| 2003-09-11 00:00:00 | ********* UNSAT ***************** |
| | |
| | 1)NOTE: PLEASE SHOW LOCATION OF MAIN |
| | PANEL ON PLANS. |
| | |
| | 2)NOTE: PLEASE SHOW SIZE OF OCP FOR FEED |
| | TO NEW PANEL. SHOWS 6/3 ROMEX WHICH IS |
| | NOW PERMITTED, HOWEVER, ROMEX MUST BE |
| | PROTECTED FROM ALL PHYSICAL DAMAGE AND |
| | MUST MEET NEC. |
| | |
| | 3)NOTE: PLEASE SHOW ALL OUTLETS SERVING |
| | KITCHEN COUNTERSPACE AS GFI'S. |
| | 210.8A6 |
| | |
| | 4)NOTE: PLEASE LIST THE REQ'D DEDICATED |
| | BATH CIRCUIT(S) PER 210.52D/ 210.11C3 |
| | #1220A |
| | |
| | 5)NOTE: PLEASE SHOW REQ'D SD'S INSIDE |
| | AND OUTSIDE SLEEPING ROOMS. NFPA-72 |
| | 8-1.4.2 |
| | |
| | 6)NOTE: PLEASE CORRELATE PLANS SUBMITTED |
| | , REVERSE SIDE OF DRAWING SHOWS A |
| | COMPLETELY DIFFERENT LAYOUT?? |
| | |
| | 7)NOTE: PLEASE SEE PLAN, APPEARS TO SHOW |
| | PANEL IN BATHROOM? THIS IS NOT PERMITTED |
| | PER 240.24 NEC |
| | |
| | 8)NOTE: PLEASE SEE 210.52E FOR FRONT AND |
| | REAR RECEPT REQ'D. |
| | |
| | 9)NOTE: PLEASE CLARIFY IF THERE IS A |
| | SECOND MEANS OF EGRESS. IF SO, PLEASE |
| | SEE 210.70 FOR LT/SW REQ'D. |
| | |
| | 10)NOTE: PLEASE SEE LOAD CALCS, SHOWS |
| | RANGES AS GAS, HOWEVER WATER HEATER AND |
| | WASHER/ DRYER IS SHOWN AS N/A, |
| | PLEASE CLARIFY IF GAS ALSO. |
| | PLEASE SEE 220.16B FOR MIN CIRCUIT REQ'D |
| | FOR WASHER. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |