| Plan Review Stops For Permit 03090174 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2003-09-15 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-09-15 |
Time |
15:56 |
Rev Time |
4.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-09-15 00:00:00 | | | | "PROVISO" | | | ----------- | | | | | | A STATE OF FLORIDA ACCESSABILITY WAIVER | | | IS REQUIRED FOR THE ELEVATED SEATING. | | | | | | | | | | | | LUIS MARTINEZ | | | 805-6710 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-09-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-11 |
Time |
09:46 |
Rev Time |
3.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-09-08 00:00:00 | | | | BUILDING COMMENTS | | | -------- -------- | | | | | | 1] | | | SUBMIT OCCUPANT LOAD CLARIFICATION, FBC | | | 1003.1 | | | | | | 2] | | | PROVIDE LIFE SAFTY EGRESS PLAN PER FBC | | | 1019.1 | | | | | | 3] | | | USE 'B' TYPE CORRIDOR SEPERATION WALL | | | AT WEST AND SOUTH AUDITORIUM WALLS. FBC | | | 704.2.4 | | | | | | 4] | | | CORRIDOR #1 AT RESTROOM AREA IS A DEAD | | | END, MAXIMUM CORRIDOR LENGTH IS 20'. FBC | | | 1004. | | | | | | 5] | | | STATE OF FLORIDA ACCESSABILITY WAIVER | | | IS REQUIRED FOR THE ELEVATED SEATING | | | AREA. | | | | | | | | | L.MARTINEZ 805-6710 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
N |
Date |
2003-09-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-16 |
Time |
10:15 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2003-09-12 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2003-09-12 00:00:00 | ************ NOTE *************** | | | | | | AS REQUESTED BY CONT IN ORDER FOR | | | BLDG PERMIT TO BE ISSUED. | | | SEPARATE PLANS WILL BE REQ'D FOR | | | ELECTRICAL WORK AND SEPARATE PERMIT | | | APPLICATION TO FOLLOW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-11 |
Time |
11:36 |
Rev Time |
0.75 |
| Received By |
dpalmer |
Date |
2003-09-11 |
Time |
11:36 |
Sent To |
|
|
| Notes |
| 2003-09-11 00:00:00 | ************* UNSAT ***************** | | | | | | PLEASE SEE THAT MOST NOTES FROM ORIG | | | REVIEW WERE NOT ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE FS'S 481 AND FAC | | | 61G1-16.004. PLEASE SEE ATTACHED COPY | | | OF FAC FOR INFORMATION MISSING ON TITLE | | | BLOCK. | | | | | | 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS | | | AND CORRELATE WITH PANEL SCHEDULE(S) | | | TO BE SUBMITTED. | | | | | | 3)NOTE: PLEASE SUBMIT ALL INFORMATION | | | AS REQUESTED ON NOTES, 2,3,4,5&6 FROM | | | FIRST REVIEW. | | | | | | 4)NOTE; PLEASE SEE 520/540 ETC FOR | | | MOTION PICT STUDIO'S, THEATERS AND | | | PROJECTOR RMS AND THE LIKE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION AND | | | INFORMATION AS REQUESTED UNDER FIRST | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] | | | | | | PLEASE ALSO SEE ATTACHED LETTER WITH | | | RESPECT TO DESIGN PROFESSIONALS. PER | | | FS 553.80(2)(B) | | | LETTER ATTACHED PER PLUMB PLAN REVIEW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-09-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-11 |
Time |
09:51 |
Rev Time |
1.00 |
| Received By |
btrobaug |
Date |
2003-09-04 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2003-09-05 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | PLEASE PROVIDE THE FOLLOWING | | | INFORMATION,MAKE NECESSARY CHANGES IN | | | PLANS FOR CODE COMPLIENCE AND RESUBMIT | | | FOR REVIEW. | | | | | | 1} THE ARCHITECTS SEAL AND TITLE BLOCK | | | MUST CONFORM TO 61G1-16.001 AND | | | 61G1-16.004 RESPECTIVELY. | | | | | | 2} PLEASE PROVIDE LOAD | | | CALCULATIONS,PANEL SCHEDULES AND | | | INDICATE THE SIZE OF THE EXISTING | | | SERVICE INTENDED TO SUPPLY THE POWER | | | FOR THE SCOPE OF WORK SHOWN. | | | | | | 3} PLEASE SHOW ALL CONTINUOUS LOADS @ | | | 125% PER 210.19(A) & 215.2. | | | | | | 4} SHOW ALL TRACK LIGHTING PER 210.12(B) | | | | | | 5} PLEASE SHOW EGRESS LIGHTING PER | | | NFPA-101,7.8. | | | | | | 6} INDICATE BRANCH CIRCUIT NUMBERS ON | | | DRAWINGS PER 210.4(D). | | | | | | NOTE: THE USE OF THIS OCCUPANCY MUST | | | COMPLY WITH 518 & 520,ALSO ARTICLE 540 | | | IF "TECH BOOTH" IS TO CONTAIN A | | | PROJECTOR | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-09-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-12 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-12 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2003-09-12 00:00:00 | 1) HANDRAILS ARE REQUIRED AT TECH BOOTH | | | STAIRS. THE OCCUPANT LOAD FOR THE | | | BUILDING WILL BE DETERMINED BY FIRE | | | RESCUE. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-09-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-04 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-04 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2003-09-04 00:00:00 | 1) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 2) PLEASE INDICATE TOTAL OCCUPANT | | | LOADS WHEN THE BUILDING IS OCCUPIED. | | | | | | 3) NO MENTION ON THE PLANS WITH | | | REGARDS TO THE EXISTING FIRE | | | SPRINKLER SYSTEM. PLEASE MAKE | | | REFERENCE ON THE PLANS THAT THE | | | BUILDING IS FIRE SPRINKLER PROTECTED. | | | | | | 4) ARE THERE ANY PLANNED WAITING SPACES | | | FOR THE ESTABLISHMENT. | | | | | | 5) ARE THE SEATS IN THE AUDITORIUM | | | FIXED OR NON-FIXED. | | | | | | 6) NO SMOKING SIGNS SHALL BE POSTED | | | WHERE SMOKING IS PROHIBITED. | | | | | | 7) NO OPEN FLAME OR PYROTECHNICS | | | ALLOWED WITHIN THE BUILDING. | | | | | | 8) THE TECH BOOTH IF FILM OR VIDEO | | | PROJECTORS OR SPOTLIGHTS USING LIGHT | | | SOURCES ARE PLANNED, IT SHALL COMPLY | | | WITH APPLICABLE CODE REQUIREMENTS. | | | | | | 9) THE TREADS NEAR THE TECH BOOTH | | | SHALL BE AT LEAST 13" WIDE SINCE THERE | | | ARE LESS THAN THREE RISERS WILL | | | BE PRESENT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-16 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-16 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-16 |
Time |
10:15 |
Sent To |
E |
|
| Notes |
| 2003-10-16 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-09-08 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-09-08 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2003-09-08 00:00:00 | NO MECH. WORK SHOWN ON PLAN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
N |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-11 |
Time |
16:36 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-09-11 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2003-09-11 00:00:00 | SEPARATE PLANS/APPLICATION REQUIRED FOR | | | PLUMBING |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-09-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-11 |
Time |
09:33 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-09-11 |
Time |
09:33 |
Sent To |
E |
|
| Notes |
| 2003-09-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | | | | A) FOLLOWING COMMENTS FROM FIRST REVIEW | | | WERE NOT ADDRESSED. COMMENTS NUMBERS | | | SHALL BE THE SAME AS FIRST REVIEW FOR | | | CLAIRTY. | | | 1) 61G1-16.003 THE PERSONAL SEAL, SIGNA- | | | TURE, AND DATE OF THE ARCHITECT SHALL | | | APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO | | | BE FILED FOR PUBLIC RECORD. (DATE NOT | | | SHOW. - SHALL BE ON EACH SHEET WITH SIG- | | | NATURE ON SEAL) | | | 2) 61G1-16.004(2) FIRM LICENSE NUMBER IS | | | REQUIRED ON TITLE BLOCK. | | | 4) SHEET A2 SINK IN DRESSING APPEARS TO | | | BE A LAV. SEE DETAIL AND #10 OF THE FIX- | | | TURE ACCESSORY SCHEDULE. A SERVICE SINK | | | IS REQUIRED FOR CLEANING FLOORS ECT. | | | TABLE 403.1 | | | 6) SUBMIT A SANITARY & A WATER RISER | | | DIAGRAM. SECTION 104.2.1 | | | NEW COMMENT: SEE ATTACHED SHEET CONCERN- | | | ING FLORIDA STATUTE 553.80(2(B) | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-09-04 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-09-04 |
Time |
18:11 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2003-09-04 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2003-09-04 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | | | | 1) 61G1-16.003 THE PERSONAL SEAL, SIGNA- | | | TURE, AND DATE OF THE ARCHITECT SHALL | | | APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO | | | BE FILED FOR PUBLIC RECORD. | | | 2) 61G1-16.004(2) TITLE BLOCK. FIRM | | | LICENSE NUMBER REQUIRED. | | | 3) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | | TURE FACILITIES PER TABLE 1003.1 (BLDG.) | | | AND TABLE 403.1 (PLUMB.). INDICATE NUMB- | | | ER OF SEATS PER TABLE 1003.1 FOOTNOTE 1. | | | SHOW SQUARE FOOTAGE FOR EACH OCCUPANCY. | | | LIBRARY, AUDITORIUM, STORAGE, ECT. | | | 4) PER TABLE 403.1 A DRINKING FOUNTAIN, | | | AND A SERVICE SINK ARE REQUIRED. | | | 5) SHT A1 HDCP RESTROOM 07, PER SECTION | | | 11-4.22.2 DOORS SHALL NOT SWING INTO THE | | | CLEAR FLOOR SPACE REQUIRED FOR ANY FIX- | | | TURE. | | | 6) SUBMIT A SANITARY & A WATER RISER | | | ISOMETRIC. SECTION 104.2.1 | | | 7) INDICATE IF THIS IS A CHANGE OF | | | OCCUPANCY. WAS THIS AN ASSEMBLY OCCUPAN- | | | CY OR BUSINESS OCCUPANCY? IF CHANGING | | | OCCUPANCY, PER SECTION 3401.2.2 THE | | | BUILDING, ELECTRICAL, GAS, MECHANICAL, | | | AND PLUMBING SYSTEMS SHALL BE MADE TO | | | CONFORM TO THE INTENT OF THE TECHNICAL | | | CODES AS REQUIRED BY THE BUILDING OFFIC- | | | IAL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|