Plan Review Details - Permit 03090435
Plan Review Stops For Permit 03090435
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-23 Cont ID  
Sent By btrobaug Date 2003-11-04 Time 11:38 Rev Time 0.50
Received By sthyng Date 2003-10-23 Time 12:48 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-14 Cont ID  
Sent By btrobaug Date 2003-10-23 Time 07:32 Rev Time 0.50
Received By sthyng Date 2003-10-14 Time 08:41 Sent To  
Notes
2003-10-14 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)PLANS DRAWN BY AN ARCHITECT MUST
 BE SEALED, SIGNED AND DATED BY THE
 ARCHITECT, FS481.221.
  
 2.)THE WINDOW AT THE EX.TUB/NEW SHOWER
 PAN IS TO COMPLY WITH FBC2405.1
 (SAFETY GLASS).
  
 3.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-04 Cont ID  
Sent By btrobaug Date 2003-11-04 Time 11:38 Rev Time 0.25
Received By btrobaug Date 2003-11-04 Time 11:35 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-23 Cont ID  
Sent By csiegber Date 2003-10-28 Time 16:30 Rev Time 0.50
Received By sthyng Date 2003-10-23 Time 06:50 Sent To B
Notes
2003-10-23 00:00:00UNSAT
 ~~~~~
 PER 101.4.3 & 104.1.1 FBC,AN ELECTRICAL
 PERMIT IS REQUIRED FOR THIS WORK.NO
 ELECTRICAL PERMIT HAS BEEN APPLIED FOR.
 PLEASE HAVE ELECTRICAL CONTRACTOR OBTAIN
 A PERMIT PRIOR TO BEGINNING WORK.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 FBC 104.2ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
  
 A NOTICE OF COMMENCEMENT MUST BE FILED
 WITH THE CLERK OF COURTS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-25 Cont ID  
Sent By sthyng Date 2003-10-22 Time 15:46 Rev Time 0.50
Received By btrobaug Date 2003-09-25 Time 10:31 Sent To B
Notes
2003-09-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THERE IS NO ELECTRICAL CONTRACTOR
 SIGNED ON THIS APPLICATION,AND THE
 DESCRIPTION OF ELECTRICAL WORK IS NOT
 CLEAR.
 PLEASE HAVE ELECTRICAL CONTRACTOR PRO-
 VIDE A DESCRIPTION OF THE INTENDED ON
 HIS APPLICATION.
  
 NOTE: PLEASE NOTE THAT ALL PLANS
 DRAWN BY AN ARCHITECT/ENGINEER CONTAIN-
 ING A TITLE BLOCK, MUST BE SIGNED,
 DATE DAND SEALED BY THE ARCH/ENGINEER OF
 RECORD. PER FS/FAC 481.221 & 471.025
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-28 Cont ID  
Sent By csiegber Date 2003-10-28 Time 16:30 Rev Time 0.00
Received By csiegber Date 2003-10-28 Time 16:30 Sent To E
Notes
2003-10-28 00:00:00TO BT DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-22 Cont ID  
Sent By csiegber Date 2003-10-22 Time 15:01 Rev Time 0.00
Received By sthyng Date 2003-10-22 Time 15:00 Sent To E
Notes
2003-10-22 00:00:00TO ST DESK/RESUB
 TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-09 Cont ID  
Sent By csiegber Date 2003-09-09 Time 15:21 Rev Time 0.00
Received By csiegber Date 2003-09-09 Time 15:21 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-09-09 Time 15:21 Rev Time 0.25
Received By jleech Date 2003-09-24 Time 18:11 Sent To E
Notes
***NONE***