Plan Review Details - Permit 03090174
Plan Review Stops For Permit 03090174
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-09-15 Cont ID  
Sent By lmartine Date 2003-09-15 Time 15:56 Rev Time 4.00
Received By lmartine Date   Time   Sent To  
Notes
2003-09-15 00:00:00 
 "PROVISO"
 -----------
  
 A STATE OF FLORIDA ACCESSABILITY WAIVER
 IS REQUIRED FOR THE ELEVATED SEATING.
  
  
  
 LUIS MARTINEZ
 805-6710

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-08 Cont ID  
Sent By kstevens Date 2003-09-11 Time 09:46 Rev Time 3.00
Received By lmartine Date   Time   Sent To  
Notes
2003-09-08 00:00:00 
 BUILDING COMMENTS
 -------- --------
  
 1]
 SUBMIT OCCUPANT LOAD CLARIFICATION, FBC
 1003.1
  
 2]
 PROVIDE LIFE SAFTY EGRESS PLAN PER FBC
 1019.1
  
 3]
 USE 'B' TYPE CORRIDOR SEPERATION WALL
 AT WEST AND SOUTH AUDITORIUM WALLS. FBC
 704.2.4
  
 4]
 CORRIDOR #1 AT RESTROOM AREA IS A DEAD
 END, MAXIMUM CORRIDOR LENGTH IS 20'. FBC
 1004.
  
 5]
 STATE OF FLORIDA ACCESSABILITY WAIVER
 IS REQUIRED FOR THE ELEVATED SEATING
 AREA.
  
  
 L.MARTINEZ 805-6710

Review Stop E ELECTRICAL
Rev No 3 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-10-16 Time 10:15 Rev Time 0.25
Received By dpalmer Date 2003-09-12 Time 08:30 Sent To  
Notes
2003-09-12 00:00:00************ NOTE ***************
  
 AS REQUESTED BY CONT IN ORDER FOR
 BLDG PERMIT TO BE ISSUED.
 SEPARATE PLANS WILL BE REQ'D FOR
 ELECTRICAL WORK AND SEPARATE PERMIT
 APPLICATION TO FOLLOW.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-09-11 Cont ID  
Sent By dpalmer Date 2003-09-11 Time 11:36 Rev Time 0.75
Received By dpalmer Date 2003-09-11 Time 11:36 Sent To  
Notes
2003-09-11 00:00:00************* UNSAT *****************
  
 PLEASE SEE THAT MOST NOTES FROM ORIG
 REVIEW WERE NOT ADDRESSED.
  
 1)NOTE: PLEASE SEE FS'S 481 AND FAC
 61G1-16.004. PLEASE SEE ATTACHED COPY
 OF FAC FOR INFORMATION MISSING ON TITLE
 BLOCK.
  
 2)NOTE: PLEASE SHOW CIRCUITING ON PLANS
 AND CORRELATE WITH PANEL SCHEDULE(S)
 TO BE SUBMITTED.
  
 3)NOTE: PLEASE SUBMIT ALL INFORMATION
 AS REQUESTED ON NOTES, 2,3,4,5&6 FROM
 FIRST REVIEW.
  
 4)NOTE; PLEASE SEE 520/540 ETC FOR
 MOTION PICT STUDIO'S, THEATERS AND
 PROJECTOR RMS AND THE LIKE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AND
 INFORMATION AS REQUESTED UNDER FIRST
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
 PLEASE ALSO SEE ATTACHED LETTER WITH
 RESPECT TO DESIGN PROFESSIONALS. PER
 FS 553.80(2)(B)
 LETTER ATTACHED PER PLUMB PLAN REVIEW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-05 Cont ID  
Sent By kstevens Date 2003-09-11 Time 09:51 Rev Time 1.00
Received By btrobaug Date 2003-09-04 Time 17:49 Sent To  
Notes
2003-09-05 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES IN
 PLANS FOR CODE COMPLIENCE AND RESUBMIT
 FOR REVIEW.
  
 1} THE ARCHITECTS SEAL AND TITLE BLOCK
 MUST CONFORM TO 61G1-16.001 AND
 61G1-16.004 RESPECTIVELY.
  
 2} PLEASE PROVIDE LOAD
 CALCULATIONS,PANEL SCHEDULES AND
 INDICATE THE SIZE OF THE EXISTING
 SERVICE INTENDED TO SUPPLY THE POWER
 FOR THE SCOPE OF WORK SHOWN.
  
 3} PLEASE SHOW ALL CONTINUOUS LOADS @
 125% PER 210.19(A) & 215.2.
  
 4} SHOW ALL TRACK LIGHTING PER 210.12(B)
  
 5} PLEASE SHOW EGRESS LIGHTING PER
 NFPA-101,7.8.
  
 6} INDICATE BRANCH CIRCUIT NUMBERS ON
 DRAWINGS PER 210.4(D).
  
 NOTE: THE USE OF THIS OCCUPANCY MUST
 COMPLY WITH 518 & 520,ALSO ARTICLE 540
 IF "TECH BOOTH" IS TO CONTAIN A
 PROJECTOR
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-09-12 Cont ID  
Sent By mcarsill Date 2003-09-12 Time 16:05 Rev Time 0.00
Received By mcarsill Date 2003-09-12 Time 16:05 Sent To  
Notes
2003-09-12 00:00:001) HANDRAILS ARE REQUIRED AT TECH BOOTH
 STAIRS. THE OCCUPANT LOAD FOR THE
 BUILDING WILL BE DETERMINED BY FIRE
 RESCUE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 16:17 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 16:17 Sent To  
Notes
2003-09-04 00:00:001) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 2) PLEASE INDICATE TOTAL OCCUPANT
 LOADS WHEN THE BUILDING IS OCCUPIED.
  
 3) NO MENTION ON THE PLANS WITH
 REGARDS TO THE EXISTING FIRE
 SPRINKLER SYSTEM. PLEASE MAKE
 REFERENCE ON THE PLANS THAT THE
 BUILDING IS FIRE SPRINKLER PROTECTED.
  
 4) ARE THERE ANY PLANNED WAITING SPACES
 FOR THE ESTABLISHMENT.
  
 5) ARE THE SEATS IN THE AUDITORIUM
 FIXED OR NON-FIXED.
  
 6) NO SMOKING SIGNS SHALL BE POSTED
 WHERE SMOKING IS PROHIBITED.
  
 7) NO OPEN FLAME OR PYROTECHNICS
 ALLOWED WITHIN THE BUILDING.
  
 8) THE TECH BOOTH IF FILM OR VIDEO
 PROJECTORS OR SPOTLIGHTS USING LIGHT
 SOURCES ARE PLANNED, IT SHALL COMPLY
 WITH APPLICABLE CODE REQUIREMENTS.
  
 9) THE TREADS NEAR THE TECH BOOTH
 SHALL BE AT LEAST 13" WIDE SINCE THERE
 ARE LESS THAN THREE RISERS WILL
 BE PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-16 Cont ID  
Sent By csiegber Date 2003-10-16 Time 10:15 Rev Time 0.00
Received By csiegber Date 2003-10-16 Time 10:15 Sent To E
Notes
2003-10-16 00:00:00TO DP DESK/REV

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-09-08 Cont ID  
Sent By lmartine Date 2003-09-08 Time 17:33 Rev Time 0.00
Received By lmartine Date   Time   Sent To  
Notes
2003-09-08 00:00:00NO MECH. WORK SHOWN ON PLAN

Review Stop P PLUMBING
Rev No 3 Status N Date 2003-09-11 Cont ID  
Sent By kstevens Date 2003-09-11 Time 16:36 Rev Time 0.25
Received By kstevens Date 2003-09-11 Time 16:36 Sent To  
Notes
2003-09-11 00:00:00SEPARATE PLANS/APPLICATION REQUIRED FOR
 PLUMBING

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-09-11 Cont ID  
Sent By kstevens Date 2003-09-11 Time 09:33 Rev Time 1.00
Received By kstevens Date 2003-09-11 Time 09:33 Sent To E
Notes
2003-09-11 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 A) FOLLOWING COMMENTS FROM FIRST REVIEW
 WERE NOT ADDRESSED. COMMENTS NUMBERS
 SHALL BE THE SAME AS FIRST REVIEW FOR
 CLAIRTY.
 1) 61G1-16.003 THE PERSONAL SEAL, SIGNA-
 TURE, AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO
 BE FILED FOR PUBLIC RECORD. (DATE NOT
 SHOW. - SHALL BE ON EACH SHEET WITH SIG-
 NATURE ON SEAL)
 2) 61G1-16.004(2) FIRM LICENSE NUMBER IS
 REQUIRED ON TITLE BLOCK.
 4) SHEET A2 SINK IN DRESSING APPEARS TO
 BE A LAV. SEE DETAIL AND #10 OF THE FIX-
 TURE ACCESSORY SCHEDULE. A SERVICE SINK
 IS REQUIRED FOR CLEANING FLOORS ECT.
 TABLE 403.1
 6) SUBMIT A SANITARY & A WATER RISER
 DIAGRAM. SECTION 104.2.1
 NEW COMMENT: SEE ATTACHED SHEET CONCERN-
 ING FLORIDA STATUTE 553.80(2(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-04 Cont ID  
Sent By kstevens Date 2003-09-04 Time 18:11 Rev Time 1.25
Received By kstevens Date 2003-09-04 Time 18:11 Sent To  
Notes
2003-09-04 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
  
 1) 61G1-16.003 THE PERSONAL SEAL, SIGNA-
 TURE, AND DATE OF THE ARCHITECT SHALL
 APPEAR ON ALL ARCHITECTURAL DOCUMENTS TO
 BE FILED FOR PUBLIC RECORD.
 2) 61G1-16.004(2) TITLE BLOCK. FIRM
 LICENSE NUMBER REQUIRED.
 3) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURE FACILITIES PER TABLE 1003.1 (BLDG.)
 AND TABLE 403.1 (PLUMB.). INDICATE NUMB-
 ER OF SEATS PER TABLE 1003.1 FOOTNOTE 1.
 SHOW SQUARE FOOTAGE FOR EACH OCCUPANCY.
 LIBRARY, AUDITORIUM, STORAGE, ECT.
 4) PER TABLE 403.1 A DRINKING FOUNTAIN,
 AND A SERVICE SINK ARE REQUIRED.
 5) SHT A1 HDCP RESTROOM 07, PER SECTION
 11-4.22.2 DOORS SHALL NOT SWING INTO THE
 CLEAR FLOOR SPACE REQUIRED FOR ANY FIX-
 TURE.
 6) SUBMIT A SANITARY & A WATER RISER
 ISOMETRIC. SECTION 104.2.1
 7) INDICATE IF THIS IS A CHANGE OF
 OCCUPANCY. WAS THIS AN ASSEMBLY OCCUPAN-
 CY OR BUSINESS OCCUPANCY? IF CHANGING
 OCCUPANCY, PER SECTION 3401.2.2 THE
 BUILDING, ELECTRICAL, GAS, MECHANICAL,
 AND PLUMBING SYSTEMS SHALL BE MADE TO
 CONFORM TO THE INTENT OF THE TECHNICAL
 CODES AS REQUIRED BY THE BUILDING OFFIC-
 IAL.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]