| Plan Review Stops For Permit 03090521 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2004-04-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-04-12 |
Time |
09:24 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-04-12 |
Time |
09:24 |
Sent To |
|
|
| Notes |
| 2004-04-12 00:00:00 | STEEL SHOPS PREPARED BY ANAN | | | ALMUGHRABI 12/19/3 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2004-04-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
11:44 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-04-05 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2004-04-05 00:00:00 | ****CORRECTIONS**** | | | USA STEEL SUBMITTALS | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)PROVIDE TWO SETS OF PLANS.ONLY | | | ONE WAS SUBMITTED. | | | | | | 2.)THE PRINTED NAME AND LICENSE | | | NUMBER OF THE PERSON SEALING THE PLAN | | | IS TO BE ON EACH SHEET FAC61G15-23.002. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-02-18 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-02 |
Time |
09:03 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-02-18 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2004-02-18 00:00:00 | REVISION DATED 2/11/04 (FOUNDATION) |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-02-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2004-02-18 |
Time |
12:43 |
Rev Time |
0.50 |
| Received By |
shill |
Date |
2004-02-18 |
Time |
12:43 |
Sent To |
|
|
| Notes |
| 2004-02-18 00:00:00 | ***CORRECTIONS*** | | | | | | STEEL STRUCTURAL DRAWINGS, PHASE II | | | PREPARED BY ANAN ALMUGHRABI, PE 12/19/3 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | 1.)SEE PREVIOUS LIST, ITEM #1.A | | | REQUEST WAS MADE FOR A TITLE BLOCK FOR | | | THE ENGINEER AS PER FAC61G15-23.002. | | | AN ADDRESS WAS PROVIDED FOR THE | | | MANUFACTURER.THIS WOULD REQUIRE AN | | | ENGINEERING AUTHORIZATION NUMBER FOR | | | THE COMPANY AS PER THE FBPE. | | | | | | 2.)SEE PREVIOUS LIST, ITEM #2.NOT | | | ADDRESSED; HAVE REVIEWED BY THE | | | DESIGNER OF RECORD.SEE FAC61G15-30.006 | | | REGARDING DELEGATED ENGINEERS. | | | | | | 3.)IF THIS JOB HAS A RESIDENT | | | INSPECTOR, SUBMIT THREE COPIES. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2004-01-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-12 |
Time |
11:50 |
Rev Time |
1.00 |
| Received By |
shill |
Date |
2004-01-20 |
Time |
09:51 |
Sent To |
|
|
| Notes |
| 2004-01-20 00:00:00 | *****CORRECTIONS****** | | | | | | STEEL STRUCTURAL DRAWINGS, PHASE II | | | PREPARED BY ANAN ALMUGHRABI, PE 12/19/3 | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE TITLE BLOCK FOR THE ENGINEER | | | IS TO INCLUDE THE ADDRESS OF THE | | | ENGINEER FAC61G15-23.002. | | | | | | 2.)SHOP DRAWINGS ARE TO BE REVIEWED | | | BY THE DESIGNER OF RECORD. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-15 |
Time |
12:06 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-12-30 |
Time |
14:38 |
Sent To |
|
|
| Notes |
| 2003-12-30 00:00:00 | PASSED WITH THE FOLLOWING PROVISIONS: | | | | | | 1)THE STAIRS REQUIRE A 42" HIGH | | | GUARDRAIL IN ACCORDANCE WITH FBC | | | 1015.1.PROVIDE AMENDED PLANS AND/OR | | | SHOP DRAWINGS DEMONSTRATING COMPLIANCE | | | BEFORE INSTALLATION. | | | | | | 2)PROVIDE A COPY OF THE UL | | | CERTIFICATEFROM THE MASONRY UNIT | | | SUPPLIER AS PROVIDED FOR IN DESIGN #UL | | | 905 BEFORE INSTALLATION. | | | | | | 3)PROVIDE A SPECIFICATION FOR THE | | | SCREW ANCHOR IN SECTION 1/403.1, SIGNED | | | AND SEALED, THAT CAN BE MADE A PART OF | | | THE PERMIT PLANS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-05 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2003-10-16 |
Time |
12:42 |
Sent To |
|
|
| Notes |
| 2003-10-16 00:00:00 | THE PLANS SPECIFY A FIRE DESIGN OF UL | | | 905 WHICH IN TURN CITES UL LISTED BLOCK | | | MANUFACTURERS THAT MUST BE COMPLIED | | | WITH AT TIME OF INSPECTION. | | | | | | SHEET 308 DECLARES A 3/4 HR RATING FOR | | | THE STAIR DOORS.FBC TABLE 705.1.2 | | | REQUIRES A 1 HOURRATING.SEE ALSO, | | | FBC 705.1.3.4.PLEASE REVISE AS | | | NECESSARY. | | | | | | SHEETS 309 AND 402 DO NOT CITE THE | | | CORRECT MINIMUM DESIGN LOAD CRITERIA AS | | | PROVIDED FOR IN FBC 1608.2. | | | | | | SINCE THE ARCHITECT HAS ASSUMED THE | | | STRUCTURAL RESPONSIBILITIES, SEE RULE | | | 61G-1530 OF THE FL ADMINISTRATIVE CODE | | | FOR THE INFORMATION REQUIRED WHEN | | | DELEGATING DESIGN RESPONSIBILITY SUCH | | | AS THE BAR JOIST DECK SYSTEM FOR THE | | | SECOND FLOOR. | | | | | | PLEASE PROVIDE COMPLETE STRUCTURAL | | | CALCLULATIONS DEMOSTRATING COMPLIANCE | | | WITH THE FBC CHAPTER 16. | | | | | | SECTION 1/403.1 CALLS OUT A "SCREW | | | ANCHOR" FOR THE ANGLE.WHAT IS THE | | | SIZE, DEPTH OF EMBEDMENT AND SPACING OF | | | THE SCREW ANCHORS? | | | | | | SHEET 402 HAS REFERENCE TO SECTION | | | 4/403 FOR A BEAM TO COLUMN DETAIL THAT | | | IS NOT FOUND IN THAT SECTION.PLEASE | | | CLARIFY. | | | | | | SECTION 2/403 HAS A REFERRAL NOTE TO | | | 3/313 FOR THE DOWELS IN THE FLOOR AND | | | THERE IS NO INFORMATION FOR THE DOWELS | | | IN SECTION 3/313.PLEASE CLARIFY. | | | | | | SHEET 603 SHOWS THE A/C DUCT WORK | | | PENETRATING THE STAIR SHAFT.THIS IS | | | PROHIBITTED BY FBC 1006.1.3.1.PLEASE | | | REVISE AS NECESSARY. | | | | | | THE PLANS MUST BE REVIEWED BY PALM BEACH | | | COUNTY FOR IMPACT FEE COORDINATION WITH | | | PHASE I.PLEASE HAVE THE PERMIT PLANS | | | STAMPED BY THAT OFFICE. | | | | | | THE DECLARED PERMIT VALUATION OF | | | $604,125.00 IS TOO LOW FOR THIS SCOPE | | | OF WORK. THE CITY'S ESTIMATE IS | | | $986,141.00.THERE ARE $9447.26 IN | | | PERMIT FEES REMAINING DUE TO THE CITY | | | AS OF THIS DATE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-15 |
Time |
12:06 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-01-15 |
Time |
12:06 |
Sent To |
B |
|
| Notes |
| 2004-01-15 00:00:00 | SENT TO BLDG FOR PROCESSING. | | | | | | REDLINED, MAINS TO BE GROUPED. 230.72 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-01-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-12 |
Time |
06:14 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-01-12 |
Time |
06:14 |
Sent To |
|
|
| Notes |
| 2004-01-12 00:00:00 | ************* UNSAT **************** | | | | | | 1)NOTE: PLANS STILL REFERENCE THE 1999 | | | NEC. THIS HAS BEEN NOTED ON TWO PREVIOUS | | | REVIEWS. PLEASE CORRELATE ALL NEC ARTS | | | TO 2002 NEC AND CHANGE REFERENCES ON | | | PLANS. INLCUDING COVER SHEET /LS PLAN | | | AND ANY OTHERS. | | | | | | 2)NOTE: PLEASE SEE THAT IT WAS ALSO | | | REQUESTED ON PREVIOUS REVIEWS THAT ALL | | | OLD/VOIDED SHEETS BE REMOVED FOR TWO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | PLEASE HAVE NEW SHEETS ISSUED. | | | PLEASE MAKE ALL CODE CHANGES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] | | | SHEETS FOR |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-12-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-12-04 |
Time |
06:39 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-12-04 |
Time |
06:39 |
Sent To |
|
|
| Notes |
| 2003-12-04 00:00:00 | ************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE NOTES FROM FIRST | | | REVIEW. PLEASE SEE 801, THIS SHEET WAS | | | NOT CORRECTED FOR TITLE BLOCK INFORMAT- | | | -ION. | | | PLEASE SIGN PLANS WITH A SIGNATURE AS | | | REQ'D UNDER FS 471.025 AND FAC 61G15-23. | | | 002. | | | PLEASE BE ADVISED, THE FBPE`S HAS | | | NOTIFIED THIS OFFICE INITIALS ARE NOT | | | ACCEPTABLE AND A MIN OF A VISABLE FIRST | | | AND LAST NAME IS REQ'D. /AND OR HOW | | | SIGNATURE IS ON RECORD WITH THE STATE | | | ENG BOARD. | | | | | | 2)NOTE: PLEASE REMOVE ALL OLD/VOIDED | | | SHEETS AND INSERT NEW SHEETS ONLY INTO | | | TWO COMPLETE SETS FOR REVIEW AND STAMP- | | | -ING. ONE STE OF OLD/VOIDED SHEETS MAY | | | BE SUBMITTED FOR COMPARISON. | | | | | | 3)NOTE: PLEASE SEE TWO CLOUDED REV'S | | | SHOWN ON RISER DIAGRAM AROUND MDP/METER | | | LABELED AS #6. ? PLEASE CLARIFY REV? | | | PLANS APPEARS TO BE SAME AS PREVIOUS. | | | | | | 4)NOTE: PLEASE SEE THAT CODES STILL | | | REF 99 NEC. (801) | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-09-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-29 |
Time |
06:32 |
Rev Time |
1.75 |
| Received By |
dpalmer |
Date |
2003-09-29 |
Time |
06:32 |
Sent To |
|
|
| Notes |
| 2003-09-29 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE FAC61G15-23.002 FOR | | | ENGINEERS AND 61G1-16.004 FOR ARCH'S. | | | PLEASE SEE MISSING INFORMATION REQ'D ON | | | TITLE BLOCKS FOR BOTH ENGINEERS AND ARCH | | | 'S. PER FS 471 AND 481 | | | | | | 2)NOTE: PLEASE SEE THAT SOME CIRCUITING | | | FOR EM/EXT LTS ARE NOT PER 700.12E AND | | | ALSO THERE ARE A FEW MISSING CIRCUIT #`S | | | | | | 3)NOTE: PLEASE CLARFIY EM/EXT LTS, THEY | | | ARE SHOWN AS WHAT APPEARS TO BE COMBO | | | FIXTURES, HOWEVER FIXTURE SCHEDULE | | | SHOW THESE AS BEING EXIT ONLY? | | | PLEASE SEE THAT THERE WOULD BE MANY | | | LOCATIONS MISSING EM LTS. PLEASE SEE | | | THAT THERE SOME LOCATION WHERE EM LTS | | | ARE SHOWN. | | | PLEASE ALSO SEE SECOND FLR ON 804, WEST | | | END OF CORRIDOR THAT SEEMS TO NEED AN | | | ADDITIONAL EM LT. | | | THERE ARE ALSO FIXTURES THAT ARE SHOWN | | | JUST AS EXT LTS? | | | PLEASE SEE 700.12E. | | | | | | 4)NOTE: PLEASE SEE CODE ARTS REFERENCED | | | ON PLANS ARE FROM THE 99 NEC. PLEASE SEE | | | THAT AS OF JULY 1ST, 2003 THE STATE | | | ADOPTED THE 2002 NEC. PLEASE ADJUST PLAN | | | -S AND ARTS FOR 2002. | | | | | | 5)NOTE: PLEASE SEE 700.16 FOR LOCATIONS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-12-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-12-12 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-12-12 |
Time |
14:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2003-09-16 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-16 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-16 |
Time |
17:09 |
Sent To |
|
|
| Notes |
| 2003-09-16 00:00:00 | APPROVED PROVISO: | | | | | | 1) ON PAGE 603 IT APPEARS THAT DUCTWORK | | | IS CONTAINED WITHIN THE STAIRWELL AND | | | THEN BREACHES OUT TO OTHER AREAS OF | | | THE BUILDING. ONLY CERTAIN EQUIPMENT | | | CAN BE OBTAINED WITHIN A STAIRWELL. | | | | | | 2) SEPARATE PLANS AND PERMITS ARE | | | REQUIRED FOR FIRE ALARM INSTALLATION. | | | | | | 3) STRAIGHT STAIR ELEVATION ON PAGE | | | 402 MAKES REFERENCE TO "MARTIN COUNTY" | | | THIS JOB IS NOT LOCATED IN MARTIN | | | COUNTY BUT PALM BEACH COUNTY. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2004-07-26 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-26 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-07-26 |
Time |
16:14 |
Sent To |
M |
|
| Notes |
| 2004-07-26 00:00:00 | TO PK BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2004-04-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-07 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-07 |
Time |
11:44 |
Sent To |
B |
|
| Notes |
| 2004-04-07 00:00:00 | TO SH DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2004-04-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-04-02 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-04-02 |
Time |
09:03 |
Sent To |
B |
|
| Notes |
| 2004-04-02 00:00:00 | TO SH DESK/SUBMITTAL PHASE II |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2004-02-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-12 |
Time |
11:50 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-12 |
Time |
11:50 |
Sent To |
B |
|
| Notes |
| 2004-02-12 00:00:00 | TO SH DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2004-02-09 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-02-09 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-02-09 |
Time |
11:01 |
Sent To |
B |
|
| Notes |
| 2004-02-09 00:00:00 | TO SH DESK/REV/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2004-01-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-07 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-07 |
Time |
10:52 |
Sent To |
B |
|
| Notes |
| 2004-01-07 00:00:00 | TO SH/HP DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-01-07 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-07 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-07 |
Time |
10:48 |
Sent To |
|
|
| Notes |
| 2004-01-07 00:00:00 | TO COMM BD#16 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-12-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-05 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-05 |
Time |
09:47 |
Sent To |
B |
|
| Notes |
| 2003-12-05 00:00:00 | TO HP DESK/SUBMITTAL/USA STRUC CALCS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-11-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-17 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-17 |
Time |
14:51 |
Sent To |
|
|
| Notes |
| 2003-11-17 00:00:00 | TO COMM BD#62 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-11 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-11 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2003-09-11 00:00:00 | ON COMM BD#32 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2004-07-29 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2004-07-29 |
Time |
15:17 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2004-07-29 |
Time |
15:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-07-26 |
Time |
16:14 |
Rev Time |
0.50 |
| Received By |
pkrauss |
Date |
2003-12-17 |
Time |
07:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-10-20 |
Time |
06:43 |
Rev Time |
1.15 |
| Received By |
pkrauss |
Date |
2003-10-17 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2003-10-20 00:00:00 | DENIED: | | | 1.PLEASE NOTE AS PER 2001 FBC(M) | | | 601.4EXCEPTION # 2. TRANSFER GRILLES | | | SHALL USE 50 SQUARE INCHES (OF GRILLE | | | AREA) TO 100 CFM (OF SUPPLY AIR) FOR | | | SIZING THROUGH-THE-WALL TRANSFER | | | GRILLES & USING AN UNRESTRICTED 1 INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER | | | RETURN AIR BALANCE.PLEASE REVISE | | | TRANSFER GRILLES TO REFLECT PROPER SIZE. | | | | | | 2.PLAN SHEET 603 INDICATES DUCTWORK | | | ABOVE THE RATED CEILING.THIS SHALL NOT | | | COMPROMISE THE HEIGHT REQUIREMENTS FOR | | | THE STAIRWELL OR ACCESS TO THE DUCT | | | SMOKE DETECTOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2004-01-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2004-01-12 |
Time |
14:57 |
Rev Time |
1.50 |
| Received By |
kstevens |
Date |
2004-01-12 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2004-01-12 00:00:00 | PROVISO - REMOVE ALL OLD PAGES FROM | | | PLANS AND INSERT NEW SHEETS. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-12-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-12 |
Time |
16:50 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-12-12 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2003-12-12 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) ANY CHANGES TO THE SANITARY AND WATER | | | SYSTEMS SHALL BE REFLECTED ON THE SANT. | | | AND WATER RISERS. SEE REVISION #6 ON | | | SHSEET 501. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2003-10-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-15 |
Time |
10:35 |
Rev Time |
2.50 |
| Received By |
kstevens |
Date |
2003-10-15 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2003-10-15 00:00:00 | PASSED/PROVISO | | | | | | BREAKROOM SINKS SHALL COMPLY WITH SECT- | | | ION 11-4.24 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2003-09-11 |
Time |
11:59 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
I |
|
| Notes |
|
|