Plan Review Details - Permit 03090282
Plan Review Stops For Permit 03090282
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-15 Cont ID  
Sent By kstevens Date 2003-10-10 Time 18:21 Rev Time 0.50
Received By lsmith Date 2003-09-15 Time 11:13 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By dpalmer Date 2003-10-10 Time 14:22 Rev Time 0.25
Received By dpalmer Date 2003-10-10 Time 14:22 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-15 Cont ID  
Sent By csiegber Date 2003-10-08 Time 11:57 Rev Time 0.25
Received By dpalmer Date 2003-09-15 Time 07:29 Sent To B
Notes
2003-09-15 00:00:00***************UNSAT *****************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 PLEASE SEE MISSING INFORMATION REQ'D ON
 TITLE BLOCK FOR ENGINEER OF RECORD.
 PLEASE NOTE, THIS HAS BEEN REQUESTED ON
 MANY OTHER REVIEWS.
 ALL INFORMATION SHOULD BE LEGIBLE AND/OR
 PRINTED.
  
 2)NOTE: PLEASE SEE PLUMB REVIEW COMMENTS
 THAT WILL AFFECT ELECTRICAL SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-08 Cont ID  
Sent By csiegber Date 2003-10-08 Time 11:57 Rev Time 0.00
Received By csiegber Date 2003-10-08 Time 11:57 Sent To E
Notes
2003-10-08 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-05 Cont ID  
Sent By csiegber Date 2003-09-05 Time 15:58 Rev Time 0.00
Received By csiegber Date 2003-09-05 Time 15:58 Sent To Z
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By kstevens Date 2003-10-10 Time 18:21 Rev Time 0.33
Received By kstevens Date 2003-10-10 Time 18:21 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-13 Cont ID  
Sent By dpalmer Date 2003-10-10 Time 14:22 Rev Time 0.50
Received By kstevens Date 2003-09-13 Time 18:18 Sent To E
Notes
2003-09-13 00:00:00DENIED
 REFERENCE: FBC-2001 242.2 SWIMMING POOLS
 FLORIDA ADMINISTRATIVE CODE
  
 A) PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR PLAN REVIEW.
 1) FBC-2001424.2.6.6.2 SHOW COMPLIANCE
 WITH ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL OR ADD NOTE)(SUBMITTAL)
 2) FBC-2001 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 3) FBC-2001 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2001 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2001 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6) FBC-2001 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 7) FBC02001 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 8) 61G15-23.002(2) LICENSE NUMBER SHALL
 BE ON EACH SHEET.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-09-05 Time 15:58 Rev Time 0.00
Received By mmclean Date   Time   Sent To P
Notes
***NONE***