Plan Review Details - Permit 03091015
Plan Review Stops For Permit 03091015
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2004-02-26 Cont ID  
Sent By btrobaug Date 2004-02-26 Time 12:45 Rev Time 1.00
Received By btrobaug Date 2004-02-26 Time 12:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2004-01-15 Cont ID  
Sent By csiegber Date 2004-02-26 Time 10:35 Rev Time 1.00
Received By btrobaug Date 2004-01-15 Time 16:57 Sent To  
Notes
2004-01-15 00:00:00 
 FAILED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE 4/0 FEEDERS FROM THE 600 AMP TRIP
 BREAKER ARE TOO SMALL FOR THE OCP PER
 310.16 NEC.CORRECT OCP OR WIRE SIZE AND
 RESUBMIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-12-22 Cont ID  
Sent By btrobaug Date 2004-01-15 Time 16:57 Rev Time 1.00
Received By btrobaug Date 2003-12-22 Time 10:15 Sent To  
Notes
2003-12-22 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE PLANS FOR REVIEW
 INDICATING PROPER PRIMARY & SECONDERY
 OVERCURRENT PROTECTION PER 450.3(B).
  
 NOTE: PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.THE NUMER OF
 THE ENGINEER OR ENGINEERING BUSINESS IS
 A REQUIREMENT OF THIS ARTICLE.
 ALSO A SIGNATURE IS A REQUIREMENT OF
 471.025,NOT INITIALS.
  
 ALSO VERIFY SIZE AND NUMBER OF CONDUCTOR
 IN THE PRIMARY AND SECONDARY.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2004-02-26 Cont ID  
Sent By csiegber Date 2004-02-26 Time 10:35 Rev Time 0.00
Received By csiegber Date 2004-02-26 Time 10:35 Sent To E
Notes
2004-02-26 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2004-01-15 Cont ID  
Sent By btrobaug Date 2004-01-15 Time 16:57 Rev Time 0.00
Received By btrobaug Date 2004-01-15 Time 16:57 Sent To E
Notes
***NONE***