Plan Review Details - Permit 03091037
Plan Review Stops For Permit 03091037
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-16 Cont ID  
Sent By dpalmer Date 2003-10-16 Time 11:46 Rev Time 0.75
Received By dpalmer Date 2003-10-16 Time 11:46 Sent To  
Notes
2003-10-16 00:00:00**** PLANS REDLINED *****
  
 PANEL IN STORAGE AREA THAT FEEDS OTHER
 AREAS MAY NOT BE IN THAT LOCATION.
 PANEL FEEDS OTHER AREAS AND IS NOT
 ACCESSIBLE BY OTHER TENANTS.
 PANEL WOULD ONLY BE ACCESIBLE BY THIS
 TENANT OR LANDLORD, IF LANDLORD WAS
 PRESENT.
  
 PANEL LOCATION WAS NOT AND IS NOT
 APPROVED AT THIS LOCATION BY ELECTRICAL
 PLAN REVIEW.
 PERMISSION FOR PANEL TO BE GRANTED BY
 OTHER AUTHORITY.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-17 Cont ID  
Sent By dpalmer Date 2003-09-17 Time 13:44 Rev Time 2.00
Received By dpalmer Date 2003-09-17 Time 13:43 Sent To  
Notes
2003-09-17 00:00:00************ PROVISO/ NOTES ************
  
 1)NOTE: PLEASE REVISE LOAD CALCUALTIONS
 AND SHOW ANY TRACK LIGHTING LOAD CALCS.
 PLEASE SEE 220.3,220.10,220.11,220.13
 AND 220.12B FOR TRK LTS.
 PLEASE SHOW ALL CONT LOADS PER 215.3,
 230.42
  
 2)NOTE: PLEASE SEE REDLINES ON PLANS
 AND SUBMIT A REVISED PLAN BEFORE FINAL.
 EGRESS LIGHTING REQD. LS 101 5-8
 ROOF TOP RECEPT FOR A/C EQUIPMENT 210.63
 CORRELATE ALL CIRCUITING ON PLANS WITH
 PANEL SCHEDULE(S).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE FINAL. PLEASE NOTE THIS IS
 REQ'D BE ELECTRICAL CONTRACTOR.
 IF THERE ARE ANY QUESTIONS,PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
 ************* PROVISO ************
  
 1)NOTE: PLANS SHOW AN ADDITIONAL 100A
 PANEL IN STORAGE RM FOR ADJACENT TENANT
 SPACE. PLEASE SEE THAT THIS PANEL MUST
 BE ACCESSIBLE FROM OTHER TENANT SPACE.
 PANEL MAY BE MOVED OR REVERSED TO FACE
 INTO OTHER SPACE.(324) BANYAN
 FIRE RATING FOR TENANT SPACE 322MUST
 BE MAINTAINED.
  
 PLEASE NOTE: THIS MUST BE COMPLETED
 BEFORE C.O. CAN BE ISSUED ON SPACE 322.
  
 PLEASE HAVE AN ELECTRICAL CONTRACTOR
 SUBMIT FOR PERMIT TO MOVE PANEL OR?
 BEFORE C.O. 215.5
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW/ ELECTRICAL INSP.
 561-805-6717
 [email protected].

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By dpalmer Date 2003-09-17 Time 11:28 Rev Time 1.00
Received By dpalmer Date 2003-09-17 Time 11:28 Sent To  
Notes
2003-09-17 00:00:00** UNSAT **
  
 PLANS NEED TO HAVE CORRECTIONS MADE.
 MEETING ELECTRICAL CONT ON SITE AT 1PM
 9/17/03 TO GO OVER PLANS AND HAVE PLANS
 CORRECTED.