Plan Review Details - Permit 03090776
Plan Review Stops For Permit 03090776
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-29 Cont ID  
Sent By btrobaug Date 2003-09-29 Time 17:29 Rev Time 0.50
Received By btrobaug Date 2003-09-29 Time 17:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By csiegber Date 2003-09-29 Time 14:44 Rev Time 1.00
Received By btrobaug Date 2003-09-19 Time 07:59 Sent To  
Notes
2003-09-23 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION AND RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110.9.
  
 2} PLEASE PROVIDE LOAD CALCULATIONS AND
 PANEL SCHEDULES FOR NEW SERVICE.
  
 3} LINE AND LOAD CONDUCTORS ARE IN THE
 THE SAME ENCLOSURE,MUST BE SEPARATED
 PE 230.7.
  
 4} THE #6 GEC AT THE REAR HOUSE FOR THE
 200 AMP DISCONNECT SHOULD BE A #4 PER
 250.66.
  
 5} INDICATE THE SIZE OF THE GUTTERS USED
 IN FEET AND INCHES, IS THE ONE SHOWN
 18" OR 18'?.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 14:44 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 14:44 Sent To E
Notes
2003-09-29 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 14:45 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 14:45 Sent To E
Notes
***NONE***