Plan Review Details - Permit 03091176
Plan Review Stops For Permit 03091176
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2005-05-24 Cont ID  
Sent By shill Date 2005-05-24 Time 14:01 Rev Time 0.50
Received By shill Date 2005-05-24 Time 14:01 Sent To  
Notes
2005-05-24 00:00:00WALL REPAIR DETAIL PREPARED BY DAVID
 CARMO, PE DATED 5/17/05

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2005-05-19 Cont ID  
Sent By shill Date 2005-05-19 Time 13:41 Rev Time 0.50
Received By shill Date 2005-05-19 Time 13:41 Sent To PC
Notes
2005-05-19 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THIS DETAIL WAS NOT PREPARED BY
 DESIGNER OF RECORD.HAVE REVIEWED BY
 DOR OR HAVE HIM PREPARE A DETAIL.
  
 2.)THE PRINTED NAME OF THE PERSON
 SEALING THE DOCUMENT IS TO BE ON THE
 PLAN, FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2005-03-09 Cont ID  
Sent By shill Date 2005-03-09 Time 17:00 Rev Time 1.00
Received By shill Date 2005-03-09 Time 17:00 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2005-03-07 Cont ID  
Sent By shill Date 2005-03-07 Time 17:56 Rev Time 0.50
Received By shill Date 2005-03-07 Time 17:56 Sent To PC
Notes
2005-03-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)BOTH SETS ARE REQUIRED TO BE
 STAMPED BY THE HISTORIC PRESERVATION
 DEPARTMENT.
  
 ****NO RESUB FEE****

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-11-24 Cont ID  
Sent By shill Date 2004-11-24 Time 10:20 Rev Time 1.50
Received By shill Date 2004-11-24 Time 07:56 Sent To E
Notes
2004-11-24 00:00:00PROVISO - SUBMIT PRODUCT APPROVAL FOR
 ROOF VENT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2004-06-29 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 15:31 Rev Time 1.50
Received By shill Date 2004-06-29 Time 14:05 Sent To  
Notes
2004-06-29 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PERMIT APPLICATION IS EXPIRED,
 FBC104.1.6.SUBMIT A NEW PERMIT
 APPLICATION.
  
 2.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED (OVER 90 DAYS WITHOUT
 COMMENCING WORK, FS 713.13).
  
 3.)SEPARATE PERMITS REQUIRED.
  
 4.)DETAILS 7-A5 AND 1-A5, SPECIFY
 WHICH CONNECTORS ARE TO BE USED.
 FASTENING CANNOT CONFLICT WITH THE
 MANUFACTURER'S CATALOG.
  
 5.)CITY OF WPB AMENDMENTS TO THE
 FBC 1804.1.7, THE LOWEST BUILDING
 FLOOR ELEVATION AT THE PERIMETER OF
 A MONOLOTHIC FOUNDATION AT HABITABLE
 AREAS SHALL BE A MINIMUM OF 4" ABOVE THE
 FINISHED GRADE.FBC1804.1.3, THE
 BOTTOM OF FOUNDATIONS SHALL EXTEND NO
 LESS THAN 12" BELOW FINISH GRADE.
 REVISE 7-A5 TO SHOW GRADE AND COMPLIANCE
 WITH THE TWO CODES REFERENCED.
  
 6.)THE IMPACT FEE DOCUMENTATION
 INDICATES NO SQUARE FOOTAGE BEING
 ADDED.THIS IS AN ADDITION OF 150
 SQUARE FEET.PLEASE CONTACT 233-5025.
  
 7.)THE AREA CALCS PREPARED BY THE
 ARCHITECT SHOW AN ADDITION OF 150 SQUARE
 FEET, THE THE ENERGY CALCS SHOW 175.
 BOTH MUST BE CONSISTENT.SIGN THE
 OWNER/AGENT LINE OF THE ENERGY CALC.
 SUBMIT TWO COPIES.
  
 8.)PRODUCT APPROVALS REQUIRED FOR
 THE FRENCH DOORS, WINDOWS AND IMPACT
 PROTECTION.TWO COPIES OF EACH ARE
 REQUIRED.FLORIDA STATEWIDE, LOCAL OR
 SITE SPECIFIC PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE TEST REPORT FAC9B72.
 WWW.FLORIDABUILDING.ORG

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-15 Cont ID  
Sent By kstevens Date 2004-06-29 Time 07:40 Rev Time 2.00
Received By sthyng Date 2003-10-15 Time 12:28 Sent To Z
Notes
2003-10-15 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 2.)SEPARATE PERMITS REQUIRED.
  
 3.)HAVE AN ENGINEER CONFIRM THAT THE
 INTERIOR WALLS TO BE REMOVED ARE NOT
 LOAD BEARING.
  
 4.)IT APPEARS THAT YOU ARE REMOVING
 THE EXTERIOR WALL BETWEEN THE KITCHEN
 AND THE BACK PORCH AND ENCLOSING THE
 BACK PORCH.PROVIDE INFORMATION ABOUT
 THE EXISTING CONDITIONS, INCLUDING
 STRUCTURAL CONNECTIONS.PROVIDE A
 PROPOSED WALL SECTION FROM FOUNDATION
 THROUGH ROOF, INCLUDING ASSEMBLY AND
 MATERIALS FBC104.3.1.1.
  
 5.)PROVIDE AREA CALCULATIONS ON THE
 PLAN (EXISTING, PROPOSED, NEW TOTALS
 UNDER AIR).
  
 6.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.SIGN THE OWNER/AGENT LINE OF THE
 ENERGY CALC.
  
 7.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 8.)THE PLANS SHOW SHUTTERED WINDOWS,
 THE PRODUCT APPROVALS ARE FOR IMPACT.
 CLARIFY.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2006-03-30 Cont ID  
Sent By dpalmer Date 2006-03-27 Time 10:25 Rev Time 0.00
Received By dpalmer Date 2006-03-27 Time 10:24 Sent To PC
Notes
2006-03-30 00:00:00REDLINED 210.52C1-5

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2006-03-02 Cont ID  
Sent By dpalmer Date 2006-03-02 Time 19:30 Rev Time 0.00
Received By dpalmer Date 2006-03-02 Time 19:20 Sent To PC
Notes
2006-03-02 00:00:00********* UNSAT ***********
  
  
 1)NOTE: PLEASE MAKE ALL CHANGES TO PLANS
 WIHTOUT HANDDRAWN CHANGES.
 PLEASE SEE PLASN A COLORED PHOTO-COPIES
 WITH CHNAGES MADE TO ORIGINAL SSTAMPED
 PLANS.
 PLANS MUST BE REPRINTED AND DONE WITH
 DRAFTSMAN QUALITY AND SIGNED, DATED AND
 SEALED BY THE ARCHITECT OF RECORD.
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY
 THE CITY OF WEST PALM BEACH 104.2.1,
 104.2.1.3
 FS 481.221
  
 ** PLEASE KNOW, A TECHNICAL REVIEW OF
 SAID PLANS WILL BE DONE AT THAT TIME.
 ** PLEASE KNOW, IF PLUMB IS NOT GOING TO
 BE PART OF REVSION, PLEASE REMOVE FROM
 PLAN/SHEET OR HAVE ARCHITECT INDICATE NO
 REVISION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2005-03-03 Cont ID  
Sent By dpalmer Date 2005-03-03 Time 15:53 Rev Time 0.30
Received By dpalmer Date 2005-03-03 Time 15:53 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-12-01 Cont ID  
Sent By dpalmer Date 2004-12-01 Time 06:15 Rev Time 0.30
Received By dpalmer Date 2004-12-01 Time 06:07 Sent To B
Notes
2004-12-01 00:00:00********** UNSAT *********
  
 1)NOTE: PLEASE SEE LOAD CALCULATIONS
 NEED TO MEET NEC 220.31
 PLEASE SEE A/C LOAD IS NOT DERATED W/
 GEN LT LOAD.
  
 2)NOTE: PLEASE SEE AREAS ON PLANS WHERE
 CHANGES HAVE BEEN MADE ARE INITIALED AND
 DO NOT CORRELATE WITH OTHER INITIALS OR
 SIGNATURE FROM ARCHITECT. THESE ARE
 SIGNED AND SEALED PLANS BY AN ARCHITECT
 AND THAT PERSON IS THE ONLY ONE
 PERMITTED TO MAKE ANY CHANGES.
 FS 481.221
  
 3)NOTE: PLEASE SEE 210.8A6. ALL RECEPTS
 ON KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED.
 ALSO 210.52C1
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-06-23 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 11:29 Rev Time 0.50
Received By dpalmer Date 2004-06-23 Time 11:28 Sent To P
Notes
2004-06-23 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SEE THIS PERMIT APPLICAT-
 -ION IS NOW EXPIRED DUE TO 6 MONTHS OF
 INACTIVITY. PLEASE SEE BLDG REVIEW
 COMMENTS FOR THIS.
  
 2)NOTE: PLEASE SEE ALL RECEPT SERVING
 KITCHEN OCUNTERSPACE ARE TO BE SHOWN AS
 GFI/GFI PROTECTED. 210.8A6
  
 3)NOTE: PLEASE SEE FAC 61G1-16.004,
 PLEASE INCLUDE COMPLETE ADDRESS INFORMA-
 -TION ON TITLE BLOCK.
  
 4)NOTE: PLEASE SEE LOAD CALCS, SHOW
 PER 220.31 EXISTING DWELLING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-24 Cont ID  
Sent By shill Date 2004-06-21 Time 15:11 Rev Time 0.33
Received By dpalmer Date 2003-09-24 Time 06:32 Sent To P
Notes
2003-09-24 00:00:00******** REDLINED NOTES********
  
 EGRESS LIGHTING FROM KITCHEN TO OUTSIDE?
 210.70
 RECEPT SPACING ALONG KITCHEN COUNTER TO
 MEET 210.52C1

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2006-03-24 Cont ID  
Sent By spalmer Date 2006-03-24 Time 17:48 Rev Time 0.00
Received By spalmer Date 2006-03-24 Time 17:48 Sent To E
Notes
2006-03-24 00:00:00TO DVP DESK

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2006-03-02 Cont ID  
Sent By adarroug Date 2006-03-02 Time 09:15 Rev Time 0.00
Received By adarroug Date 2006-03-02 Time 09:15 Sent To E
Notes
2006-03-02 00:00:00TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2005-05-24 Cont ID  
Sent By adarroug Date 2005-05-24 Time 11:32 Rev Time 0.00
Received By adarroug Date 2005-05-24 Time 11:32 Sent To B
Notes
2005-05-24 00:00:00TO "SHILL" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2005-03-09 Cont ID  
Sent By adarroug Date 2005-03-09 Time 16:44 Rev Time 0.00
Received By adarroug Date 2005-03-09 Time 16:44 Sent To B
Notes
2005-03-09 00:00:00TO "SHILL"/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 16:02 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 16:02 Sent To E
Notes
2005-03-02 00:00:00TO DPALMER DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-16 Cont ID  
Sent By mjacobs Date 2004-11-16 Time 15:30 Rev Time 0.00
Received By mjacobs Date 2004-11-16 Time 15:30 Sent To B
Notes
2004-11-16 00:00:00SENT TO "B" TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-06-21 Cont ID  
Sent By shill Date 2004-06-21 Time 15:11 Rev Time 0.00
Received By shill Date 2004-06-21 Time 15:11 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-16 Cont ID  
Sent By mjacobs Date 2004-06-16 Time 08:51 Rev Time 0.00
Received By mjacobs Date 2004-06-16 Time 08:51 Sent To B
Notes
2004-06-16 00:00:00SENT TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-06-14 Cont ID  
Sent By mmclean Date 2004-06-15 Time 12:43 Rev Time 0.00
Received By mjacobs Date 2004-06-14 Time 15:03 Sent To Z
Notes
2004-06-14 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-09-19 Time 12:24 Rev Time 0.00
Received By csiegber Date 2003-09-19 Time 12:24 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-10-07 Cont ID  
Sent By jleech Date 2003-10-02 Time 17:12 Rev Time 0.15
Received By pkrauss Date 2003-10-07 Time 12:39 Sent To B
Notes
2003-10-07 00:00:00NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLAN SHEET 4 OF 7 NOTE #7
 INDICATES EXTENDING EXISTING DUCTWORK
 INTO NEW KITCHEN SPACE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2004-06-29 Cont ID  
Sent By kstevens Date 2004-06-29 Time 07:40 Rev Time 0.75
Received By kstevens Date 2004-06-29 Time 07:00 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-02 Cont ID  
Sent By dpalmer Date 2004-06-23 Time 11:35 Rev Time 0.33
Received By jleech Date 2003-10-02 Time 17:11 Sent To M
Notes
2003-10-02 00:00:00PLAN REVIEW FOR PLUMBING ONLY. NO GAS.

Review Stop Z ZONING
Rev No 2 Status P Date 2004-06-15 Cont ID  
Sent By mmclean Date 2004-06-15 Time 12:43 Rev Time 0.00
Received By mmclean Date 2004-06-15 Time 12:43 Sent To I
Notes
2004-06-15 00:00:00RENOVATION OF KITCHEN MEETS THE EXISTING
 SETBACKS WITH NO ADDITION EXTENSION MM

Review Stop Z ZONING
Rev No 1 Status F Date 2003-10-15 Cont ID  
Sent By mjacobs Date 2004-06-14 Time 15:03 Rev Time 0.00
Received By mmclean Date   Time   Sent To  
Notes
2003-10-15 00:00:0010/15/03 DENIED, NEED 2 COPY OF SURVEY
 SHOWING THE WORK CALLED OWNER FILE V MM