| Plan Review Stops For Permit 03090168 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-12-01 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-12-01 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-12-01 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2004-12-01 00:00:00 | REVISION SUBMITTED 11/23/04 FOR SHEETS | | | A-5, A-0 AND TITLE/NOTES SHEET |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2004-11-19 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-11-19 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-11-19 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2004-11-19 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | REVISION SUBMITTED 10/29/04 FOR SHEETS | | | A-3, A-4, A-5, A-6 AND E-1 | | | | | | ***NOTE*** | | | FOR THE SECOND TIME, NONE OF THE | | | REDLINED NOTES HAVE BEEN INCORPORATED, | | | BY THE ARCHITECT, ON THE REVISED SHEETS. | | | THESE NOTES HAVE AREADY BEEN REDLINED | | | TWICE BY THIS OFFICE. THE PROVISO SENT | | | OUT WITH THE PERMIT APPROVED PLANS | | | STATED "ANY REVISIONS TO THIS PERMIT, | | | SUBMITTED WITHOUT INCORPORATING THE | | | REDLINED NOTES WILL BE DENIED." | | | | | | 1) THE REVISION SHALL INCLUDE THE NOTES/ | | | CHANGES THAT WERE REDLINED ON SHEETS | | | A-1, A-3 AND THE TITLE SHEET.ALSO THE | | | REVISED SHEETS STILL DO NOT INCLUDE THE | | | M. SIMON & ASSOCIATES STREET ADDRESS | | | (SEE REDLINED PLANS), THE ARCHITECT'S | | | PRINTED LICENSE NUMBER OR THE | | | ARCHITECT'S PRINTED NAME (SEE FLORIDA | | | ADMINISTRATIVE CODE 61G1-16.003 & 004). | | | SUBMIT REVISED SHEETS. | | | | | | 2) FBC 803.3SHEET A-5, WALL SECTIONS | | | 10 AND 12.REVISION FROM PAINTED | | | DRYWALL TO MDF PANELS.THE MDF PANELS | | | SHALL HAVE A FLAMESPREAD RATING OF LESS | | | THAN 200.ADD A NOTE TO THE PLANS. | | | | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2004-07-13 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2004-07-13 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2004-07-13 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2004-07-13 00:00:00 | NONE OF THE REDLINED NOTES WERE | | | INCORPORATED ON THE RE-SUBMITTED SHEETS | | | BY THE ARCHITECT.THEY HAVE BEEN | | | REDLINED AGAIN.ANY REVISIONS TO THIS | | | PERMIT, SUBMITTED WITHOUT INCORPORATING | | | THE REDLINED NOTES WILL BE DENIED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-12-08 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-12-08 |
Time |
17:13 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-12-08 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2003-12-08 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS | | | ARE NUMBERED AS PER THE BUILDING PLAN | | | REVIEW OF 9/12/03: | | | | | | 2) FL. ADMIN CODE 61G1-16.004THIS | | | COMMENT HAS NOT BEEN PROPERLY ADDRESSED. | | | THE TITLE BLOCKS ON THE ARCHITECTURAL | | | PLANS STILL DO NOT INCLUDE THE STREET | | | ADDRESS OF THE ARCHITECTURAL BUSINESS. | | | ALSO: THE SIGNATURES ON THE REVISED | | | SHEETS ARE NOT DATED.THESE ITEMS ARE | | | REQUIRED ON ALL DOCUMENTS PREPARED BY AN | | | ARCHITECT AND BEING FILED FOR PUBLIC | | | RECORD, PER 481.221 FS. | | | | | | 7) FBC 704.3.1SHEET A-3.BOTH TENANT | | | SEPARATION WALLS WERE ORIGINALLY | | | SPECIFIED AS 1-HOUR FIRE-RATED U.L #465. | | | THE REVISED PLAN NOW SHOWS ONLY THE | | | RIGHT SIDE TENANT SEPARATION WALL AS | | | TYPE 1 (REF. WALL LEGEND), WHICH IS | | | 1-HOUR RATED.AMEND THE PLAN TO STATE | | | THE REQUIRED 1-HOUR FIRE-RATING FOR THE | | | LEFT SIDE TENANT SEPARATION WALL ALSO. | | | | | | 8) COVER SHEET, SHEET A-2 AND SHEET A-5. | | | ITEMS THAT WERE REDLINED AS A RESULT OF | | | THE PREVIOUS PLAN REVIEW HAVE NOT BEEN | | | CORRECTED ON THE REVISED SET.THESE | | | ITEMS HAVE BEEN REDLINED AGAIN ON THE | | | REVISED PLANS. | | | | | | 9) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-09-12 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2003-09-12 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-09-12 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2003-09-12 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6716 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) THE NOTICE OF COMMENCEMENT SHALL BE | | | RECORDED AT PALM BEACH COUNTY COURTHOUSE | | | AND A COPY SUBMITTED TO THIS OFFICE | | | BEFORE A PERMIT CAN BE ISSUED.BLANK | | | FORMS ARE AVAILABLE FROM THIS OFFICE. | | | | | | 2) FL. ADMIN CODE 61G1-16.004THE TITLE | | | BLOCKS ON THE ARCHITECTURAL SHEETS DO | | | NOT INCLUDE THE STREET ADDRESS OF THE | | | ARCHITECTURAL BUSINESS.ALSO, SHEETS | | | A-1 AND A-4 DO NOT SHOW ANY PROJECT | | | ADDRESS AND NONE OF THE SHEETS STATE THE | | | STREET ADDRESS AS '1801 PALM BEACH LAKES | | | #712' OR STATE THE LOCATION AS 'WEST | | | PALM BEACH' (SHEETS SAY "WPM").AMEND | | | THE TITLE BLOCKS TO SHOW THE MINIMUM | | | INFORMATION REQUIRED BY THE FLORIDA | | | ADMINISTRATIVE CODE. | | | | | | 3) FBC 11-4.15DRINKING FOUNTAIN. | | | REVISE THE PLANS TO SHOW THE REQUIRED | | | ACCESSIBILITY HEIGHTS AND CLEARANCES | | | (REF. FIG 27) | | | | | | 4) FBC 11-4.16.4 AND 11-4.26.3 SHEET A-2 | | | WASHROOM ACCCESSORY LEGEND NOTE W7 DOES | | | NOT COMPLY WITH THE REQIREMENTS SHOWN IN | | | CH 11, FIG. 29 AND DOES NOT DEMONSTRATE | | | COMPLIANCE WITH THE REQUIREMENT FOR GRAB | | | BARS TO RESIST A LOAD OF 250 LBF APPLIED | | | IN ANY DIRECTION.AMEND THE NOTE. | | | | | | 5) FBC 803.5.2FABRIC SWAG, SHEET A-3, | | | PLAN AND SHEET A-6, ELEVATION 3. ADDRESS | | | COMMENT #3 OF FIRE PLAN REVIEW DATED | | | 9/10/03, REQUIRING FIRESPREAD DATA. | | | | | | 6) IF NEW PLAN SHEETS ARE REQUIRED, IN | | | ORDER TO ADDRESS THE ABOVE COMMENTS, THE | | | OLD SHEETS SHALL BE REMOVED AND THE NEW | | | SHEETS INSERTED.ONE COPY OF EACH OLD | | | SHEET SHALL BE INCLUDED WITH THE | | | RESUBMITTAL FOR COMPARISON OF REVISIONS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | TELEPHONE: (561) 805 6716ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2004-11-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-11-04 |
Time |
13:42 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2004-11-04 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-07-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-07-07 |
Time |
11:20 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-07-07 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2004-07-07 00:00:00 | SCOPE OF WORK HAS DECREASED TO ONLY | | | CASH REGISTER AREAS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2004-06-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-06-17 |
Time |
16:33 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-06-17 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2004-06-17 00:00:00 | *********** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE RESUB SHEET NOW | | | MENTIONS REDESIGN, HOWEVER NEW PLANS | | | DO NOT SEEM TO INCLUDE ANY INFORMATION. | | | PLEASE SEE OLD STAMPED ELECTRICAL PLANS | | | ARE SUBMITTED BACK ALSO. IF SCOPE OF | | | WORK ON THESE PLANS IS NO LONGER GOING | | | TO BE DONE, PLEASE VOID OUT SHEETS. | | | PLEASE SUBMIT COMPLETED SETS FOR ONES | | | THAT ARE TO BE REVIEWED. | | | NEW PLAN ONLY APPEARS TO SHOW WORK FOR | | | EIGHT NEW RECEPTS ONLY? | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2003-11-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-11-06 |
Time |
07:02 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-11-06 |
Time |
07:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-09-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-09-15 |
Time |
18:02 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-09-15 |
Time |
18:02 |
Sent To |
|
|
| Notes |
| 2003-09-15 00:00:00 | ************* UNSAT ************** | | | | | | 1)NOTE: PLANS REFERENCE THE 2001 FBC FOR | | | ELECTRICAL? PLEASE NOTE ELECTRICAL FALLS | | | UNDER THE NEC. WE ARE CURRENTLY UNDER | | | THE 2002 NEC W/ LOCAL AMENDMENTS. | | | | | | 2)NOTE: PLEASE SEE THAT THERE ARE OTHER | | | LOCATIONS ON PLANS THAT REFERENCE OTHER | | | JURISDICTIONS.? PLEASE SEE THAT PROPOSED | | | WORK IS TO COMMENCE IN THE CITY OF WEST | | | PALM BEACH. | | | | | | 3)NOTE: PLEASE SEE FAC 61G15-23.002 AND | | | FAC 61G1-16.004 FOR COMPLETE INFORMATION | | | REQ'D ON PLANS AND TITLE BLOCK(S). | | | PLEASE INCLUDE COMPLETE ADDRESS OF JOB. | | | PLEASE ALSO INCLUDE LICENSE #'S, CERTIF- | | | -ICATE OF AUTHORIZATION #`S ETC. | | | | | | 4)NOTE: PLEASE SEE THAT ELECTRICAL | | | SHEETS REFERENCE THE 99 NEC AND NOTES | | | REFERENCE CODES FROM 96 NEC.? | | | PLEASE ADJUST AND CORRELATE. | | | | | | PLEASE SEE COMMENTS FROM ALL OTHER | | | REVIEWERS, AS THEY MAY HAVE COMMENTS | | | THAT MAY HAVE AN AFFECT ON ELECTRICAL | | | PLANS. | | | | | | PLEASE NOTE: UPON CORRECTIONS MADE TO | | | EXSITING PLANS, PLEASE REMOVE OLD/VOIDED | | | SHEETS AND REPLACE WITH NEW ONES. | | | PLEASE SUBMIT ONLY ONE SET OF OLD SHEETS | | | FOR ANY REVIEWS OR COMPARISIONS THAT | | | MAY BE NEEDED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-11-23 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-11-23 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2004-11-23 00:00:00 | REVISION DATED 10-22-04 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2004-07-08 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2004-07-08 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2004-07-08 |
Time |
15:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2003-11-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-11-24 |
Time |
16:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-11-24 |
Time |
16:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2003-09-10 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2003-09-10 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2003-09-10 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2003-09-10 00:00:00 | 1) FIRE PROTECTION NOTE ON TITLE | | | PAGE IS INCORRECT. SHOULD READ 2001 | | | FLORIDA FIRE PREVENTION CODE. | | | | | | 2) DEMOLITION, RENOVATION, AND | | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | | | 3) PLEASE PROVIDE FLAMESPREAD | | | INFORMATION FOR FABRIC SWAG. GENERAL | | | NOTES REQUIRES THAT ALL WOOD AND | | | FABRICS TO BE FIRE TREATED. PLEASE | | | PROVIDE DOCUMENTATION. | | | | | | 4) LIFE SAFETY NOTES # 10 MENTIONS | | | "WITH CITY OF SUNRISE". JOB IS | | | NOT LOCATED IN SUNRISE, FLORIDA. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-11-23 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2004-11-23 |
Time |
18:43 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2004-11-23 |
Time |
18:43 |
Sent To |
B |
|
| Notes |
| 2004-11-23 00:00:00 | SENT TO "RB" DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2004-11-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-11-01 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-11-01 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2004-11-01 00:00:00 | TO COMM BD#8 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-06-11 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-06-11 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-06-11 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2004-06-11 00:00:00 | TO COMM BD#48 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-11-05 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-05 |
Time |
15:39 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-05 |
Time |
15:39 |
Sent To |
|
|
| Notes |
| 2003-11-05 00:00:00 | TO COMM BD#15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-04 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2003-09-04 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2003-09-04 00:00:00 | ON COMM BD #29 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-12-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-02 |
Time |
07:01 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2003-12-02 |
Time |
06:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2003-09-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-09-29 |
Time |
07:28 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-09-29 |
Time |
07:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-12-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-06 |
Time |
10:39 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-12-06 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2003-12-06 00:00:00 | PASSED/PROVISO - THERMAL EXPANSION CON- | | | TROL REQUIRED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2003-10-02 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-02 |
Time |
14:13 |
Rev Time |
1.00 |
| Received By |
kstevens |
Date |
2003-10-02 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2003-10-02 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 11 | | | FBC-2001 CHAPTER 1 | | | FLORIDA ADMIN CODE | | | | | | 1) SUBMIT DETAIL FOR DRINKING FOUNTAIN. | | | SHOW COMPLIANCE WITH 11-4.15 AND ALL | | | SUBSECTIONS. ALSO PROVISIONS SHALL BE | | | MADE FOR THOSE WHO HAVE TROUBLE BENDING | | | OR STOOPING PER SEC 11-4.1.3(10)(A). | | | 2) SHT P2 WATER HEATER DETAIL. THERMAL | | | EXPANSION PROTECTION REQUIRED PER SEC | | | 607.3.2 | | | 3) SHT P2 WATER RISER DIAGRAM. AIR | | | CHAMBERS ARE NOT APPROVED. PLEASE DELETE | | | AT TOP OF D.F. DROP. IF WATER HAMMER IS | | | USED IS SHALL BE LOCATED NEAR THE FIX- | | | TURE IN AN "EFFECTIVE RANGE" NOT IN | | | CEILING. PDI-WH 201/MANUF. INSTALL. IN- | | | STRUCTIONS. | | | 4) SEE ATTACHED SHEET CONCERNING DESIGN | | | PROFESSIONALS. TITLE BLOCK, CERTIFICAT- | | | ION OF AUTHROIZATION ECT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|