Plan Review Details - Permit 03090521
Plan Review Stops For Permit 03090521
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-04-12 Cont ID  
Sent By shill Date 2004-04-12 Time 09:24 Rev Time 1.00
Received By shill Date 2004-04-12 Time 09:24 Sent To  
Notes
2004-04-12 00:00:00STEEL SHOPS PREPARED BY ANAN
 ALMUGHRABI 12/19/3

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-04-05 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:44 Rev Time 0.50
Received By shill Date 2004-04-05 Time 11:26 Sent To  
Notes
2004-04-05 00:00:00****CORRECTIONS****
 USA STEEL SUBMITTALS
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)PROVIDE TWO SETS OF PLANS.ONLY
 ONE WAS SUBMITTED.
  
 2.)THE PRINTED NAME AND LICENSE
 NUMBER OF THE PERSON SEALING THE PLAN
 IS TO BE ON EACH SHEET FAC61G15-23.002.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-02-18 Cont ID  
Sent By csiegber Date 2004-04-02 Time 09:03 Rev Time 0.50
Received By shill Date 2004-02-18 Time 14:05 Sent To  
Notes
2004-02-18 00:00:00REVISION DATED 2/11/04 (FOUNDATION)

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-02-18 Cont ID  
Sent By shill Date 2004-02-18 Time 12:43 Rev Time 0.50
Received By shill Date 2004-02-18 Time 12:43 Sent To  
Notes
2004-02-18 00:00:00***CORRECTIONS***
  
 STEEL STRUCTURAL DRAWINGS, PHASE II
 PREPARED BY ANAN ALMUGHRABI, PE 12/19/3
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
  
 1.)SEE PREVIOUS LIST, ITEM #1.A
 REQUEST WAS MADE FOR A TITLE BLOCK FOR
 THE ENGINEER AS PER FAC61G15-23.002.
 AN ADDRESS WAS PROVIDED FOR THE
 MANUFACTURER.THIS WOULD REQUIRE AN
 ENGINEERING AUTHORIZATION NUMBER FOR
 THE COMPANY AS PER THE FBPE.
  
 2.)SEE PREVIOUS LIST, ITEM #2.NOT
 ADDRESSED; HAVE REVIEWED BY THE
 DESIGNER OF RECORD.SEE FAC61G15-30.006
 REGARDING DELEGATED ENGINEERS.
  
 3.)IF THIS JOB HAS A RESIDENT
 INSPECTOR, SUBMIT THREE COPIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-01-20 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:50 Rev Time 1.00
Received By shill Date 2004-01-20 Time 09:51 Sent To  
Notes
2004-01-20 00:00:00*****CORRECTIONS******
  
 STEEL STRUCTURAL DRAWINGS, PHASE II
 PREPARED BY ANAN ALMUGHRABI, PE 12/19/3
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE TITLE BLOCK FOR THE ENGINEER
 IS TO INCLUDE THE ADDRESS OF THE
 ENGINEER FAC61G15-23.002.
  
 2.)SHOP DRAWINGS ARE TO BE REVIEWED
 BY THE DESIGNER OF RECORD.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-12-30 Cont ID  
Sent By dpalmer Date 2004-01-15 Time 12:06 Rev Time 0.00
Received By hpiskura Date 2003-12-30 Time 14:38 Sent To  
Notes
2003-12-30 00:00:00PASSED WITH THE FOLLOWING PROVISIONS:
  
 1)THE STAIRS REQUIRE A 42" HIGH
 GUARDRAIL IN ACCORDANCE WITH FBC
 1015.1.PROVIDE AMENDED PLANS AND/OR
 SHOP DRAWINGS DEMONSTRATING COMPLIANCE
 BEFORE INSTALLATION.
  
 2)PROVIDE A COPY OF THE UL
 CERTIFICATEFROM THE MASONRY UNIT
 SUPPLIER AS PROVIDED FOR IN DESIGN #UL
 905 BEFORE INSTALLATION.
  
 3)PROVIDE A SPECIFICATION FOR THE
 SCREW ANCHOR IN SECTION 1/403.1, SIGNED
 AND SEALED, THAT CAN BE MADE A PART OF
 THE PERMIT PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:47 Rev Time 0.00
Received By hpiskura Date 2003-10-16 Time 12:42 Sent To  
Notes
2003-10-16 00:00:00THE PLANS SPECIFY A FIRE DESIGN OF UL
 905 WHICH IN TURN CITES UL LISTED BLOCK
 MANUFACTURERS THAT MUST BE COMPLIED
 WITH AT TIME OF INSPECTION.
  
 SHEET 308 DECLARES A 3/4 HR RATING FOR
 THE STAIR DOORS.FBC TABLE 705.1.2
 REQUIRES A 1 HOURRATING.SEE ALSO,
 FBC 705.1.3.4.PLEASE REVISE AS
 NECESSARY.
  
 SHEETS 309 AND 402 DO NOT CITE THE
 CORRECT MINIMUM DESIGN LOAD CRITERIA AS
 PROVIDED FOR IN FBC 1608.2.
  
 SINCE THE ARCHITECT HAS ASSUMED THE
 STRUCTURAL RESPONSIBILITIES, SEE RULE
 61G-1530 OF THE FL ADMINISTRATIVE CODE
 FOR THE INFORMATION REQUIRED WHEN
 DELEGATING DESIGN RESPONSIBILITY SUCH
 AS THE BAR JOIST DECK SYSTEM FOR THE
 SECOND FLOOR.
  
 PLEASE PROVIDE COMPLETE STRUCTURAL
 CALCLULATIONS DEMOSTRATING COMPLIANCE
 WITH THE FBC CHAPTER 16.
  
 SECTION 1/403.1 CALLS OUT A "SCREW
 ANCHOR" FOR THE ANGLE.WHAT IS THE
 SIZE, DEPTH OF EMBEDMENT AND SPACING OF
 THE SCREW ANCHORS?
  
 SHEET 402 HAS REFERENCE TO SECTION
 4/403 FOR A BEAM TO COLUMN DETAIL THAT
 IS NOT FOUND IN THAT SECTION.PLEASE
 CLARIFY.
  
 SECTION 2/403 HAS A REFERRAL NOTE TO
 3/313 FOR THE DOWELS IN THE FLOOR AND
 THERE IS NO INFORMATION FOR THE DOWELS
 IN SECTION 3/313.PLEASE CLARIFY.
  
 SHEET 603 SHOWS THE A/C DUCT WORK
 PENETRATING THE STAIR SHAFT.THIS IS
 PROHIBITTED BY FBC 1006.1.3.1.PLEASE
 REVISE AS NECESSARY.
  
 THE PLANS MUST BE REVIEWED BY PALM BEACH
 COUNTY FOR IMPACT FEE COORDINATION WITH
 PHASE I.PLEASE HAVE THE PERMIT PLANS
 STAMPED BY THAT OFFICE.
  
 THE DECLARED PERMIT VALUATION OF
 $604,125.00 IS TOO LOW FOR THIS SCOPE
 OF WORK. THE CITY'S ESTIMATE IS
 $986,141.00.THERE ARE $9447.26 IN
 PERMIT FEES REMAINING DUE TO THE CITY
 AS OF THIS DATE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-15 Cont ID  
Sent By dpalmer Date 2004-01-15 Time 12:06 Rev Time 0.50
Received By dpalmer Date 2004-01-15 Time 12:06 Sent To B
Notes
2004-01-15 00:00:00SENT TO BLDG FOR PROCESSING.
  
 REDLINED, MAINS TO BE GROUPED. 230.72

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-01-12 Cont ID  
Sent By dpalmer Date 2004-01-12 Time 06:14 Rev Time 0.50
Received By dpalmer Date 2004-01-12 Time 06:14 Sent To  
Notes
2004-01-12 00:00:00************* UNSAT ****************
  
 1)NOTE: PLANS STILL REFERENCE THE 1999
 NEC. THIS HAS BEEN NOTED ON TWO PREVIOUS
 REVIEWS. PLEASE CORRELATE ALL NEC ARTS
 TO 2002 NEC AND CHANGE REFERENCES ON
 PLANS. INLCUDING COVER SHEET /LS PLAN
 AND ANY OTHERS.
  
 2)NOTE: PLEASE SEE THAT IT WAS ALSO
 REQUESTED ON PREVIOUS REVIEWS THAT ALL
 OLD/VOIDED SHEETS BE REMOVED FOR TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE HAVE NEW SHEETS ISSUED.
 PLEASE MAKE ALL CODE CHANGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
 SHEETS FOR

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-12-04 Cont ID  
Sent By dpalmer Date 2003-12-04 Time 06:39 Rev Time 1.00
Received By dpalmer Date 2003-12-04 Time 06:39 Sent To  
Notes
2003-12-04 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE NOTES FROM FIRST
 REVIEW. PLEASE SEE 801, THIS SHEET WAS
 NOT CORRECTED FOR TITLE BLOCK INFORMAT-
 -ION.
 PLEASE SIGN PLANS WITH A SIGNATURE AS
 REQ'D UNDER FS 471.025 AND FAC 61G15-23.
 002.
 PLEASE BE ADVISED, THE FBPE`S HAS
 NOTIFIED THIS OFFICE INITIALS ARE NOT
 ACCEPTABLE AND A MIN OF A VISABLE FIRST
 AND LAST NAME IS REQ'D. /AND OR HOW
 SIGNATURE IS ON RECORD WITH THE STATE
 ENG BOARD.
  
 2)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW SHEETS ONLY INTO
 TWO COMPLETE SETS FOR REVIEW AND STAMP-
 -ING. ONE STE OF OLD/VOIDED SHEETS MAY
 BE SUBMITTED FOR COMPARISON.
  
 3)NOTE: PLEASE SEE TWO CLOUDED REV'S
 SHOWN ON RISER DIAGRAM AROUND MDP/METER
 LABELED AS #6. ? PLEASE CLARIFY REV?
 PLANS APPEARS TO BE SAME AS PREVIOUS.
  
 4)NOTE: PLEASE SEE THAT CODES STILL
 REF 99 NEC. (801)
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-29 Cont ID  
Sent By dpalmer Date 2003-09-29 Time 06:32 Rev Time 1.75
Received By dpalmer Date 2003-09-29 Time 06:32 Sent To  
Notes
2003-09-29 00:00:00************** UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC61G15-23.002 FOR
 ENGINEERS AND 61G1-16.004 FOR ARCH'S.
 PLEASE SEE MISSING INFORMATION REQ'D ON
 TITLE BLOCKS FOR BOTH ENGINEERS AND ARCH
 'S. PER FS 471 AND 481
  
 2)NOTE: PLEASE SEE THAT SOME CIRCUITING
 FOR EM/EXT LTS ARE NOT PER 700.12E AND
 ALSO THERE ARE A FEW MISSING CIRCUIT #`S
  
 3)NOTE: PLEASE CLARFIY EM/EXT LTS, THEY
 ARE SHOWN AS WHAT APPEARS TO BE COMBO
 FIXTURES, HOWEVER FIXTURE SCHEDULE
 SHOW THESE AS BEING EXIT ONLY?
 PLEASE SEE THAT THERE WOULD BE MANY
 LOCATIONS MISSING EM LTS. PLEASE SEE
 THAT THERE SOME LOCATION WHERE EM LTS
 ARE SHOWN.
 PLEASE ALSO SEE SECOND FLR ON 804, WEST
 END OF CORRIDOR THAT SEEMS TO NEED AN
 ADDITIONAL EM LT.
 THERE ARE ALSO FIXTURES THAT ARE SHOWN
 JUST AS EXT LTS?
 PLEASE SEE 700.12E.
  
 4)NOTE: PLEASE SEE CODE ARTS REFERENCED
 ON PLANS ARE FROM THE 99 NEC. PLEASE SEE
 THAT AS OF JULY 1ST, 2003 THE STATE
 ADOPTED THE 2002 NEC. PLEASE ADJUST PLAN
 -S AND ARTS FOR 2002.
  
 5)NOTE: PLEASE SEE 700.16 FOR LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-12-12 Cont ID  
Sent By mcarsill Date 2003-12-12 Time 14:16 Rev Time 0.00
Received By mcarsill Date 2003-12-12 Time 14:16 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-09-16 Cont ID  
Sent By mcarsill Date 2003-09-16 Time 17:09 Rev Time 0.00
Received By mcarsill Date 2003-09-16 Time 17:09 Sent To  
Notes
2003-09-16 00:00:00APPROVED PROVISO:
  
 1) ON PAGE 603 IT APPEARS THAT DUCTWORK
 IS CONTAINED WITHIN THE STAIRWELL AND
 THEN BREACHES OUT TO OTHER AREAS OF
 THE BUILDING. ONLY CERTAIN EQUIPMENT
 CAN BE OBTAINED WITHIN A STAIRWELL.
  
 2) SEPARATE PLANS AND PERMITS ARE
 REQUIRED FOR FIRE ALARM INSTALLATION.
  
 3) STRAIGHT STAIR ELEVATION ON PAGE
 402 MAKES REFERENCE TO "MARTIN COUNTY"
 THIS JOB IS NOT LOCATED IN MARTIN
 COUNTY BUT PALM BEACH COUNTY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2004-07-26 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:14 Rev Time 0.00
Received By csiegber Date 2004-07-26 Time 16:14 Sent To M
Notes
2004-07-26 00:00:00TO PK BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2004-04-07 Cont ID  
Sent By csiegber Date 2004-04-07 Time 11:44 Rev Time 0.00
Received By csiegber Date 2004-04-07 Time 11:44 Sent To B
Notes
2004-04-07 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2004-04-02 Cont ID  
Sent By csiegber Date 2004-04-02 Time 09:03 Rev Time 0.00
Received By csiegber Date 2004-04-02 Time 09:03 Sent To B
Notes
2004-04-02 00:00:00TO SH DESK/SUBMITTAL PHASE II

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2004-02-12 Cont ID  
Sent By csiegber Date 2004-02-12 Time 11:50 Rev Time 0.00
Received By csiegber Date 2004-02-12 Time 11:50 Sent To B
Notes
2004-02-12 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-02-09 Cont ID  
Sent By csiegber Date 2004-02-09 Time 11:01 Rev Time 0.00
Received By csiegber Date 2004-02-09 Time 11:01 Sent To B
Notes
2004-02-09 00:00:00TO SH DESK/REV/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 10:52 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 10:52 Sent To B
Notes
2004-01-07 00:00:00TO SH/HP DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-07 Cont ID  
Sent By csiegber Date 2004-01-07 Time 10:49 Rev Time 0.00
Received By csiegber Date 2004-01-07 Time 10:48 Sent To  
Notes
2004-01-07 00:00:00TO COMM BD#16

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-05 Cont ID  
Sent By csiegber Date 2003-12-05 Time 09:47 Rev Time 0.00
Received By csiegber Date 2003-12-05 Time 09:47 Sent To B
Notes
2003-12-05 00:00:00TO HP DESK/SUBMITTAL/USA STRUC CALCS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-17 Cont ID  
Sent By csiegber Date 2003-11-17 Time 14:51 Rev Time 0.00
Received By csiegber Date 2003-11-17 Time 14:51 Sent To  
Notes
2003-11-17 00:00:00TO COMM BD#62

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-11 Cont ID  
Sent By csiegber Date 2003-09-11 Time 16:44 Rev Time 0.00
Received By csiegber Date 2003-09-11 Time 16:44 Sent To  
Notes
2003-09-11 00:00:00ON COMM BD#32

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2004-07-29 Cont ID  
Sent By hmoser Date 2004-07-29 Time 15:17 Rev Time 0.50
Received By hmoser Date 2004-07-29 Time 15:16 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-17 Cont ID  
Sent By csiegber Date 2004-07-26 Time 16:14 Rev Time 0.50
Received By pkrauss Date 2003-12-17 Time 07:08 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-10-20 Cont ID  
Sent By pkrauss Date 2003-10-20 Time 06:43 Rev Time 1.15
Received By pkrauss Date 2003-10-17 Time 10:18 Sent To  
Notes
2003-10-20 00:00:00DENIED:
 1.PLEASE NOTE AS PER 2001 FBC(M)
 601.4EXCEPTION # 2. TRANSFER GRILLES
 SHALL USE 50 SQUARE INCHES (OF GRILLE
 AREA) TO 100 CFM (OF SUPPLY AIR) FOR
 SIZING THROUGH-THE-WALL TRANSFER
 GRILLES & USING AN UNRESTRICTED 1 INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE.PLEASE REVISE
 TRANSFER GRILLES TO REFLECT PROPER SIZE.
  
 2.PLAN SHEET 603 INDICATES DUCTWORK
 ABOVE THE RATED CEILING.THIS SHALL NOT
 COMPROMISE THE HEIGHT REQUIREMENTS FOR
 THE STAIRWELL OR ACCESS TO THE DUCT
 SMOKE DETECTOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2004-01-12 Cont ID  
Sent By kstevens Date 2004-01-12 Time 14:57 Rev Time 1.50
Received By kstevens Date 2004-01-12 Time 14:57 Sent To  
Notes
2004-01-12 00:00:00PROVISO - REMOVE ALL OLD PAGES FROM
 PLANS AND INSERT NEW SHEETS.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-12-12 Cont ID  
Sent By kstevens Date 2003-12-12 Time 16:50 Rev Time 0.50
Received By kstevens Date 2003-12-12 Time 16:50 Sent To  
Notes
2003-12-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) ANY CHANGES TO THE SANITARY AND WATER
 SYSTEMS SHALL BE REFLECTED ON THE SANT.
 AND WATER RISERS. SEE REVISION #6 ON
 SHSEET 501.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-10-15 Cont ID  
Sent By kstevens Date 2003-10-15 Time 10:35 Rev Time 2.50
Received By kstevens Date 2003-10-15 Time 10:34 Sent To  
Notes
2003-10-15 00:00:00PASSED/PROVISO
  
 BREAKROOM SINKS SHALL COMPLY WITH SECT-
 ION 11-4.24

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-11 Cont ID  
Sent By sgraham Date 2003-09-11 Time 11:59 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***