Plan Review Details - Permit 03090181
Plan Review Stops For Permit 03090181
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-02 Cont ID  
Sent By nmccray Date 2003-10-02 Time 10:23 Rev Time 0.00
Received By nmccray Date 2003-10-02 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 06:55 Rev Time 0.00
Received By nmccray Date 2003-09-17 Time 10:36 Sent To  
Notes
2003-09-17 00:00:00PLEASE SEE MECHANICAL REVIEW NOTES
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-29 Cont ID  
Sent By csiegber Date 2003-09-29 Time 16:34 Rev Time 0.00
Received By csiegber Date 2003-09-29 Time 16:34 Sent To M
Notes
2003-09-29 00:00:00TO PK BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-04 Time 14:51 Rev Time 0.00
Received By csiegber Date 2003-09-04 Time 14:51 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-01 Cont ID  
Sent By pkrauss Date 2003-10-01 Time 06:55 Rev Time 0.40
Received By pkrauss Date 2003-10-01 Time 06:55 Sent To FIRE
Notes
2003-10-01 00:00:00PROVISO:
 1.PLAN SHEET 2 OF 2 (REVISED) :
 INDICATES 3M FASTWRAP OR SHAFT FOR
 CLEARANCE REDUCTION METHOD.PLEASE
 PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS ON THE JOBSITE AT THE TIME
 OF INSPECTION.WELDED DUCT TO BE
 INSPECTED PRIOR TO COVERING.
  
 2.NOTE REFERENCING TERMINATION OF
 EXHAUST INDICATES NFPA 96 506.2.14.3,
 THIS IS INCORRECT SHOULD READ NFPA 96
 4-8.2.1 (A) OR 2001 FBC(M) 506.2.14.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-16 Cont ID  
Sent By csiegber Date 2003-09-29 Time 16:34 Rev Time 0.45
Received By pkrauss Date 2003-09-16 Time 12:54 Sent To FIRE
Notes
2003-09-16 00:00:00DENIED:
 INSUFFICIENT INFORMATION FOR REVIEW.
 PLEASE CLARIFY THE FOLLOWING:
  
 1.TERMINATION OF EXHAUST IN RELATION
 TO PROPERTY LINE, ADJACENT & CONTINGUOUS
 BUILDINGS, AS WELL AS AIR INTAKES.
 2.ELEVATION OF ROOF WHERE EXHAUST AND
 SUPPLY FANS ARE LOCATED. (GREATER THAN
 16 FT REQUIRES A PERMANENT MEANS OF
 ACCESS)
 3.PLAN SHEET 2 OF 2 INDICATES WOOD
 CEILING AND ROOF JOIST.PROVIDE A
 MINIMUM OF 18" CLEARANCE OR INDICATE
 CLEARANCE REDUCTION METHOD.
  
 PLEASE NOTE FOR FUTURE HOOD & GREASE
 DUCT PERMITS THIS INFORMATION WILL BE
 REQUIRED AS TO ALLEVIATE PROBLEMS DURING
 CONSTRUCTION AND AT FINAL INSPECTIONS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.