Plan Review Details - Permit 03090776
| Plan Review Stops For Permit 03090776 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-09-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-09-29 |
Time |
17:29 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-09-29 |
Time |
17:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-09-23 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-29 |
Time |
14:44 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-09-19 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2003-09-23 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION AND RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110.9. | | | | | | 2} PLEASE PROVIDE LOAD CALCULATIONS AND | | | PANEL SCHEDULES FOR NEW SERVICE. | | | | | | 3} LINE AND LOAD CONDUCTORS ARE IN THE | | | THE SAME ENCLOSURE,MUST BE SEPARATED | | | PE 230.7. | | | | | | 4} THE #6 GEC AT THE REAR HOUSE FOR THE | | | 200 AMP DISCONNECT SHOULD BE A #4 PER | | | 250.66. | | | | | | 5} INDICATE THE SIZE OF THE GUTTERS USED | | | IN FEET AND INCHES, IS THE ONE SHOWN | | | 18" OR 18'?. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-29 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-29 |
Time |
14:44 |
Sent To |
E |
|
| Notes |
| 2003-09-29 00:00:00 | TO BT DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-09-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-12 |
Time |
14:45 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-12 |
Time |
14:45 |
Sent To |
E |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |