Plan Review Details - Permit 03091225
Plan Review Stops For Permit 03091225
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-10-27 Cont ID  
Sent By hpiskura Date 2003-10-27 Time 10:20 Rev Time 0.00
Received By hpiskura Date 2003-10-27 Time 10:20 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-26 Cont ID  
Sent By btrobaug Date 2003-11-26 Time 15:29 Rev Time 1.00
Received By btrobaug Date 2003-11-17 Time 13:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 19:19 Rev Time 0.50
Received By dpalmer Date 2003-09-29 Time 19:19 Sent To  
Notes
2003-09-29 00:00:00************* UNSAT ******************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 INFORMATION REQD' ON TITLE BLOCK FOR
 ENGINEER OF RECORD. PLEASE INDICATE
 LICENSE # OF ENG WITH THE CA# WHICH
 APPEARS TO BE SHOWN.
  
 2)NOTE: PLEASE SEE THAT PLANS REFERENCE
 THE 1991 LS 101. WE ARE CURRENTLY UNDER
 THE 1999 LS 101
 PLEASE ALSO SEE THAT ELECTRICAL CODES
 REFERENCED ON PLANS ARE FROM THE 1996
 NEC.PLEASE SEE THAT AS OF JULY 1ST,2003
 THE STATE HAS ADAOPTED THE 2002 NEC.
  
 PLEASE SEE FIRE REVIEW COMMENTS THAT MAY
 HAVE AN AFECT ON ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By mcarsill Date 2003-11-24 Time 16:12 Rev Time 0.00
Received By mcarsill Date 2003-11-24 Time 16:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 15:23 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 15:23 Sent To  
Notes
2003-10-03 00:00:001) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2) EXITS ARE TO REMAIN TO CLEAR AND
 UNOBSTRUCTED AT ALL TIMES.
  
 3) DEBRIS TO BE REMOVED FROM THE SITE
 DAILY.
  
 4) FP-1 DOES NOT INDICATE ANY EXISTING
 OR NEW FIRE PROTECTION FOR ELECTRICAL
 ROOM OR JANITOR'S CLOSET.
  
 5) SEPARATE PLANS AND PERMITS REQUIRED
 FIRE ALARM SYSTEM AND FIRE SPRINKLER
 REMODEL.
  
 6) PLEASE INDICATE INTERIOR FINISH
 FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-10 Cont ID  
Sent By csiegber Date 2003-11-10 Time 09:40 Rev Time 0.00
Received By csiegber Date 2003-11-10 Time 09:40 Sent To  
Notes
2003-11-10 00:00:00TO COMM BD#53

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-22 Time 11:53 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 11:52 Sent To  
Notes
2003-09-22 00:00:00TO COMM BD#25

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By pkrauss Date 2003-11-24 Time 13:02 Rev Time 0.40
Received By pkrauss Date 2003-11-24 Time 12:54 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By pkrauss Date 2003-10-20 Time 13:07 Rev Time 0.40
Received By pkrauss Date 2003-10-20 Time 12:06 Sent To  
Notes
2003-10-20 00:00:00DENIED:
 1.PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 2.AS PER 2001 FBC(M) 601.4, FAN SHUT
 DOWN BY DUCT SMOKE DETECTOR REQUIRED
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER NFPA 90A
 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-21 Time 18:47 Rev Time 0.33
Received By kstevens Date 2003-10-21 Time 18:47 Sent To  
Notes
2003-10-21 00:00:00NO PLUMBING PLANS SUBMITTED - NO PLUMB-
 ING WORK SHOWN