Plan Review Details - Permit 03090080
Plan Review Stops For Permit 03090080
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-11 Cont ID  
Sent By rbrown Date 2003-09-11 Time 16:55 Rev Time 0.00
Received By rbrown Date 2003-09-11 Time 16:55 Sent To  
Notes
2003-09-11 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC* 11-4.26.3THE GRAB BARS AND THEIR
 SUPPORTS SHALL BE CAPABLE OF RESISTING A
 LOAD OF 250 LBF APPLIED IN ANY DIRECTION

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-12-29 Cont ID  
Sent By dpalmer Date 2003-12-29 Time 12:00 Rev Time 0.75
Received By dpalmer Date 2003-12-29 Time 12:00 Sent To  
Notes
2003-12-29 00:00:00**** REDLINED
  
 CWP 250.50
 210.62

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-12-16 Cont ID  
Sent By alange Date 2003-12-18 Time 14:56 Rev Time 2.00
Received By dpalmer Date 2003-12-16 Time 11:41 Sent To  
Notes
2003-12-16 00:00:00***************** UNSAT ****************
  
 PLEASE SEE THERE ARE A COMPLETELY NEW
 COMMENTS DUE TO THE PLANS/SERVICE/RISER
 BEING CHANGED FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SHOW ALL EQUIPMENT
 GROUNDING CONDUCTORS PER 250.110, 250.24
 AND SIZE PER 250.122.
  
 2)NOTE: PLEASE SEE ORIG PLANS SHOWS
 EXISTING METERSFOR 4209 & 4211, PLANS
 NOW SHOW A NEW 400A METER AND DISC YET,
 TWO EXISTING METERS ARE STILL BEING
 SHOWN AND THESE ARE NOT ON RISER DIAGRAM
 ?? PLEASE ALSO SHOW HOW AND WHERE NEW
 SERVICE IS BEING FED? FROM EXISTING
 OR NEW GUTTER/RISER ETC???215.5
 IF SERVICE IS BEING FROM EXSITNG RISER
 ETC, PLEASE PROVIDE LOAD CALCS AND SIZE
 OF EXISTING SEC'S.
  
 3)NOTE: PLEASE SEE RISER SHOWS NEW
 PANEL(MDP) "G" YET PLANS DO NOT SHOW
 A NEW PANEL SCHEDULE FOR THIS?????
  
 4)NOTE: PLEASE SEE THAT PLANS DO NOT
 SHOW NEW DISC'S THAT ARE NOW SHOWN IN-
 -BETWEEN MDP AND PANELS?
  
 5)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 SYSTEM FOR NEW SERVICE. 250.50
  
 6)NOTE: PLEASE SEE CONDUIT FILL TABLES
 BEING THAT AN EQUIPMENT GRND IS REQ'D
 AND VERIFY SIZE OF CONDUITS.
  
 7)NOTE: PLEASE SEE THAT DUE TO THE
 AMOUNT OF WORK BEING DONE "SHOW WINDOW"
 RECEPTS WILL BE REQ'D IF NOT EXSITING
 PER 210.62.
 FBC CHAPTER 34
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-15 Cont ID  
Sent By csiegber Date 2003-12-10 Time 11:06 Rev Time 0.50
Received By dpalmer Date 2003-10-15 Time 17:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By dpalmer Date 2003-09-10 Time 12:59 Rev Time 0.75
Received By dpalmer Date 2003-09-10 Time 12:59 Sent To  
Notes
2003-09-10 00:00:00***********UNSAT ***************
  
 1)NOTE: PLEASE SHOW ARE REQ'D FOR EM LTS
 TO MEET 700.16
  
 2)NOTE: OK
  
  
 3)NOTE: PLEASE SHOW LOAD CALCULATIONS
 PER NEC 220, PLEASE ALSO SHOW ANY
 CONTINUOUS AT 125%. 215.3/230.42 ETC.
  
 4)NOTE: PLEASE CLARIFY NEW OR EXISTING
 SIGN CIRCUIT PER 600.5
  
 PLEASE SEE FIRE REVIEW COMMENTS FOR
 ANY CHANGES THAT MAY BE NEEDED FOR
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-10-03 Cont ID  
Sent By mcarsill Date 2003-10-03 Time 14:49 Rev Time 0.00
Received By mcarsill Date 2003-10-03 Time 14:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-12-18 Cont ID  
Sent By alange Date 2003-12-18 Time 14:56 Rev Time 0.00
Received By alange Date 2003-12-18 Time 14:56 Sent To E
Notes
2003-12-18 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-10 Cont ID  
Sent By csiegber Date 2003-12-10 Time 11:06 Rev Time 0.00
Received By csiegber Date 2003-12-10 Time 11:06 Sent To E
Notes
2003-12-10 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-10 Cont ID  
Sent By csiegber Date 2003-10-10 Time 08:15 Rev Time 0.00
Received By csiegber Date 2003-10-10 Time 08:15 Sent To  
Notes
2003-10-10 00:00:00TO COMM BD#48

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-03 Cont ID  
Sent By csiegber Date 2003-09-03 Time 11:04 Rev Time 0.00
Received By csiegber Date 2003-09-03 Time 11:04 Sent To  
Notes
2003-09-03 00:00:00TO COMM BD #57

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-28 Cont ID  
Sent By pkrauss Date 2003-09-28 Time 14:19 Rev Time 0.55
Received By pkrauss Date 2003-09-28 Time 14:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-24 Cont ID  
Sent By kstevens Date 2003-10-24 Time 14:57 Rev Time 2.00
Received By kstevens Date 2003-10-23 Time 17:12 Sent To  
Notes
2003-10-24 00:00:00 
  
  
  
 PASSED/PROVISO
  
 FIELD INSPECTOR SHALL VERIFY THAT DRYERS
 ARE CSA APPROVED. CHECK TAG ON DRYERS.
  
 REVISION REQUIRED FOR GAS RISER DIAGRAM
 SEE RED LINE CORRECTIONS.
  
 IF GAS LINE IS WELD PIPE, THEN PRIOR TO
 COMMENCING WELDING THE FOLLOWING INFOR-
 MATION IS REQUIRED AT APPLICATION FOR
 THE SEPARATE GAS PERMIT REQUIRED.
 A) CERTIFICATION OF WELDER
 B) PICTURE IDENTIFICATION OF WELDER
 C) COPY OF WELDING PROCEDURE TO BE USED
 ---INSPECTION WILL BE REQUIRED AT TACK-
 UP OF PIPE AND FITTINGS.--INSPECTION
 WILL BE REQUIRED AT ROOT PASS --INSPECT-
 ION WILL BE REQUIRED AT FINAL WHEN GAS
 PIPE IS TESTED FOR ROUGH INSPECTION. ---
  
  
  
 Z

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-10-01 Cont ID  
Sent By kstevens Date 2003-10-01 Time 10:17 Rev Time 2.50
Received By kstevens Date 2003-10-01 Time 10:17 Sent To  
Notes
2003-10-01 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 1
  
 A) THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT. (SEPARATE PERMIT REQ'D)
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE. (SEE RED LINE COMMENTS ON
 PLANS)
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. TYPE OF GAS, (LP OR NATURAL)
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2001 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34). THERE IS CONFLICTING INFORMAT-
 ION ON PLANS. ONE NOTE STATES 40 DRYER
 UNITS, BUT THE COUNT INDICATES 36 DRYERS
 ALSO TOTAL BTU'S INCORRECT. PLEASE
 CLAIRFY.
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2001 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3). DISTANCE TO
 MOST REMOTE ON NOTES SAYS 89 FEET BUT
 THE DROP FOR THE DRYERS IN AREA 2 ARE
 NOT ADDED. PLEASE RECALCULATE.
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 TABLE 402(2) SHOWS 3,250,000 MAX FOR 3"
 PIPE. TOTAL BTU'S SEEM TO BE 3,605,000.
 EITHER 4" PIPE WILL HAVE TO BE USED OR
 A 2 LB SYSTEM CAN BE USED REDUCING MAXI-
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2001 FUEL GAS CODE SEC 402.2
 8. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
 9. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND
 APPURTENANCES PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
 10) SECTION 409.7 EACH GAS APPLIANCE
 SHALL BE PROVIDED WITH A GAS SHUTOFF
 VALVE INSTALLED UPSTREAM OF THE UNION.
 SHOW ON GAS RISER DIAGRAM.
 B) SHT 6 OF 7 WATER RISER DIAGRAM. SEC
 604.9 WATER HAMMER ARRESTORS SHALL BE
 INSTALLED FOR ALL QUICK CLOSING VALVES.
 THEY SHALL BE INSTALLED AT THE WASHMACH-
 INES AND SIZED FOR EACH RUN. ALL WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE"
 PER PDI-WH 201 AND MANUF. INSTALLATION
 INSTRUCTIONS NOT IN THE CEILING AS SH0WN
 C) SHT 6 OF 7 WATER HEATER. THERMAL
 EXPANSION PROTECTION REQUIRED PER SEC
 607.3.2
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]