Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-01-21 Cont ID  
Sent By rbrown Date 2004-01-21 Time 11:45 Rev Time 0.00
Received By rbrown Date 2004-01-21 Time 11:45 Sent To  
Notes
2004-01-21 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 A SEPARATE PERMIT APPLICATION AND FEES
 WILL BE REQUIRED FOR THE PROPOSED
 MODIFIED BITUMEN ROOFING SYSTEM AS NO
 PRODUCT APPROVALS WERE SUBMITTED UNDER
 THIS PERMIT APPLICATION.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.
  
 --PROVISO--
 A SEPARATE PERMIT APPLICATION AND FEES
 WILL BE REQUIRED FOR THE NEW STOREFRONT,
 HOLLOW METAL DOORS, FIXED WINDOWS,
 SINGLE HUNG WINDOWS (AND SHUTTERS FOR
 ANY EXTERIOR GLAZING NOT SPECIFIED AS
 IMPACT RATED) AS NO PRODUCT APPROVALS
 WERE SUBMITTED UNDER THIS PERMIT APPLIC.
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE, TO IDENTIFY
 WHICH PRODUCT OPTIONS/MATERIALS/SIZES
 ARE TO BE USED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-11-12 Cont ID  
Sent By rbrown Date 2003-11-12 Time 16:11 Rev Time 0.00
Received By rbrown Date 2003-11-12 Time 16:11 Sent To  
Notes
2003-11-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 NOTE:
 CHAPTER 553.80(2)(B) FLORIDA STATUTES
 STATES THAT A LOCAL GOVERNMENT SHALL
 IMPOSE A FEE OF FOUR TIMES THE FEE FOR
 PLAN REVIEW, IF PLANS ARE REJECTED THREE
 OR MORE TIMES FOR REPEATED FAILURE TO
 CORRECT A CODE VIOLATION.NOTE THE
 COMMENTS LISTED BELOW AS 'NOT ADDRESSED'
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 10/21/03:
  
 2) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 13-103.1.1.1THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING, MECHANICAL AND PLUMBING
 SYSTEMS SHALL EACH SIGN SHEET 2 OF THE
 ENERGY CODE COMPLIANCE FORM, TO CERTIFY
 COMPLIANCE.
  
 3) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 1010.1.1TWO EXITS ARE REQUIRED
 FROM EACH STOREY (REF: FBC 1004.1.2).
 THE SECOND FLOOR DOES NOT HAVE AN EXIT
 DIRECTLY CONNECTED TO A PUBLIC WAY (REF:
 FBC 1010.1.1) SO THE FIRST FLOOR
 ELEVATOR LOBBY AT STAIR #1 MUST MEET THE
 REQUIREMENTS OF AN EXIT PASSAGEWAY OR
 VESTIBULE (REF: FBC 1010.1.1).AS THE
 DEPTH OF THE FIRST FLOOR ELEVATOR LOBBY
 FROM THE FRONT OF THE BUILDING EXCEEDS
 10 FEET, THAT LOBBY MUST MEET THE
 RREQUIREMENTS OF AN EXIT PASSAGEWAY.AN
 EXIT PASSAGEWAY SHALL NOT HAVE ANY
 OPENINGS OTHER THAN THE REQUIRED EXIT
 DOORS, SO THE ELEVATOR AND ELEVATOR
 MACHINE ROOM SHALL NOT BE ACCESSED FROM
 THIS SPACE.
  
 4) FBC 1006.2.4EXTERIOR STAIRWAY.
 SHEET A3.2, EAST ELEVATION,THE EXIT
 DISCHARGE ROUTE PASSES THE NEW FIRST
 FLOOR EXIT DOORS SO THESE SHALL BE MIN.
 1-HOUR DOOR ASSEMBLIES.AMEND/ANNOTATE
 THE PLANS.
  
 6) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 705.1.1.2SHEET A3.2, SOUTH
 ELEVATION.THIRD FLOOR REPLACEMENT
 WINDOWS.SEE PREVIOUS PLAN REVIEW.
  
 7) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-1, FOUNDATION PLAN - NEW FOOTERS
 SEE PREVIOUS PLAN REVIEW.
  
 8) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-1, 2ND FLOOR FRAMING PLAN -
 REINFORCEMENT.SEE PREVIOUS PLAN REVIEW
  
 9) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-1, 2ND FLOOR FRAMING PLAN -
 LANDING SLAB.SEE PREVIOUS PLAN REVIEW.
  
 10) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-4STAIR SECTION - MONOLITHIC
 FOOTING.SEE PREVIOUS PLAN REVIEW.
  
 11) THIS COMMENT HAS NOT BEEN ADDRESSED.
 PROVIDE ELEVATIONAL VIEW OF DETAIL 1/S-1
 SEE PREVIOUS PLAN REVIEW.
  
 12) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SHEET S-5OUTDATED REFERENCE STANDARDS
 SEE PREVIOUS PLAN REVIEW.
  
 13) THIS COMMENT HAS NOT BEEN ADDRESSED.
 DOOR, WINDOW, STOREFRONT AND SHUTTER
 PRODUCT APPROVALS.SEE PREVIOUS PLAN
 REVIEW.
  
 14) THIS COMMENT HAS NOT BEEN ADDRESSED.
 SUBMIT A ROOFING SYSTEM PRODUCT APPROVAL
 SEE PREVIOUS PLAN REVIEW.
  
 15) THIS COMMENT HAS NOT BEEN ADDRESSED.
 FBC 11-4.1.3(11)ACCESSIBLE TOILET
 FACILITIES.SEE PREVIOUS PLAN REVIEW.
  
 16) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-21 Cont ID  
Sent By rbrown Date 2003-10-21 Time 10:34 Rev Time 0.00
Received By rbrown Date 2003-10-21 Time 10:34 Sent To  
Notes
2003-10-21 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FBC 13-103.1.1.1THE PROFESSIONALS
 RESPONSIBLE FOR THE DESIGN OF THE
 BUILDING SHELL AND THE ELECTRICAL,
 LIGHTING AND PLUMBING SYSTEMS SHALL EACH
 SIGN THE ENERGY CODE COMPLIANCE FORM, TO
 CERTIFY COMPLIANCE.
  
 3) FBC 1010.3THE 1ST FLOOR ELEVATOR
 LOBBY IS IN FACT THE EXIT PASSAGEWAY
 FROM STAIR #1 TO THE EXIT DISCHARGE.
 THE EXIT PASSGEWAY SHALL NOT HAVE ANY
 OPENINGS OTHER THAN THE REQUIRED EXIT
 DOORS, SO THE ELEVATOR AND ELEVATOR
 MACHINE ROOM SHALL NOT BE ACCESSED FROM
 THIS SPACE.AMEND THE 1ST FLOOR PLAN.
  
 4) FBC 1006.2.5EXTERIOR STAIRWAY.
 AMEND THE PLANS TO CLARIFY WHERE THE
 EXTERIOR STAIRWAY DISCHARGES TO.
  
 5) FBC 1006.2.4THE EXTERIOR STAIRWAY/
 CATWALK PASSES A THIRD FLOOR WINDOW THAT
 DOES NOT HAVE A FIRE RESISTANCE RATING
 OF 1 HOUR.AMEND THE PLANS.IT IS
 NOTED THAT 2-HOUR RATED FIRE SPRINKLER
 HEADS (1 EXTERIOR AND 1 INTERIOR) HAVE
 BEEN SPECIFIED ABOVE EACH WINDOW.
  
 6) FBC 705.1.1.2SHEET A3.2, SOUTH
 ELEVATION.REPLACEMENT WINDOWS IN A
 WALL WITHIN 15 FEET OF THE PROPERTY LINE
 WILL REQUIRE OPENING PROTECTIVES.THIS
 APPLIES TO EXISTING BUILDINGS WHERE THE
 VALUE OF THE REPAIRS AND ALTERATIONS
 EXCEEDS 25% OF THE VALUE OF THE EXISTING
 BUILDING (REF FBC 3401,7,2,5).AMEND
 THE PLANS.IT IS NOTED THAT 2-HOUR
 RATED FIRE SPRINKLER HEADS (1 EXTERIOR
 AND 1 INTERIOR) HAVE BEEN SPECIFIED
 ABOVE EACH WINDOW.
  
 7) SHEET S-1, FOUNDATION PLAN STATES
 THAT NEW FOOTINGS ARE PROPORTIONED FOR
 2000 PSF ALLOWABLE BEARING PRESSURE.
 WHAT IS THE SIZE OF THE FOOTINGS FOR THE
 EXISING CONCRETE COLUMNS WHICH WILL
 RECEIVE INCREASED LOADING FROM THE
 NEW STAIR, SECOND FLOOR CONSTRUCTION AND
 ADDITIONAL ROOF MOUNTED EQUIPMENT.
  
 8) SHEET S-1, 2ND FLOOR FRAMING PLAN.
 NO BOTTOM REINFORCEMENT IS SHOWN IN THE
 SECOND SPAN OF THE NEW CONCRETE SLAB
 (EAST-WEST DIRECTION) ADJACENT THE NEW
 STAIRWAY.IS THIS INTENTIONAL?
  
 9) SHEET S-1, 2ND FLOOR FRAMING PLAN.
 AMEND THE PLANS TO CLARIFY THE SLAB
 FRAMING AROUND THE ELEVATOR SHAFT AND
 STAIRWELL.IS THE "PRE-ENGINEERED
 METAL PAN STAIR" SUPPORTED BY A CONCRETE
 LANDING SLAB AT 2ND FLOOR LEVEL, IF SO
 WHAT REINFORCEMENT IS SPECIFIED FOR THE
 LANDING SLAB?
  
 10) SHEET S-4STAIR SECTION.SUBMIT
 DETAILS FOR FORMING THE "NEW MONOLITHIC
 FOOTING" IN THE EXISTING SLAB AT THE
 BASE OF THE NEW STAIR.
  
 11) SHEET S-1PROVIDE AN ELEVATIONAL
 VIEW OF DETAIL 1/S-1 TO CLARIFY THE
 ARRANGEMENT OF THE 3/8" STIFFENERS, THE
 HILTI 1" DIA SUPER ROD AND THE 3/8" X 12
 AND 3/8" X 5" PLATES.
  
 12) SHEET S-5, CONCRETE NOTE #12 REFERS
 TO ACI 318-83 AND REINFORCING STEEL
 NOTE #9 REFERS TO ASTM A 185-68.
 FLORIDA BUILDING CODE 2001 (AS AMENDED)
 REFERS TO ACI 318-02 AND ASTM A 185-97
 RESPECTIVELY.AMEND THE NOTES.
  
 13) SUBMIT TWO COPIES OF A PRODUCT
 APPROVAL FOR THE NEW STOREFRONT, HOLLOW
 METAL DOORS, FIXED WINDOWS, SINGLE HUNG
 WINDOWS (AND SHUTTERS FOR ANY EXTERIOR
 GLAZING NOT SPECIFIED AS IMPACT RATED).
 THE PRODUCT APPROVAL SHEETS SHALL BE
 MARKED, AS APPROPRIATE TO IDENTIFY WHICH
 PRODUCT OPTIONS/MATERIALS/SIZES ARE TO
 BE USED.
  
 14) SHEET A2.3, ROOF PLAN.SUBMIT A
 PRODUCT APPROVAL FOR THE PROPOSED
 MODIFIED BITUMEN ROOFNG SYSTEM.
  
 15) FBC 11-4.1.3(11)ACCESSIBLE TOILET
 FACILITIES.AT THE TIME TENANT BUILD-
 OUT ACCESSIBLE TOILET FACILITIES WILL BE
 REQUIRED.
  
 16) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-01-09 Cont ID  
Sent By dpalmer Date 2004-01-09 Time 14:56 Rev Time 1.00
Received By dpalmer Date 2004-01-09 Time 14:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 09:55 Rev Time 0.50
Received By dpalmer Date 2003-11-03 Time 09:55 Sent To  
Notes
2003-11-03 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT SAME PLANS CAME
 BACK IN W/OUT NEW SHEETS AS MENTIONED
 IN RESPONSE NOTES?
 LOAD CALCS?
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 PLEASE SEE ANY COMMENTS FROM OTHER
 REVIEWS THAT MAY AFFECT ELECTRICAL
 PLANS.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-10-09 Cont ID  
Sent By dpalmer Date 2003-10-09 Time 13:53 Rev Time 1.50
Received By dpalmer Date 2003-10-09 Time 13:52 Sent To  
Notes
2003-10-09 00:00:00*********UNSAT *******************
  
 1)NOTE: PLEASEE CLARIFY MEANS OF
 LIGHTING CONTROLS FOR FIRST FLOOR, SHOWS
 WHAT APPEARS TO NUMEROUS SWITCHES, BUT
 FOR WHICH LTS? LS 101 5-8
  
 3)NOTE: PLEASESIZE GROUNDING ELOCTRODE
 PER 250.66
 SHOWN AS#2??
  
 4)NOTE: PLEASE SHOW LOAD CALCULATIONS,
 PER 220 AND CONTINOUS LOADS PER 215.3/
 230.42 ETC.
  
 5)PLEASE SEE OTHER REVIEWERS COMMENTS
 THAT MAY HAVE AN EFFECT ON ELECTRICAL
 PLANS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THER ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-08-12 Cont ID  
Sent By nmccray Date 2004-08-12 Time 12:15 Rev Time 0.00
Received By nmccray Date 2004-08-12 Time 12:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2004-01-02 Cont ID  
Sent By csiegber Date 2004-07-30 Time 11:42 Rev Time 0.00
Received By mcarsill Date 2004-01-02 Time 15:25 Sent To  
Notes
2004-01-02 00:00:001) FIRE ALARM RISER, NOTE # 5 IS
 NOT CORRECT. DUCT DETECTORS SHALL
 CAUSE AN ALARM NOT A SUPERVISORY
 SIGNAL.
  
 2) FIRE SPRINKLER PLANS ARE REQUIRED
 AT TIME OF PERMIT APPLICATION. FIRE
 SPRINKLER SHOP DRAWINGS CAN BE
 SUBMITTED LATER BUT INITIAL DESIGN
 DRAWINGS ARE REQUIRED.
  
 3) BUILDING OFFICIAL'S APPROVAL IS
 REQUIRED TO USE DELUGE FIRE SPRINKLER
 HEADS IN LIEU OF OPENING PROTECTIVES.
 PREVIOUS EXAMPLES CITED, FIRST WENT
 TO THE CONSTRUCTION BOARD OF ADJUSTMENT
 AND APPEALS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2003-11-14 Cont ID  
Sent By mcarsill Date 2003-11-14 Time 15:35 Rev Time 0.00
Received By mcarsill Date 2003-11-14 Time 15:35 Sent To  
Notes
2003-11-14 00:00:001) DUCT DETECTORS SHALL INTITIATE AN
 ALARM NOT SUPERVISORY SIGNAL AS
 INDICATED ON SHEET E-4.
  
 2) PLEASE EXPLAIN SINGLE EXIT THEORY
 FROM SECOND FLOOR. THE FLOOR PLAN
 DIFFERS FROM EXIT SIGN PLAN.
  
 3) FUTURE KITCHEN EXHAUST FAN SHALL
 BE A MINIMUM OF 10 FEET FROM ANY
 MAKE-UP AIR LOCATIONS.
  
 4) PORTABLE FIRE EXTINGUISHERS REQUIRED.
  
 5) PLEASE SEE COMMENTS REGARDING EXITS,
 EXIT PASSAGEWAYS, PROVIDED BY ROBERT
 BROWN, BUILDING PLAN REVIEWER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By mcarsill Date 2003-10-02 Time 07:26 Rev Time 0.00
Received By mcarsill Date 2003-10-02 Time 07:26 Sent To  
Notes
2003-10-02 00:00:001) PLEASE INDICATE EXISTING USE IF ANY
 FOR THE EXISTING BUILDING. IS THE
 BUILDING CURRENTLY OCCUPIED AND IF
 SO, SINGLE TENANT OR MULTIPLE TENANTS.
 IF BUILDING IS VACANT, HOW LONG HAS
 IT BEEN VACANT.
  
 2) ALL DEMOLITION, RENOVATION, AND
 CONSTRUCTION ACTIVITIES TO COMPLY
 WITH NFPA 241.
  
 3) ALL DEBRIS IS TO BE REMOVED FROM
 THE BUILDING DAILY.
  
 4) STAIRS USED FOR EXITING IS TO BE
 PROVIDED.
  
 5) ALL SHAFTS THAT ARE LARGE ENOUGH
 FOR PERSONS TO FALL INTO MUST BE
 MARKED SHAFTWAY.
  
 6) PLEASE EXPLAIN RATIONALE FOR OPEN
 STAIR # 2.
  
 7) IT APPEARS THAT WINDOW OPENINGS MAY
 BE PRESENT NEAR EXIT ACCESS TO THE
 REAR STAIR.
  
 8) FUTURE KITCHEN MAKE-UP AND EXHAUST
 SHALL BE SEPARATED BY AT LEAST 10
 FEET.
  
 9) NOTE 14 ON PAGE A3.1 INDICATES 2
 HOUR FIRE SPRINKLER HEADS. PLEASE
 PROVIDE PRODUCT APPROVALS.
  
 10) PLEASE INDICATE EXIT DISCHARGE
 LOCATION FROM EXTERIOR STAIR. PLEASE
 DISPLAY 10 FEET HIGH, 10 FEET WIDE
 EXIT DISCHARGE. WHO'S PROPERTY DOES
 EXIT DISCHARGE OCCUR.
  
 11) PLEASE PROVIDE DETAILS ON
 EXTERIOR STAIR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-07-30 Cont ID  
Sent By csiegber Date 2004-07-30 Time 11:42 Rev Time 0.00
Received By csiegber Date 2004-07-30 Time 11:42 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-30 Cont ID  
Sent By csiegber Date 2003-12-30 Time 13:50 Rev Time 0.00
Received By csiegber Date 2003-12-30 Time 13:50 Sent To  
Notes
2003-12-30 00:00:00TO COMM BD#52

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-29 Cont ID  
Sent By csiegber Date 2003-10-29 Time 16:34 Rev Time 0.00
Received By csiegber Date 2003-10-29 Time 16:34 Sent To  
Notes
2003-10-29 00:00:00TO COMM BD#14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-22 Time 11:54 Rev Time 0.00
Received By csiegber Date 2003-09-22 Time 11:54 Sent To  
Notes
2003-09-22 00:00:00TO COMM BD #6

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-01-21 Cont ID  
Sent By pkrauss Date 2004-01-21 Time 15:52 Rev Time 0.15
Received By pkrauss Date 2004-01-21 Time 15:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-22 Cont ID  
Sent By hmoser Date 2003-11-22 Time 09:45 Rev Time 1.50
Received By hmoser Date 2003-11-22 Time 09:45 Sent To  
Notes
2003-11-22 00:00:00PASS PRIVISO
 1) ADD ADDITIONAL FIRE DAMPERS.MARKED ON
 PLAN.
 2) INSTALL AUXILIARY DRAIN PROTECTION ON
 PACKAGE UNIT.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-14 Cont ID  
Sent By pkrauss Date 2003-10-14 Time 10:11 Rev Time 0.55
Received By pkrauss Date 2003-10-14 Time 10:11 Sent To  
Notes
2003-10-14 00:00:00DENIED:
 1.FIRE DAMPERS REQUIRED AT THE FLOOR
 PENETRATION 1ST FLOOR TO 2ND FLOOR FROM
 AHU-1.
  
 2.FIRE DAMPERS ALSO REQUIRED AT 2ND
 FLOOR MECHANICAL CLOSET ON BOTH SUPPY
 DUCTS.
  
 3.FIRE DAMPER ALSO REQUIRED AT 1ST
 FLOOR SUPPLY DUCT PENETRATING WALL AT
 THE ELEVATOR LOBBY.
  
 4.ADDITIONAL PERMITS REQUIRED FOR
 HOOD, FIRE SUPPRESSION AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLANS
 AND MANUFACTURER SUBMITTAL DATA WITH
 PERMIT APPLICATIONS.
  
 5.PLEASE NOTE, A MINIMUM OF 10 FT
 SEPARATION BETWEEN HOOD EXHAUST AND ANY
 FRESH AIR INTAKE, PROPERTY LINE OR
 ADJACENT BUILDINGS. NFPA 96 4-8.2.1
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-14 Cont ID  
Sent By kstevens Date 2004-01-14 Time 18:50 Rev Time 0.33
Received By kstevens Date 2004-01-14 Time 18:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-12-05 Cont ID  
Sent By kstevens Date 2003-12-05 Time 16:54 Rev Time 0.50
Received By kstevens Date 2003-12-05 Time 16:54 Sent To  
Notes
2003-12-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESSED.
 2) SEE ATTACHED SHEET CONCERNING FLORIDA
 STATUTE 533.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By kstevens Date 2003-10-20 Time 08:40 Rev Time 1.50
Received By kstevens Date 2003-10-20 Time 08:40 Sent To  
Notes
2003-10-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
  
 1) PROVIDE SANITARY, WATER, AND STORM
 ISOMETRIC RISER DIAGRAMS.
 2) RPZ BACKFLOWS REQUIRED ON WATER SERV-
 ICES.
 3) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW AREA
 OF ROOF AND SHOW 1/2 AREA OF ALL VERTIC-
 AL WALLS INCLUDING PARAPETS BEING ADDED
 AND SHOW AREA OF ROOFS THAT DRAIN ONTO
 THE ROOF FROM ABOVE.
 4) THIS PERMIT IS BEING REVIEWED AS A
 SHELL AND MINIMUM FIXTURES REQUIRED BY
 TABLE 403.1 SHALL BE DETERMINED AT THE
 TIME OF TENANT BUILD-OUT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]