| Plan Review Stops For Permit 03090673 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-12-23 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2003-12-23 |
Time |
16:21 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2003-12-23 |
Time |
16:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-12-14 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-19 |
Time |
10:54 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2003-12-14 |
Time |
18:01 |
Sent To |
|
|
| Notes |
| 2003-12-14 00:00:00 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND THE RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 2.)SIGN THE OWNER/AGENT LINE OF THE | | | ENERGY CALC. | | | | | | 3.)PROVISO - SEPARATE PERMIT REQUIRED | | | FOR HURRICANE SHUTTERS AS PRODUCT | | | APPROVALS WERE NOT SUBMITTED. | | | | | | 4.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | NO FEE FOR RESUB |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-11-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-12-13 |
Time |
06:38 |
Rev Time |
0.50 |
| Received By |
sthyng |
Date |
2003-11-08 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2003-11-08 00:00:00 | *****CORRECTIONS****** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)NONE OF THE COMMENTS FROM THE | | | FIRST LIST WERE ADDRESSED.THE SAME | | | PLANS, DATED 6/3/03 WERE SUBMITTED. | | | SEE PREVIOUS LIST AND ADDRESS ALL ITEMS. | | | | | | 2.)SEE ATTACHED NOTICE REGARDING | | | FS553.80(2)(B). | | | | | | 3.)WHEN RESUBMITTING, CLOUD ALL | | | CHANGES.REVISED SHEETS ONLY ARE TO | | | BE REPLACED WITH OLD SHEETS SUBMITTED | | | SEPARATELY. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-31 |
Time |
16:46 |
Rev Time |
2.00 |
| Received By |
sthyng |
Date |
2003-10-15 |
Time |
09:04 |
Sent To |
|
|
| Notes |
| 2003-10-15 00:00:00 | ******CORRECTIONS******* | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)SEPARATE PERMITS REQUIRED. | | | | | | 2.)A NOTICE OF COMMENCEMENT MUST BE | | | FILED WITH THE CLERK OF COURTS. | | | | | | 3.)IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY.THE PLANS MUST BE | | | STAMPED AND RECEIPT ATTACHED TO THE | | | APPLICATION.233-5025 | | | | | | 4.)SUBMIT TWO COPIES OF ALL | | | DOCUMENTATION (PRODUCT APPROVALS, | | | PLANS, ENERGY CALCS, SURVEY). | | | | | | 5.)THE TITLE BLOCK REQUIRES THE | | | ENGINEER'S LICENSE NUMBER, FAC61G15-23.0 | | | 02.EACH SHEET REQUIRES A SEAL, | | | SIGNATURE AND DATE FS471.025. | | | | | | 6.)GENERAL NOTES A1 REFERS TO THE | | | WRONG BUILDING CODE. | | | | | | 7.)FEES DUE (VALUE ADJUSTMENT, | | | RADON) $28.98.SEE ATTACHED BZ231380. | | | | | | 8.)ENERGY CALCS REQUIRED, FBC13-103.1. | | | 2.SIGN OWNER/AGENT LINE OF ENERGY | | | CALC. | | | | | | 9.)SPECIFY UNDER ATTIC INSULATION | | | ON THE WALL SECTION.PLEASE NOTE THAT | | | IF A 600C SHORT FORM IS USED FOR THE | | | ENERGY CALC, MINIMUM WALL INSULATION | | | IS R19 FOR A 2X6 WALL, R30 UNDER ATTIC. | | | REVISE WALL SECTION IF NECESSARY. | | | | | | 10.) SPECIFY STRAPS AND CLIPS, WALL | | | SECTION (A2). | | | | | | 11.)MTS14 IS NOT IN THE SIMPSON 2003 | | | CATALOG; CLARIFY. | | | | | | 12.)BOTTOM OF THE FOOTER IS REQUIRED | | | TO BE A MINIMUM OF 12" BELOW GRADE | | | FBC1804.1.3. | | | | | | 13.)IMPACT PROTECTION REQUIRED | | | FBC1606.1.4.PROVIDE TWO COPIES OF | | | PRODUCT APPROVALS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-11-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-11-26 |
Time |
07:08 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-11-26 |
Time |
06:02 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-10-28 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-25 |
Time |
09:58 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-10-28 |
Time |
07:11 |
Sent To |
P |
|
| Notes |
| 2003-10-28 00:00:00 | PROVISO | | | ~~~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE NOTE THE FOLLOWING IS NOT CODE | | | COMPLIANT. | | | | | | 1} THE NOTE ON SHEET A-4 REGARDING THE | | | SPARE APPLIANCE CIRCUIT BEING "TAPPED" | | | TO BE USED IN THE CLOSET OR BATH DOES | | | NOT CCOMPLY WITH THE INTENT OF | | | 210.52(B)(1) AND CANNOT BE USED IN | | | THESE ROOMS. | | | | | | 2} PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S). PER 210-11-C-3 | | | MUST BE 20A AND #12AWG. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-09-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-24 |
Time |
14:30 |
Rev Time |
0.33 |
| Received By |
btrobaug |
Date |
2003-09-22 |
Time |
15:37 |
Sent To |
P |
|
| Notes |
| 2003-09-22 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOTE: PLEASE NOTE THAT ALL PLANS | | | DRAWN BY AN ARCHITECT/ENGINEER CONTAIN- | | | ING A TITLE BLOCK, MUST BE SIGNED, DATED | | | AND SEALED BY THE ARCH/ENGINEER OF | | | RECORD. PER FS/FAC 481.221 & 471.025 | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2004-12-07 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-12-07 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-12-07 |
Time |
15:22 |
Sent To |
P |
|
| Notes |
| 2004-12-07 00:00:00 | SENT TO "P" BOX, |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-05-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-18 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-05-18 |
Time |
11:42 |
Sent To |
P |
|
| Notes |
| 2004-05-18 00:00:00 | TO KS BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2003-12-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-19 |
Time |
10:54 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-19 |
Time |
10:54 |
Sent To |
B |
|
| Notes |
| 2003-12-19 00:00:00 | TO SH DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-11-25 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-25 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-25 |
Time |
09:58 |
Sent To |
E |
|
| Notes |
| 2003-11-25 00:00:00 | TO BT DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-10-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-24 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-24 |
Time |
14:30 |
Sent To |
E |
|
| Notes |
| 2003-10-24 00:00:00 | TO BT DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-17 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-17 |
Time |
15:13 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-09-17 |
Time |
14:59 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-11 |
Time |
15:21 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2004-12-11 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-12-11 |
Time |
12:34 |
Rev Time |
0.00 |
| Received By |
pschmitz |
Date |
2004-12-11 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2006-05-31 00:00:00 | SUBJECT TO FIELD INSPECTOR APPROVAL |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
F |
Date |
2004-05-19 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2004-05-19 |
Time |
08:22 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2004-05-19 00:00:00 | PLUMBING PLAN REVIEW, DENIED FBS 2001 | | | (1) SEC 104.2.2 DESIGN PROFESSIONAL: | | | ARCHITECT OR ENGINEER SEAL,SIGNAURE, ON | | | ALL PLANSOR REVISIONS,THAT ARE BY A | | | DESIGN PROFESSIONAL. | | | END OF COMMENTS QUESTIONS 561-805-6692 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-12-13 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-05-18 |
Time |
11:43 |
Rev Time |
0.20 |
| Received By |
jleech |
Date |
2003-12-13 |
Time |
06:38 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-10-31 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-11-26 |
Time |
07:08 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-31 |
Time |
16:35 |
Sent To |
B |
|
| Notes |
| 2003-10-31 00:00:00 | DENIED | | | REFERENCE: FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1) ENGINEERS LICENSE NUMBER SHALL BE IN- | | | DICATED ON EACH SHT PER 61G15-23.002(2) | | | NO LICENSE NUMBER IS SHOWN. (SEE BLDG | | | PLAN REVIEW COMMENT #5) | | | ONE SET OF PLANS SHALL BE KEPT ON FILE | | | TO BE TURNED IN TO THE FBPE. | | | | | | 2) TRAP REQUIRED FOR TUB. SEE RED LINE | | | CORRECTION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-10-28 |
Time |
07:18 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2003-09-24 |
Time |
17:09 |
Sent To |
B |
|
| Notes |
| 2003-09-24 00:00:00 | DRAWING HAVE TITLE BLOCK AND NOT SEALED. | | | SEE FS/FAC 481.221 & 471.025. | | | JOHN LEECH | | | PLUMBING PLAN REVIEW | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-09-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-11 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|