Plan Review Details - Permit 03091223
Plan Review Stops For Permit 03091223
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-10-20 Cont ID  
Sent By hpiskura Date 2003-10-20 Time 15:38 Rev Time 0.00
Received By hpiskura Date 2003-10-20 Time 15:38 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 06:17 Rev Time 0.25
Received By dpalmer Date 2003-10-28 Time 06:17 Sent To  
Notes
2003-10-28 00:00:00PASSED PENDING FIRE REVIEW

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 19:04 Rev Time 0.75
Received By dpalmer Date 2003-09-29 Time 19:04 Sent To  
Notes
2003-09-29 00:00:00******** UNSAT *****************
  
 1)NOTE: PLEASE SEE THAT PLANS REFERENCE
 THE 99 NEC. PLEASE SEE THAT AS OF JULY
 1ST, 2003 THE STATE ADOPTED THE 2002
 NEC.
  
 2)NOTE: PLEASE SEE FIRE REVIEW NOTES FOR
 LOCATION OF EXT SIGNS. PLEASE VERIFY
 FOR NO EXT SIGNS LEADING TO STAIRWELLS?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-04 Cont ID  
Sent By csiegber Date 2003-11-04 Time 11:06 Rev Time 0.00
Received By mcarsill Date 2003-11-04 Time 15:56 Sent To  
Notes
2003-11-04 00:00:00PLEASE SEE BLOCK STAMP ON PLANS FOR MEC
 APPROVAL/DEE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By mcarsill Date 2003-10-02 Time 07:42 Rev Time 0.00
Received By mcarsill Date 2003-10-02 Time 07:42 Sent To  
Notes
2003-10-02 00:00:001) ON SHEET # 4, NO EXIT SIGNS ARE
 SHOWN AT THE STAIRTOWERS. PLEASE
 EXPLAIN PURPOSE OF EXIT SIGNS THAT
 LEAD PERSONS TO THE ELEVATOR LOBBY.
  
 2) IT DOES NOT APPEAR THAT ANY
 EMERGENCY LIGHTS ARE PRESENT IN THE
 RECEPTION 101 HALLWAY.
  
 3) SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE SPRINKLER REMODEL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-27 Cont ID  
Sent By csiegber Date 2003-10-27 Time 11:25 Rev Time 0.00
Received By csiegber Date 2003-10-27 Time 11:25 Sent To  
Notes
2003-10-27 00:00:00TO COMM BD#25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-22 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:07 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 12:07 Sent To  
Notes
2003-09-19 00:00:00TO COMM BD#9

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-10-10 Cont ID  
Sent By pkrauss Date 2003-10-10 Time 12:08 Rev Time 0.40
Received By pkrauss Date 2003-10-10 Time 12:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-18 Cont ID  
Sent By kstevens Date 2003-10-18 Time 13:40 Rev Time 0.33
Received By kstevens Date 2003-10-18 Time 13:40 Sent To  
Notes
***NONE***