.SIGNATURE IS REQUIRED ON PLANS IN
 ACCORDANCE WITH FS 471.025.INITIALS
 ARE NOT CONSIDERED A SIGNATURE.
  
 PLANS ARE OTHERWISE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status N Date 2004-05-11 Cont ID  
Sent By shill Date 2004-05-11 Time 12:53 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2004-05-11 00:00:00SEE BLDG REVIEW RE RESTAMP

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2004-05-04 Cont ID  
Sent By pkrauss Date 2004-05-04 Time 16:07 Rev Time 0.30
Received By pkrauss Date 2004-05-04 Time 16:07 Sent To  
Notes
2004-05-04 00:00:00DENIED:RE-STAMP
 PLEASE NOTE SIGNATURE ON THE RE-STAMP
 COPY DOES NOT MATCH THE SIGNATURE ON
 THE ORIGINAL APPROVED SET OF PLANS.
 SEE COMMENTS FROM SAMANTHA HILL
 (BUILDING) AND DEWEY PALMER
 (ELECTRICAL).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-02-18 Cont ID  
Sent By pkrauss Date 2004-02-18 Time 14:19 Rev Time 0.45
Received By pkrauss Date 2004-02-18 Time 14:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2004-01-06 Cont ID  
Sent By pkrauss Date 2004-01-06 Time 10:32 Rev Time 0.40
Received By pkrauss Date 2004-01-06 Time 10:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-28 Cont ID  
Sent By pkrauss Date 2003-10-28 Time 12:03 Rev Time 0.45
Received By pkrauss Date 2003-10-28 Time 12:03 Sent To  
Notes
2003-10-28 00:00:00DENIED:
 SEE COMMENT #1 BY H. PISKURA, CLARIFY
 OCCUPANCY TYPE.
  
 PLEASE NOTE, ADDITIONAL VENTILANTION MAY
 BY REQUIRED SHOULD FUTURE OCCUPANT HAVE
 HAZARDOUS OR NOXIOUS CONTAMINANT ISSUES.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 7 Status P Date 2004-11-05 Cont ID  
Sent By kstevens Date 2004-11-05 Time 13:36 Rev Time 0.50
Received By kstevens Date 2004-11-05 Time 13:36 Sent To  
Notes
2004-11-05 00:00:00REVISION OK - DELETED BUILD-OUT OF BAY
 NUMBER 12 - SEPARATE PERMIT FOR
 BUILD-OUT PER PLANS

Review Stop P PLUMBING
Rev No 6 Status F Date 2004-10-09 Cont ID  
Sent By kstevens Date 2004-10-09 Time 14:40 Rev Time 0.50
Received By kstevens Date 2004-10-09 Time 14:40 Sent To  
Notes
2004-10-09 00:00:00REVISION/DENIED
  
 SIGNATURE ON REVISION IS NOT THE SAME AS
 THE SIGNATURE ON THE STAMPED SET OF
 PLANS ON FILE - FULL SIGNATURE OF ENG.
 OF RECORD REQUIRED ON REVISION - INITI-
 ALS ARE NOT ACCEPTABLE.RESUBMIT REV-
 ISION WITH FULL SIGNATURE OR REVISION
 WILL BE DENIED. FAC 61G15-23.003
 FS 471.025
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status N Date 2004-05-11 Cont ID  
Sent By shill Date 2004-05-11 Time 12:53 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2004-05-11 00:00:00SEE BLDG REVIEW RE RESTAMP

Review Stop P PLUMBING
Rev No 4 Status F Date 2004-04-29 Cont ID  
Sent By kstevens Date 2004-04-29 Time 18:43 Rev Time 0.33
Received By kstevens Date 2004-04-29 Time 18:43 Sent To  
Notes
2004-04-29 00:00:00DENIED
  
 SEE COMMENTS FROM 4-28-4 BY ELECTRICAL
 PLAN REVIEWER
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-02-03 Cont ID  
Sent By dpalmer Date 2004-04-28 Time 07:26 Rev Time 0.50
Received By kstevens Date 2004-02-03 Time 18:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2004-01-09 Cont ID  
Sent By kstevens Date 2004-01-09 Time 18:11 Rev Time 1.00
Received By kstevens Date 2004-01-09 Time 18:11 Sent To  
Notes
2004-01-09 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FLA. ADMIN. CODE
 FLA. STATUTES
  
 1) FROM PREVIOUS REVIEW: (#3) INDICATE
 THE NAME OF THE PERSON RESPONSIBLE FOR
 DRAWINGS. 104.2.1
 2) FROM PREVIOUS REVIEW: (#5) CERTIFIC-
 ATE OF AUTHORIZATION REQUIRED ON EACH
 SHEET. 61G15-23.002(2) - FS471.025
 3) SEE COMMENT #4 BY ELECTRICAL PLAN
 REVIEWER. SIGNATURE REQUIRED ON SEAL.
 INITALS NOT ACCEPTABLE PER FBPE & BLDG.
 OFFICIAL.
 4) PLEASE REMOVE ALL OLD SHEET AND SUB-
 MIT ONE COPY OF OLD SHEETS FOR COMPARI-
 SON.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-23 Cont ID  
Sent By kstevens Date 2003-10-22 Time 14:24 Rev Time 1.25
Received By kstevens Date 2003-10-22 Time 14:24 Sent To  
Notes
2003-10-22 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) SUBMIT CALCULATIONS FOR ROOF GUTTERS
 AND DOWNSPOUTS PER TABLE 1106.6. SHOW SQ
 FT OF ROOF, & SHOW 1/2 AREA OF ALL
 VERTICAL WALLS INCLUDING PARAPETS IN THE
 CALCULATIONS. INDICATE SLOPE OF GUTTER,
 AND SHOW SLOPE OF GUTTER ON PLANS.
 2) DRINKING FOUNTAIN SHALL COMPLY WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
 ALSO 11-4.1.3(10)(A) PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE DIFFICULTY BEND-
 ING OR STOOPING. PLEASE SUBMIT A DETAIL.
 3) SEPARATE IRRIGATION PERMIT/PLANS RE-
 QUIRED.
 4) SHT L-1 ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 5) CERTIFICATE OF AUTHORIZATION REQUIRED
 PER 61G15-23.002(2) FS 471
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2004-02-02 Cont ID  
Sent By csiegber Date 2004-01-23 Time 15:25 Rev Time 1.00
Received By gjoyce Date 2004-02-02 Time 08:57 Sent To B
Notes
2003-12-22 00:00:00ZONING ISSUES WERE NOT ADDRESSED GMJ
2003-10-28 00:00:00MET WITH OWNER DO NOT ISSUE PERMIT!!!!!
 OWNER IS REVISING PLANS TO ADDRESS CODE
 ISSUSES.HE IS ADDING RESIDENTAIL TO EN
 TIRE 2ND FLOOR.HE IS REVISING CIRCULAT
 ION AND LANDSCAPING.DO NOT ISSUE PERMIT!
 !
2003-09-29 00:00:00PARKING SIZE NOT TO CODE, LANDSCAPING NO
 T TO CODE, DUMPSTER NOT TO CODE THE PLAN
 S ARE ON THE 5TH FLOOR W/ GRACE.WAITIN
 G TO SET-UP MEETIN WITH THE OWNER FOR A
 REDESIGN.