Plan Review Details - Permit 03090351
Plan Review Stops For Permit 03090351
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-10-07 Cont ID  
Sent By jleech Date 2003-09-23 Time 20:00 Rev Time 3.00
Received By rmcdouga Date 2003-10-07 Time 08:51 Sent To  
Notes
2003-10-07 00:00:00BUILDING PROVISO
  
 1) SUBMIT THE MANUFACTURER'S SPECS. AND
 UL LISTING INFORMATION FOR PREFAB
 FIREPLACE. SUBMIT SPECS. AND LISTING FOR
 FLUE PIPE. SUBMIT SIGNED AND SEALED
 DRAWINGS OF THE FRAMING, BRACING AND
 STRAPPING DETAILS FOR CHIMNEY PRIOR TO
 ROOF FRAMING INSPECTION.
  
 2) SUBMIT SIGNED AND SEALED DRAWINGS OF
 ANY SPECIAL BRACING OR FRAMING THAT WILL
 BE REQUIRED AT THE CANTILEVER TRUSSES ON
 THE COVERED PORCH.
  
 3) SUBMIT SPECIFICATIONS AND LISTING
 INFORMATION FOR THE OPTIONAL BBQ IF IT
 WILL BE INSTALLED.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-16 Time 11:06 Rev Time 0.75
Received By btrobaug Date 2003-09-17 Time 17:39 Sent To M
Notes
2003-09-17 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
  
 THE GEC MUST BE INSTALLED #2 CU PER 210.
 66.
  
 THE BATH CIRCUITS MUST BE INSTALLED PER
 210.11(C)(3),#12 ON A 20A CIRCUIT(S).
  
 NOTE THAT PER 210.12 ALL BRANCH CIRCUITS
 ~~~~~~~~SHALL BE PROTECTED BY ARC FAULT
 CIRCUIT INTERRUPTER.THAT INCLUDES LIGHT
 OUTLETS AND SMOKE DETECTORS AS WELL AS
 RECEPTACLES.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-16 Time 11:06 Rev Time 0.00
Received By csiegber Date 2003-09-16 Time 11:06 Sent To E
Notes
2003-09-16 00:00:00ON SFD RACK/E

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-09 Cont ID  
Sent By mmclean Date 2003-09-16 Time 08:52 Rev Time 0.00
Received By csiegber Date 2003-09-09 Time 09:57 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-23 Cont ID  
Sent By btrobaug Date 2003-09-17 Time 18:08 Rev Time 0.25
Received By pkrauss Date 2003-09-23 Time 07:32 Sent To P
Notes
2003-09-23 00:00:00PROVISO:
 PLEASE NOTE, REVISION TO THE 2001
 FBC(M) 601.4, EFFECTIVE JUNE 30,2003:
  
 BALANCED AIR RETURN - RETURN/TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM ITS SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-23 Cont ID  
Sent By pkrauss Date 2003-09-23 Time 07:37 Rev Time 0.33
Received By jleech Date 2003-09-23 Time 19:59 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-09 Time 09:58 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***