| Plan Review Stops For Permit 03090619 |
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-10-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-01 |
Time |
13:45 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-10-01 |
Time |
13:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-09-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-26 |
Time |
14:43 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-09-26 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2003-09-26 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) MANUF INFORMATION INDICATES 246,000 | | | BTU'S FOR 6 BURNER GRILL W/OVEN, BUT | | | GAS RISER DIAGRAM SHOWS 180,000 BTU'S. | | | PLEASE CLAIRFY. | | | 2) MANUF. INFORMATION FOR 3 POT WOK DOES | | | NOT SHOW A LISTING FOR FIXTURE AND DOES | | | NOT INDICATE BTU'S. PLEAS SUBMIT MANUF. | | | INFORMATION. | | | 3) UNION REQUIRED AFTER MANUAL SHUT OFF | | | VALVE AND UPSTREAM OF FIRE VALVE. REGUL- | | | ATOR SHALL BE DOWNSTREAM OF FIRE VALVE. | | | 4) SUBMIT A CUT SHEET FOR REGULATOR. |
|
|
|