Plan Review Details - Permit 03090181
| Plan Review Stops For Permit 03090181 |
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-10-02 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-10-02 |
Time |
10:22 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-09-17 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-10-01 |
Time |
06:55 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-09-17 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2003-09-17 00:00:00 | PLEASE SEE MECHANICAL REVIEW NOTES | | | | | | NATE MCCRAY, CAPTAIN | | | 805-6722 OR 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-09-29 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-29 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-29 |
Time |
16:34 |
Sent To |
M |
|
| Notes |
| 2003-09-29 00:00:00 | TO PK BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-09-04 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-04 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-04 |
Time |
14:51 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-10-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-10-01 |
Time |
06:55 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-10-01 |
Time |
06:55 |
Sent To |
FIRE |
|
| Notes |
| 2003-10-01 00:00:00 | PROVISO: | | | 1.PLAN SHEET 2 OF 2 (REVISED) : | | | INDICATES 3M FASTWRAP OR SHAFT FOR | | | CLEARANCE REDUCTION METHOD.PLEASE | | | PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS ON THE JOBSITE AT THE TIME | | | OF INSPECTION.WELDED DUCT TO BE | | | INSPECTED PRIOR TO COVERING. | | | | | | 2.NOTE REFERENCING TERMINATION OF | | | EXHAUST INDICATES NFPA 96 506.2.14.3, | | | THIS IS INCORRECT SHOULD READ NFPA 96 | | | 4-8.2.1 (A) OR 2001 FBC(M) 506.2.14.3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2003-09-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-29 |
Time |
16:34 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-09-16 |
Time |
12:54 |
Sent To |
FIRE |
|
| Notes |
| 2003-09-16 00:00:00 | DENIED: | | | INSUFFICIENT INFORMATION FOR REVIEW. | | | PLEASE CLARIFY THE FOLLOWING: | | | | | | 1.TERMINATION OF EXHAUST IN RELATION | | | TO PROPERTY LINE, ADJACENT & CONTINGUOUS | | | BUILDINGS, AS WELL AS AIR INTAKES. | | | 2.ELEVATION OF ROOF WHERE EXHAUST AND | | | SUPPLY FANS ARE LOCATED. (GREATER THAN | | | 16 FT REQUIRES A PERMANENT MEANS OF | | | ACCESS) | | | 3.PLAN SHEET 2 OF 2 INDICATES WOOD | | | CEILING AND ROOF JOIST.PROVIDE A | | | MINIMUM OF 18" CLEARANCE OR INDICATE | | | CLEARANCE REDUCTION METHOD. | | | | | | PLEASE NOTE FOR FUTURE HOOD & GREASE | | | DUCT PERMITS THIS INFORMATION WILL BE | | | REQUIRED AS TO ALLEVIATE PROBLEMS DURING | | | CONSTRUCTION AND AT FINAL INSPECTIONS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
|