Plan Review Details - Permit 03090208
Plan Review Stops For Permit 03090208
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-11 Cont ID  
Sent By dpalmer Date 2003-10-24 Time 10:19 Rev Time 0.00
Received By hpiskura Date 2003-09-11 Time 10:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-24 Cont ID  
Sent By dpalmer Date 2003-10-24 Time 10:19 Rev Time 0.33
Received By dpalmer Date 2003-10-24 Time 10:18 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-24 Time 09:41 Rev Time 0.25
Received By dpalmer Date 2003-10-21 Time 11:58 Sent To  
Notes
2003-10-21 00:00:00**************** UNSAT ***********
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FS 471.025
 PLEASE SEE THAT PLANS DONE BY ENGINEER
 MUST BE SIGNED, DATED AND SEALED BY
 ENGINEER ON TITLE BLOCK.
 IF WORK WAS NOT DONE BY "CHANE ENG"
 PLEASE REMOVE TITLE BLOCK AND ARCH MAY
 SIGN,DATE AND SEAL.
 PLEASE BE SURE THAT BOTH SETS ARE SIGN,
 DATED AND SEALED FOR REVIEW AND STAMPING
 PLEASE SEE THAT THIS WAS NOT A COMMENT
 ON FIRST REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-16 Cont ID  
Sent By dpalmer Date 2003-09-16 Time 08:11 Rev Time 0.50
Received By dpalmer Date 2003-09-16 Time 08:07 Sent To  
Notes
2003-09-16 00:00:00PERMIT APPL NEEDS SUITE #.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-21 Cont ID  
Sent By nmccray Date 2003-10-21 Time 09:42 Rev Time 0.00
Received By nmccray Date 2003-10-21 Time 09:41 Sent To  
Notes
2003-10-21 00:00:00************PROVISO*********************
 SEPARATE SHOP DRAWING AND PERMIT ARE
 REQUIRED FOR FIRE SPRINKLER SYSTEM.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By csiegber Date 2003-10-14 Time 16:25 Rev Time 0.00
Received By mcarsill Date 2003-09-10 Time 15:54 Sent To  
Notes
2003-09-10 00:00:001) THE EXISTING HOT WATER ROOM, OFFICE,
 AND MALE HANDICAP TOILET DO NOT
 APPEAR TO BE FIRE SPRINKLER PROTECTED
 PER DRAWING 3/7. PLEASE ADVISE AND
 REVISE AS NECESSARY.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-14 Cont ID  
Sent By csiegber Date 2003-10-14 Time 16:25 Rev Time 0.00
Received By csiegber Date 2003-10-14 Time 16:25 Sent To FIRE
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 16:35 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 16:35 Sent To  
Notes
2003-09-04 00:00:00TO COMM BD #20

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-10-22 Cont ID  
Sent By pkrauss Date 2003-10-22 Time 11:12 Rev Time 0.25
Received By pkrauss Date 2003-10-22 Time 11:12 Sent To  
Notes
2003-10-22 00:00:00SUBMITTAL LETTER FROM ENGINEER (MR.
 CHANE) FOR INSTALLATION OF DUCT SMOKE
 DETECTORS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2003-10-20 Cont ID  
Sent By pkrauss Date 2003-10-20 Time 13:21 Rev Time 0.35
Received By pkrauss Date 2003-10-20 Time 13:15 Sent To P
Notes
2003-10-20 00:00:00DENIED:
 RESPONSE LETTER REVIEW NOTE 3, SEE
 SHEET M2 REVISION 1.DRAWING M2 NOT
 SUBMITTED.PLAN SHEET M1 INDICATES
 OUTSIDE AIR CALCULATIONS BUT DOES NOT
 PROVIDE INFORMATION ON THE EXISTING
 RTU OR DUCT SMOKE DETECTOR.PLEASE
 CLARIFY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-30 Cont ID  
Sent By pkrauss Date 2003-09-30 Time 13:36 Rev Time 0.40
Received By pkrauss Date 2003-09-30 Time 13:36 Sent To  
Notes
2003-09-30 00:00:00DENIED:
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER 2001 FBC(M) TABLE 403.3.
  
 PROVIDE INFORMATION ON EXISTING RTU.
 INDICATE DUCT SMOKE DETECTOR IF UNIT IS
 GREATER THAN 2,000 CFM.
  
 PLANS OTHERWISE ARE CODE COMPLIANT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-10-24 Cont ID  
Sent By kstevens Date 2003-10-24 Time 09:41 Rev Time 0.25
Received By kstevens Date 2003-10-24 Time 09:41 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-21 Cont ID  
Sent By kstevens Date 2003-10-21 Time 10:48 Rev Time 0.50
Received By kstevens Date 2003-10-21 Time 10:48 Sent To  
Notes
2003-10-21 00:00:00DENIED
 REFERENCE: FLORIDA STATUTES
  
 1) 471.025 ALL FINAL DRAWINGS, SPECIFIC-
 ATIONS, PLANS, REPORTS OR DOCUMENTS PRE-
 PARED OR ISSUED BY THE ENGINEER AND
 BEING FILED FOR PUBLIC RECORD AND ALL
 FINAL DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNERS REPRESENTATIVE SHALL BE SIGN-
 ED, DATED, AND SEALED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By pkrauss Date 2003-10-20 Time 13:28 Rev Time 1.25
Received By kstevens Date 2003-10-01 Time 15:32 Sent To  
Notes
2003-10-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1) SHT M1 SANITARY RISER DIAGRAM. THE
 SINK ADDED SHALL TIE IN DOWNSTREAM OF
 THE TOILET ROOM FIXTURES. SEC 909.1
 2) SHT 3.1 NEW SINK SHALL COMPLY WITH
 SECTION 11-4.24 AND ALL SUBSECTIONS.
 PROVIDE DETAILS. SEC 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]