Plan Review Details - Permit 03090799
Plan Review Stops For Permit 03090799
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-10-24 Cont ID  
Sent By pschmitz Date 2003-10-23 Time 09:25 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By btrobaug Date 2003-10-17 Time 11:22 Rev Time 0.50
Received By btrobaug Date 2003-10-17 Time 11:07 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-24 Cont ID  
Sent By btrobaug Date 2003-09-24 Time 10:36 Rev Time 0.50
Received By btrobaug Date 2003-09-24 Time 09:26 Sent To Z
Notes
2003-09-24 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO THE PLANS AND RESUBMIT FOR REVIEW.
  
 1} THE LOAD CALCULATIONS SUBMITTED ARE
 FOR DWELLING UNITS. PLEASE SUBMIT
 CALCULATIONS AND PANEL SCHEDULES FOR
 THE COMMERCIAL APPLICATION BEING
 APPLIED PER 220.3.
  
 2} PLEASE LABEL CIRCUITS ON THE FLOOR
 PLAN AND CORRELATE WITH THE PANEL
 SCHEDULE.
  
 3} PLEASE NOTE THAT THE RECEPTACLES IN
 CLIENT AREAS MUST COMPLY WITH 16.5.1.2
 NFPA-72.
  
 4} PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATED AND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 5} THE SMOKE DETECTOR IN THE KITCHEN IS
 IN VIOLATION OF 8-1.4.2 NFPA-72.MUST BE
 A LISTED HEAT DETECTOR OR REMOVED.
  
 NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9,
 IF ANY SERVICE EQUIPMENT IS BEING
 ADDED OR REPLACED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-10-01 Cont ID  
Sent By nmccray Date 2003-10-01 Time 14:47 Rev Time 0.00
Received By nmccray Date 2003-10-01 Time 14:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-23 Cont ID  
Sent By pschmitz Date 2003-10-23 Time 09:25 Rev Time 1.00
Received By pschmitz Date   Time   Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By btrobaug Date 2003-10-17 Time 11:22 Rev Time 1.00
Received By kstevens Date 2003-10-20 Time 09:28 Sent To  
Notes
2003-10-20 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) 61G15-23.002(1) 2 SETS OF PLANS HAVE
 NO SEAL, SIGNATURE, OR DATE ON THEM.
 61G15-23.002(2) LICENSE NOT SHOWN ON THE
 TITLE BLOCK AS REQUIRED.
 2) 11-4.1.6(1)(B) IF EXISTING ELEMENTS,
 SPACES, OR COMMON AREAS ARE ALTERED,
 THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE
 APPLICABLE PROVISIONS OF 11-4.1.1 TO
 11-4.1.3. SO PER 11-4.1.3, IF TOILET
 ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH
 11-4.22. SUBMIT A DETAIL SHOWING COMPLI-
 ANCE WILL 11-4.22, 11-4.16, & 11-4.19
 AND ALL SUBSECTIONS OF EACH. - ALSO SEE
 SECTION 3401.8.1.1 (BLDG)
 3) THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN, NOR DOES IS MEET
 CODE REQUIREMENTS. 909.1 W/M SHALL NOT
 DRAIN INTO THE HORIZONTAL WET VENT OF
 THE BATHROOM GROUP OF FIXTURES. 708.10
 WASH MACHINE STACK SHALL HAVE A CLEANOUT
 4' ABOVE THE FLOOR.SEE ATTACHED RISER
 FOR AN EXAMPLE OF A RISER THAT MEETS
 CODE REQUIREMENTS AND REFLECTS THE FLOOR
 PLAN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-16 Cont ID  
Sent By btrobaug Date 2003-09-24 Time 12:18 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***