| Plan Review Stops For Permit 03081864 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-11-12 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-11-12 |
Time |
13:52 |
Rev Time |
0.50 |
| Received By |
sthyng |
Date |
2003-11-12 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2003-11-12 00:00:00 | PROVISO - SUBMIT PRODUCT APPROVAL FOR | | | MULLIONS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-11-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-12 |
Time |
09:09 |
Rev Time |
0.50 |
| Received By |
sthyng |
Date |
2003-11-08 |
Time |
09:09 |
Sent To |
Z |
|
| Notes |
| 2003-11-08 00:00:00 | ****CORRECTIONS***** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | 561-805-6724 | | | | | | NOTE - THE SCOPE OF WORK HAS CHANGED | | | SINCE THE ORIGINAL APPLICATION. | | | | | | 1.)IMPACT PROTECTION REQUIRED FOR | | | GLAZING, FBC1606.1.4. | | | | | | 2.)PROVIDE TWO COPIES OF PRODUCT | | | APPROVALS FOR THE FRENCH DOORS, SINGLE | | | HUNG WINDOWS, MULLIONS, EXTERIOR DOOR AT | | | THE HWH (IF NOT COVERED BY THE FRENCH | | | DOOR PRODUCT APPROVAL), IMPACT | | | PROTECTION.ANY PRODUCT APPROVALS NOT | | | SUBMITTED AT THE TIME OF ISSUANCE WILL | | | NOT BE COVERED UNDER THIS PERMIT AND | | | A SEPARATE PERMIT WILL BE REQUIRED. | | | | | | 3.)PROVIDE AN INSTALLATION SCHEDULE | | | FOR HURRICANE SHUTTERS, SEE ATTACHED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2003-10-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-11-08 |
Time |
05:57 |
Rev Time |
0.50 |
| Received By |
sthyng |
Date |
2003-10-27 |
Time |
15:54 |
Sent To |
|
|
| Notes |
| 2003-10-27 00:00:00 | ****CORRECTIONS***** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE PLANS STILL SHOW CHANGES TO | | | THE EXTERIOR; DEMOLITION OF THE EXISTING | | | STOOP, NEW WINDOWS, CLOSING AN OPENING | | | WITH MASONRY.SEE PREVIOUS CORRECTION | | | LIST, ITEMS #2 AND 3.EITHER REMOVE | | | THESE ITEMS FROM THE PLAN OR SUBMIT A | | | SITE PLAN AND SURVEY FOR ZONING REVIEW | | | AND GET HISTORIC APPROVAL. | | | | | | 2.)ADDITIONAL PERMITS REQUIRED (GAS). | | | | | | 3.)CHANGES TO THE PLAN IN INK SHOULD | | | BE INITIALED BY THE ARCHITECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2003-10-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-25 |
Time |
10:33 |
Rev Time |
2.00 |
| Received By |
sthyng |
Date |
2003-10-15 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2003-10-15 00:00:00 | *****CORRECTIONS***** | | | | | | SAMANTHA THYNG, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THE NOTICE OF COMMENCEMENT | | | SUBMITTED STATES "REMODEL KITCHEN" AS | | | THE DESCRIPTION OF IMPROVEMENTS.REVISE | | | TO INCLUDE THE ENTIRE SCOPE OF WORK. | | | | | | 2.)ALTHOUGH THE APPLICATION STATES | | | "ALL INTERIOR WORK", THERE IS A DETAIL | | | FOR A STAIR OUTSIDE THE BREAKFAST | | | ROOM, REMOVAL OF EXISTING STOOP. PROVIDE | | | A SITE PLAN AND A SURVEY.ZONING AND | | | HISTORIC REVIEW REQUIRED FOR EXTERIOR | | | CHANGES. | | | | | | 3.)THE PLANS SHOULD REFLECT THE | | | SCOPE OF WORK TO BE COVERED UNDER THIS | | | PERMIT.IN ADDITION TO THE ITEMS LISTED | | | UNDER #2 ABOVE, THERE ARE REFERENCES | | | TO REMOVAL OF WINDOWS AND ALTERATION OF | | | EXTERIOR WALLS.REVISE THE PLANS TO | | | REFLECT THE SCOPE OF WORK TO BE | | | COVERED UNDER THIS PERMIT.EXTERIOR | | | CHANGES TO BE APPROVED BY HISTORIC | | | PRESERVATION DIVISION. | | | | | | 4.)ADDITIONAL PERMITS REQUIRED (GAS). |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2004-01-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2004-01-13 |
Time |
13:23 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2004-01-13 |
Time |
13:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-11-06 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-08 |
Time |
16:38 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-11-06 |
Time |
12:58 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2003-10-24 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-04 |
Time |
10:32 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-10-24 |
Time |
07:41 |
Sent To |
P |
|
| Notes |
| 2003-10-24 00:00:00 | ************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SEE THAT PLANS ARE NOW | | | COMING BACK ADDING A NEW SERVICE. | | | THE NEW SERVICE IS NOT PERMITTED. 230.2 | | | PLEASE ALSO NOTE, OLD SERVICE WILL BE | | | REQ'D TO BE CHANGED IN ORDER TO TAKE OUT | | | SECOND METER CAN. ONLY TWO(2) METERS | | | TOTAL ARE PERMITTED PER ZONING. | | | REMOVAL OF METER ALONE WILL NOT MEET | | | REQUIREMENT. PLEASE ADJUST SERVICE. | | | A MCB AT MAIN HOUSE IS STILL REQ'D. | | | 225.31 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2003-09-19 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-20 |
Time |
13:45 |
Rev Time |
1.00 |
| Received By |
dpalmer |
Date |
2003-09-19 |
Time |
07:31 |
Sent To |
P |
|
| Notes |
| 2003-09-19 00:00:00 | ************** UNSAT ******************* | | | | | | 1)NOTE: PLEASE SEE RISER, SHOWS MAIN | | | DISC FOR PANEL "A" AT DETACHED BLDG/ | | | COTTAGE. PLEASE SEE 225.31 FOR MEANS | | | OF DISC REQ'D. | | | PLANS DO NOT INDICATE MCB. | | | | | | 2)NOTE: PLEASE SEE PLANS, SHOWS LOCATION | | | FOR PANEL 'A' BUT PANEL 'B' IS NOTED | | | TO BE IN AREA BUT NOT SHOWN? | | | PLEASE SHOW. | | | | | | 3)NOTE: PLEASE CLARIFY/ SHOW COLD WATER | | | BOND FOR SERVICE GROUNDING SYSTEM. | | | 250.50,250.32 | | | | | | 4)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | | PROTECTED CIRCUITS PER 210.12 | | | | | | 5)NOTE: PLEASE SEE MISSING RECEPTS IN | | | MAST BEDRM. 210.52 | | | | | | 6)NOTE: PLEASE SEE PANEL "A", PANEL | | | DETAIL INDICATES CIRCUITS 27,29 TO BE | | | GFI AND YET 27/29 FEED PANEL "B"? | | | PLEASE CLARIFY. | | | | | | 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR | | | NEW MAIN. 110.9/215.5 | | | | | | 8)NOTE: PLEASE SEE FAC 61G15-23.002, | | | PLEASE PROVIDE CETIFICATE OF AUTHORIZAT- | | | -ION # ON TITLE BLOCK. FS 471 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2004-01-08 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-08 |
Time |
16:38 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-08 |
Time |
16:38 |
Sent To |
E |
|
| Notes |
| 2004-01-08 00:00:00 | TO DP DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2003-11-12 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-11-12 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-12 |
Time |
09:09 |
Sent To |
B |
|
| Notes |
| 2003-11-12 00:00:00 | TO ST DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2003-11-04 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2003-11-10 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-11-04 |
Time |
10:32 |
Sent To |
E |
|
| Notes |
| 2003-11-04 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-10-20 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-20 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-20 |
Time |
13:45 |
Sent To |
E |
|
| Notes |
| 2003-10-20 00:00:00 | TO DP DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-09-17 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-09-17 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-09-17 |
Time |
11:57 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2003-11-08 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2003-09-24 |
Time |
20:02 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-11-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-11-08 |
Time |
05:57 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-11-08 |
Time |
05:57 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2003-10-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-11-06 |
Time |
12:58 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-25 |
Time |
10:24 |
Sent To |
B |
|
| Notes |
| 2003-10-25 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) SANITARY RISER DIAGRAM DO NOT MEET | | | CODE REQUIREMENTS NOR DO THEY REFLECT | | | THE FLOOR PLAN. | | | POWDER ROOM: LAV NOT VENTED. "S" TRAPS | | | NOT APPROVED SECTION 1002.3(5) | | | KITCHEN: ISLAND SINK TO CONNECT ON THE | | | HORIZONTAL BLDG DRAIN. DISHWASHER SHALL | | | CONNECT TO THE TAILPIECE OF THE SINK. | | | BAR SINK: SHALL CONNECT ON THE HORIZONT- | | | AL BLDG. DRAIN AND HAVE A SEPARATE STACK | | | MASTER BATHS: TUB WITH WATER CLOSETS IS | | | NOT VENTED. FIXTURES NOT VENTED ON OTHER | | | STACK, LAVS ARE "S" TRAPPED AND BOTH | | | LAVS ARE NOT ON THE SAME SIDE OF THE | | | WALL. | | | 2) SUBMIT A RISER DIAGRAM SHOWING ALL | | | THE HORIZONTAL BUILDING DRAIN AND SHOW- | | | ING WHERE THE STACKS TIE IN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2003-09-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-10-24 |
Time |
07:42 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2003-09-24 |
Time |
20:02 |
Sent To |
M |
|
| Notes |
| 2003-09-24 00:00:00 | NO PLUMBING PLAN REVIEW DONE NOT ENOUGH | | | INFORMATION. NO RISER DIAGRAM. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2003-11-10 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-11-08 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2003-11-10 |
Time |
11:12 |
Sent To |
I |
|
| Notes |
|
|