Plan Review Details - Permit 03090703
Plan Review Stops For Permit 03090703
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-05-13 Cont ID  
Sent By shill Date 2004-05-13 Time 14:09 Rev Time 1.00
Received By shill Date 2004-05-13 Time 14:09 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-14 Cont ID  
Sent By pkrauss Date 2004-05-04 Time 15:22 Rev Time 2.50
Received By sthyng Date 2003-10-14 Time 10:39 Sent To M
Notes
2003-10-14 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.
  
 2.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE
 STAMPED AND THE RECEIPT ATTACHED TO THE
 APPLICATION.
  
 3.)SHEET M/1 REFERS TO SBC2001.
 GOVERNING CODE IS FBC2001.
  
 4.)SHEET M/1 SHOWS A CEILING OF 9'5",
 FLAT ROOF.THE PLANS SHOW A CEILING
 HEIGHT OF 8'1, PITCHED ROOF.
  
 5.)WINDOWS ANCHOR DETAIL (1/3) TO
 COMPLY WITH FBC1707.4.4.2.
  
 6.)IMPACT PROTECTION REQUIRED, FBC
 1606.1.4.
  
 7.)PRODUCT APPROVALS WERE NOT
 SUBMITTED.PROVIDE TWO LEGIBLE,
 COMPLETE COPIES FOR:SINGLE HUNG
 WINDOW, ROOF, SLIDING GLASS DOOR,
 IMPACT PROTECTION. ANY PRODUCT APPROVALS
 NOT SUBMITTED AT TIME OF ISSUANCE
 WILL NOT BE COVERED UNDER THIS PERMIT
 AND WILL REQUIRE A SEPARATE PERMIT
 APPLICATION WITH ADDITIONAL FEES.
  
 8.)ADDITIONAL FEES DUE (RADON,
 VALUE ADJUSTMENT), $270, BZ231207
 ATTACHED.
  
 9.)PROVIDE A SOILS INVESTIGATION
 REPORT.
  
 10.) THE PLANS CONFLICT; CEMENT TILE
 ROOF IS SHOWN ON THE ELEVATIONS, ASPHALT
 SHINGLES ON THE WALL SECTION.
  
 11.) ATTIC ACCESS TO COMPLY WITH FBC
 2309.6 (SIZE).
  
 12.)THE SH-H32 AT THE TUB IS TO
 COMPLY WITH FBC2405.2 (SAFETY GLASS).
  
 13.)PIGGYBACK SECTION A-A TS12 NAILING
 CONFLICTS WITH CATALOG.
  
 14.)PROVIDE DESIGN INFORMATION ON
 THE PLAN, FBC1606.1.7.
  
 15.)DETAIL B 2/3 SHOWS THE FOOTING
 ATTACHING TO THE EXISTING HOUSE BEAM.
  
 16.)NAILING (TRUSS TO TRUSS TEXT) FOR
 HETAL16 CONFLICTS WITH CATALOG.
  
 17.)WHAT CONNECTOR IS USED FOR THE
 GIRDER?PLAN SAYS "M", COULD NOT FIND
 A DETAIL "M" ON THE PLAN.
  
 18.)PROVIDE A HURRICANE SHUTTER
 ATTACHMENT SCHEDULE (SEE ATTACHED).
 IF THIS IS NOT A PART OF THE ISSUED
 PERMIT, AN SEPARATE PERMIT WILL BE
 REQUIRED.
  
 19.)PROVIDE A SURVEY AND A SITE
 PLAN.
  
 20.)DRYWALL FASTENING (NOTES, 1/3) TO
 COMPLY WITH FBC TABLE 2306.1.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-22 Cont ID  
Sent By csiegber Date 2003-09-17 Time 15:14 Rev Time 0.33
Received By btrobaug Date 2003-09-22 Time 15:23 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-04-30 Cont ID  
Sent By csiegber Date 2004-04-30 Time 15:16 Rev Time 0.00
Received By csiegber Date 2004-04-30 Time 15:16 Sent To M
Notes
2004-04-30 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-04-28 Cont ID  
Sent By mmclean Date 2004-04-29 Time 18:36 Rev Time 0.00
Received By csiegber Date 2004-04-28 Time 10:14 Sent To Z
Notes
2004-04-28 00:00:00RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 15:14 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 15:14 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-11 Cont ID  
Sent By mmclean Date 2003-09-17 Time 14:56 Rev Time 0.00
Received By csiegber Date 2003-09-11 Time 15:09 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2004-05-04 Cont ID  
Sent By pkrauss Date 2004-05-04 Time 15:21 Rev Time 0.35
Received By pkrauss Date 2004-05-04 Time 15:21 Sent To B
Notes
2004-05-04 00:00:00NO MECHANICAL PLANS SUBMITTED FOR REVIEW
 ENERGY CALCULATIONS SUBMITTED WITH
 BUILDING PERMIT.NOTE ON PLAN SHEET
 M/1 INDICATES A/C CONTRACTOR TO SUBMIT
 PLAN.
  
 MECHANICAL CONTRACTOR TO INCLUDE THE
 FOLLOWING:
 1.SUPPLY & RETURN DUCT/GRILLE SIZE,
 MATERIAL AND LAYOUT.
  
 2.RETURN AIR TO COMPLY WITH THE
 ATTACHED SCHEDULE.
  
 3.AUXILIARY DRAIN PAN WITH OVERFLOW
 PROTECTION REQUIRED PER 2001 FBC(M)
 307.2.3.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-10-15 Cont ID  
Sent By csiegber Date 2004-04-30 Time 15:16 Rev Time 0.35
Received By pkrauss Date 2003-10-15 Time 07:00 Sent To  
Notes
2003-10-15 00:00:00DENIED:PLANS ARE INCOMPLETE
 1.PLEASE PROVIDE DUCT LAYOUT INCLUDING
 SIZE OF DUCT AND GRILLES.
  
 2.PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 3.PLEASE NOTE CODE REFERENCE IS
 INCORRECT.SHOULD READ 2001 FBC, MECH.
  
 4.NOTE ON PLAN SHEET REFERENCES PLAN
 SHEET 7/7, NO SUCH DRAWING SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-28 Cont ID  
Sent By sthyng Date 2003-10-14 Time 14:10 Rev Time 0.25
Received By pkrauss Date 2003-09-28 Time 15:01 Sent To B
Notes
2003-09-28 00:00:00PLAN NOTES INDICATE A/C DWG 7/7.NO
 SUCH DRAWING SUBMITTED FOR REVIEW.
 PROVIDE INFORMATION ON THE A/C
 EQUIPMENT AND DUCT LAYOUT WITH
 MECHANICAL PERMIT APPLCIATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-24 Cont ID  
Sent By btrobaug Date 2003-09-22 Time 15:35 Rev Time 0.33
Received By jleech Date 2003-09-24 Time 16:35 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2004-04-29 Cont ID  
Sent By mmclean Date 2004-04-29 Time 18:36 Rev Time 0.00
Received By mmclean Date 2004-04-29 Time 18:36 Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By csiegber Date 2004-04-28 Time 10:14 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-17 00:00:009/17/03 DENIED, NEED TO PROVIDE 2 COPY
 OF SURVEY SHOWING WORK.CALLED OWNER
 3X TIMES NO ANSWER NO MACHINE FILE J MM