| 2003-09-12 00:00:00 | ************** UNSAT ************** |
| | |
| | 1)NOTE: PLEASE SEE THAT TOTAL VALUE IS |
| | INCLUDE LABOR AND MATERIALS. |
| | PLEASE ADJUST VALUE. FBC 104.6.5 |
| | |
| | 2)NOTE: PLEASE SEE THAT PLANS ARE NOT |
| | COMPLETE FOR ELECTRICAL REWIRE OF HOUSE. |
| | PLEASE SEE THE FOLLOWING NOTES. |
| | |
| | 3)NOTE: PLEASE SEE 210.52 FOR MISSING |
| | RECEPT SPACING. |
| | |
| | 4)NOTE: PLEASE CLARIFY BATH UPSTAIRS |
| | SHOWING A RECEPT ON EACH WALL? PLEASE |
| | SEE THAT RECEPTS ARE NOT PERMITTED IN |
| | SHOWERS OR BATH TUB AREAS. NEC 300 |
| | |
| | 5)NOTE: PLEASE SEE NFPA-72 8-1.4.2 FOR |
| | MISSING SD LOCATIONS REQ'D. |
| | |
| | 6)NOTE: PLEASE CLARIFY # OF RECEPTS |
| | INSTALLED IN WALK-IN CLOSET. PLEASE NOTE |
| | THAT CLOSETS ARE NOT REQ'D TO HAVE |
| | OUTLETS PER 210.52 |
| | |
| | 7)NOTE: PLEASE SEE THAT 2 SM APPL |
| | CIRCUITS ARE REQ'D FOR MIN. 210.11C1 |
| | |
| | 8)NOTE: PLEASE SEE 210.70 FOR MIN EGRESS |
| | LIGHTING REQ'D. |
| | |
| | 9)NOTE: PLEASE SEE 210.52C 1,2,3 ETC FOR |
| | RECEPT SPACING IN KITCHENS. |
| | |
| | 10)NOTE: PLEASE SHOW KW RATINGS FOR AHU' |
| | S, SHOWN W/ #6 AND 2P50.? PLEASE SEE |
| | 424.3B |
| | |
| | 11)NOTE: PLEASE LIST THE REQ'D ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12 ON PANEL |
| | SCHEDULE. |
| | |
| | 12)NOTE: DISC'S FOR A/C UNITS AND |
| | LOCATIONS PER 440.11 |
| | RECEPTS PER 210.63 |
| | |
| | 13)NOTE: PLEASE SUBMIT AIC RATING FOR |
| | NEW MAIN. |
| | |
| | PLEASE COMPLETE PLANS TO CONFORM TO NEC |
| | AND SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |