Plan Review Details - Permit 03090168
Plan Review Stops For Permit 03090168
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2004-12-01 Cont ID  
Sent By rbrown Date 2004-12-01 Time 16:51 Rev Time 0.00
Received By rbrown Date 2004-12-01 Time 16:51 Sent To  
Notes
2004-12-01 00:00:00REVISION SUBMITTED 11/23/04 FOR SHEETS
 A-5, A-0 AND TITLE/NOTES SHEET

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-11-19 Cont ID  
Sent By rbrown Date 2004-11-19 Time 09:26 Rev Time 0.00
Received By rbrown Date 2004-11-19 Time 09:25 Sent To  
Notes
2004-11-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 REVISION SUBMITTED 10/29/04 FOR SHEETS
 A-3, A-4, A-5, A-6 AND E-1
  
 ***NOTE***
 FOR THE SECOND TIME, NONE OF THE
 REDLINED NOTES HAVE BEEN INCORPORATED,
 BY THE ARCHITECT, ON THE REVISED SHEETS.
 THESE NOTES HAVE AREADY BEEN REDLINED
 TWICE BY THIS OFFICE. THE PROVISO SENT
 OUT WITH THE PERMIT APPROVED PLANS
 STATED "ANY REVISIONS TO THIS PERMIT,
 SUBMITTED WITHOUT INCORPORATING THE
 REDLINED NOTES WILL BE DENIED."
  
 1) THE REVISION SHALL INCLUDE THE NOTES/
 CHANGES THAT WERE REDLINED ON SHEETS
 A-1, A-3 AND THE TITLE SHEET.ALSO THE
 REVISED SHEETS STILL DO NOT INCLUDE THE
 M. SIMON & ASSOCIATES STREET ADDRESS
 (SEE REDLINED PLANS), THE ARCHITECT'S
 PRINTED LICENSE NUMBER OR THE
 ARCHITECT'S PRINTED NAME (SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.003 & 004).
 SUBMIT REVISED SHEETS.
  
 2) FBC 803.3SHEET A-5, WALL SECTIONS
 10 AND 12.REVISION FROM PAINTED
 DRYWALL TO MDF PANELS.THE MDF PANELS
 SHALL HAVE A FLAMESPREAD RATING OF LESS
 THAN 200.ADD A NOTE TO THE PLANS.
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2004-07-13 Cont ID  
Sent By rbrown Date 2004-07-13 Time 12:09 Rev Time 0.00
Received By rbrown Date 2004-07-13 Time 12:09 Sent To  
Notes
2004-07-13 00:00:00NONE OF THE REDLINED NOTES WERE
 INCORPORATED ON THE RE-SUBMITTED SHEETS
 BY THE ARCHITECT.THEY HAVE BEEN
 REDLINED AGAIN.ANY REVISIONS TO THIS
 PERMIT, SUBMITTED WITHOUT INCORPORATING
 THE REDLINED NOTES WILL BE DENIED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-12-08 Cont ID  
Sent By rbrown Date 2003-12-08 Time 17:13 Rev Time 0.00
Received By rbrown Date 2003-12-08 Time 17:13 Sent To  
Notes
2003-12-08 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 9/12/03:
  
 2) FL. ADMIN CODE 61G1-16.004THIS
 COMMENT HAS NOT BEEN PROPERLY ADDRESSED.
 THE TITLE BLOCKS ON THE ARCHITECTURAL
 PLANS STILL DO NOT INCLUDE THE STREET
 ADDRESS OF THE ARCHITECTURAL BUSINESS.
 ALSO: THE SIGNATURES ON THE REVISED
 SHEETS ARE NOT DATED.THESE ITEMS ARE
 REQUIRED ON ALL DOCUMENTS PREPARED BY AN
 ARCHITECT AND BEING FILED FOR PUBLIC
 RECORD, PER 481.221 FS.
  
 7) FBC 704.3.1SHEET A-3.BOTH TENANT
 SEPARATION WALLS WERE ORIGINALLY
 SPECIFIED AS 1-HOUR FIRE-RATED U.L #465.
 THE REVISED PLAN NOW SHOWS ONLY THE
 RIGHT SIDE TENANT SEPARATION WALL AS
 TYPE 1 (REF. WALL LEGEND), WHICH IS
 1-HOUR RATED.AMEND THE PLAN TO STATE
 THE REQUIRED 1-HOUR FIRE-RATING FOR THE
 LEFT SIDE TENANT SEPARATION WALL ALSO.
  
 8) COVER SHEET, SHEET A-2 AND SHEET A-5.
 ITEMS THAT WERE REDLINED AS A RESULT OF
 THE PREVIOUS PLAN REVIEW HAVE NOT BEEN
 CORRECTED ON THE REVISED SET.THESE
 ITEMS HAVE BEEN REDLINED AGAIN ON THE
 REVISED PLANS.
  
 9) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-12 Cont ID  
Sent By rbrown Date 2003-09-12 Time 13:29 Rev Time 0.00
Received By rbrown Date 2003-09-12 Time 13:29 Sent To  
Notes
2003-09-12 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE NOTICE OF COMMENCEMENT SHALL BE
 RECORDED AT PALM BEACH COUNTY COURTHOUSE
 AND A COPY SUBMITTED TO THIS OFFICE
 BEFORE A PERMIT CAN BE ISSUED.BLANK
 FORMS ARE AVAILABLE FROM THIS OFFICE.
  
 2) FL. ADMIN CODE 61G1-16.004THE TITLE
 BLOCKS ON THE ARCHITECTURAL SHEETS DO
 NOT INCLUDE THE STREET ADDRESS OF THE
 ARCHITECTURAL BUSINESS.ALSO, SHEETS
 A-1 AND A-4 DO NOT SHOW ANY PROJECT
 ADDRESS AND NONE OF THE SHEETS STATE THE
 STREET ADDRESS AS '1801 PALM BEACH LAKES
 #712' OR STATE THE LOCATION AS 'WEST
 PALM BEACH' (SHEETS SAY "WPM").AMEND
 THE TITLE BLOCKS TO SHOW THE MINIMUM
 INFORMATION REQUIRED BY THE FLORIDA
 ADMINISTRATIVE CODE.
  
 3) FBC 11-4.15DRINKING FOUNTAIN.
 REVISE THE PLANS TO SHOW THE REQUIRED
 ACCESSIBILITY HEIGHTS AND CLEARANCES
 (REF. FIG 27)
  
 4) FBC 11-4.16.4 AND 11-4.26.3 SHEET A-2
 WASHROOM ACCCESSORY LEGEND NOTE W7 DOES
 NOT COMPLY WITH THE REQIREMENTS SHOWN IN
 CH 11, FIG. 29 AND DOES NOT DEMONSTRATE
 COMPLIANCE WITH THE REQUIREMENT FOR GRAB
 BARS TO RESIST A LOAD OF 250 LBF APPLIED
 IN ANY DIRECTION.AMEND THE NOTE.
  
 5) FBC 803.5.2FABRIC SWAG, SHEET A-3,
 PLAN AND SHEET A-6, ELEVATION 3. ADDRESS
 COMMENT #3 OF FIRE PLAN REVIEW DATED
 9/10/03, REQUIRING FIRESPREAD DATA.
  
 6) IF NEW PLAN SHEETS ARE REQUIRED, IN
 ORDER TO ADDRESS THE ABOVE COMMENTS, THE
 OLD SHEETS SHALL BE REMOVED AND THE NEW
 SHEETS INSERTED.ONE COPY OF EACH OLD
 SHEET SHALL BE INCLUDED WITH THE
 RESUBMITTAL FOR COMPARISON OF REVISIONS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2004-11-04 Cont ID  
Sent By dpalmer Date 2004-11-04 Time 13:42 Rev Time 0.33
Received By dpalmer Date 2004-11-04 Time 13:25 Sent To  
Notes
2004-11-04 00:00:00REV.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-07-07 Cont ID  
Sent By dpalmer Date 2004-07-07 Time 11:20 Rev Time 0.50
Received By dpalmer Date 2004-07-07 Time 11:20 Sent To  
Notes
2004-07-07 00:00:00SCOPE OF WORK HAS DECREASED TO ONLY
 CASH REGISTER AREAS.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2004-06-17 Cont ID  
Sent By dpalmer Date 2004-06-17 Time 16:33 Rev Time 0.50
Received By dpalmer Date 2004-06-17 Time 16:33 Sent To  
Notes
2004-06-17 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SEE RESUB SHEET NOW
 MENTIONS REDESIGN, HOWEVER NEW PLANS
 DO NOT SEEM TO INCLUDE ANY INFORMATION.
 PLEASE SEE OLD STAMPED ELECTRICAL PLANS
 ARE SUBMITTED BACK ALSO. IF SCOPE OF
 WORK ON THESE PLANS IS NO LONGER GOING
 TO BE DONE, PLEASE VOID OUT SHEETS.
 PLEASE SUBMIT COMPLETED SETS FOR ONES
 THAT ARE TO BE REVIEWED.
 NEW PLAN ONLY APPEARS TO SHOW WORK FOR
 EIGHT NEW RECEPTS ONLY?
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-06 Cont ID  
Sent By dpalmer Date 2003-11-06 Time 07:02 Rev Time 0.33
Received By dpalmer Date 2003-11-06 Time 07:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-15 Cont ID  
Sent By dpalmer Date 2003-09-15 Time 18:02 Rev Time 0.50
Received By dpalmer Date 2003-09-15 Time 18:02 Sent To  
Notes
2003-09-15 00:00:00************* UNSAT **************
  
 1)NOTE: PLANS REFERENCE THE 2001 FBC FOR
 ELECTRICAL? PLEASE NOTE ELECTRICAL FALLS
 UNDER THE NEC. WE ARE CURRENTLY UNDER
 THE 2002 NEC W/ LOCAL AMENDMENTS.
  
 2)NOTE: PLEASE SEE THAT THERE ARE OTHER
 LOCATIONS ON PLANS THAT REFERENCE OTHER
 JURISDICTIONS.? PLEASE SEE THAT PROPOSED
 WORK IS TO COMMENCE IN THE CITY OF WEST
 PALM BEACH.
  
 3)NOTE: PLEASE SEE FAC 61G15-23.002 AND
 FAC 61G1-16.004 FOR COMPLETE INFORMATION
 REQ'D ON PLANS AND TITLE BLOCK(S).
 PLEASE INCLUDE COMPLETE ADDRESS OF JOB.
 PLEASE ALSO INCLUDE LICENSE #'S, CERTIF-
 -ICATE OF AUTHORIZATION #`S ETC.
  
 4)NOTE: PLEASE SEE THAT ELECTRICAL
 SHEETS REFERENCE THE 99 NEC AND NOTES
 REFERENCE CODES FROM 96 NEC.?
 PLEASE ADJUST AND CORRELATE.
  
 PLEASE SEE COMMENTS FROM ALL OTHER
 REVIEWERS, AS THEY MAY HAVE COMMENTS
 THAT MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE NOTE: UPON CORRECTIONS MADE TO
 EXSITING PLANS, PLEASE REMOVE OLD/VOIDED
 SHEETS AND REPLACE WITH NEW ONES.
 PLEASE SUBMIT ONLY ONE SET OF OLD SHEETS
 FOR ANY REVIEWS OR COMPARISIONS THAT
 MAY BE NEEDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2004-11-23 Cont ID  
Sent By nmccray Date 2004-11-23 Time 11:25 Rev Time 0.00
Received By nmccray Date 2004-11-23 Time 11:25 Sent To  
Notes
2004-11-23 00:00:00REVISION DATED 10-22-04

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2004-07-08 Cont ID  
Sent By nmccray Date 2004-07-08 Time 15:33 Rev Time 0.00
Received By nmccray Date 2004-07-08 Time 15:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-24 Cont ID  
Sent By mcarsill Date 2003-11-24 Time 16:14 Rev Time 0.00
Received By mcarsill Date 2003-11-24 Time 16:14 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By mcarsill Date 2003-09-10 Time 15:46 Rev Time 0.00
Received By mcarsill Date 2003-09-10 Time 15:46 Sent To  
Notes
2003-09-10 00:00:001) FIRE PROTECTION NOTE ON TITLE
 PAGE IS INCORRECT. SHOULD READ 2001
 FLORIDA FIRE PREVENTION CODE.
  
 2) DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 3) PLEASE PROVIDE FLAMESPREAD
 INFORMATION FOR FABRIC SWAG. GENERAL
 NOTES REQUIRES THAT ALL WOOD AND
 FABRICS TO BE FIRE TREATED. PLEASE
 PROVIDE DOCUMENTATION.
  
 4) LIFE SAFETY NOTES # 10 MENTIONS
 "WITH CITY OF SUNRISE". JOB IS
 NOT LOCATED IN SUNRISE, FLORIDA.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-11-23 Cont ID  
Sent By mjacobs Date 2004-11-23 Time 18:43 Rev Time 0.00
Received By mjacobs Date 2004-11-23 Time 18:43 Sent To B
Notes
2004-11-23 00:00:00SENT TO "RB" DESK.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-11-01 Cont ID  
Sent By csiegber Date 2004-11-01 Time 11:46 Rev Time 0.00
Received By csiegber Date 2004-11-01 Time 11:45 Sent To  
Notes
2004-11-01 00:00:00TO COMM BD#8

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-06-11 Cont ID  
Sent By csiegber Date 2004-06-11 Time 16:02 Rev Time 0.00
Received By csiegber Date 2004-06-11 Time 16:02 Sent To  
Notes
2004-06-11 00:00:00TO COMM BD#48

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-11-05 Cont ID  
Sent By csiegber Date 2003-11-05 Time 15:39 Rev Time 0.00
Received By csiegber Date 2003-11-05 Time 15:39 Sent To  
Notes
2003-11-05 00:00:00TO COMM BD#15

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-02 Cont ID  
Sent By csiegber Date 2003-09-04 Time 14:18 Rev Time 0.00
Received By rbrown Date 2003-09-04 Time 14:18 Sent To  
Notes
2003-09-04 00:00:00ON COMM BD #29

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-12-02 Cont ID  
Sent By pkrauss Date 2003-12-02 Time 07:01 Rev Time 0.40
Received By pkrauss Date 2003-12-02 Time 06:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-29 Cont ID  
Sent By pkrauss Date 2003-09-29 Time 07:28 Rev Time 0.45
Received By pkrauss Date 2003-09-29 Time 07:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-12-06 Cont ID  
Sent By kstevens Date 2003-12-06 Time 10:39 Rev Time 1.00
Received By kstevens Date 2003-12-06 Time 10:39 Sent To  
Notes
2003-12-06 00:00:00PASSED/PROVISO - THERMAL EXPANSION CON-
 TROL REQUIRED.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-02 Cont ID  
Sent By kstevens Date 2003-10-02 Time 14:13 Rev Time 1.00
Received By kstevens Date 2003-10-02 Time 14:13 Sent To  
Notes
2003-10-02 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN CODE
  
 1) SUBMIT DETAIL FOR DRINKING FOUNTAIN.
 SHOW COMPLIANCE WITH 11-4.15 AND ALL
 SUBSECTIONS. ALSO PROVISIONS SHALL BE
 MADE FOR THOSE WHO HAVE TROUBLE BENDING
 OR STOOPING PER SEC 11-4.1.3(10)(A).
 2) SHT P2 WATER HEATER DETAIL. THERMAL
 EXPANSION PROTECTION REQUIRED PER SEC
 607.3.2
 3) SHT P2 WATER RISER DIAGRAM. AIR
 CHAMBERS ARE NOT APPROVED. PLEASE DELETE
 AT TOP OF D.F. DROP. IF WATER HAMMER IS
 USED IS SHALL BE LOCATED NEAR THE FIX-
 TURE IN AN "EFFECTIVE RANGE" NOT IN
 CEILING. PDI-WH 201/MANUF. INSTALL. IN-
 STRUCTIONS.
 4) SEE ATTACHED SHEET CONCERNING DESIGN
 PROFESSIONALS. TITLE BLOCK, CERTIFICAT-
 ION OF AUTHROIZATION ECT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]