Plan Review Details - Permit 03081864
Plan Review Stops For Permit 03081864
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-11-12 Cont ID  
Sent By sthyng Date 2003-11-12 Time 13:52 Rev Time 0.50
Received By sthyng Date 2003-11-12 Time 13:52 Sent To  
Notes
2003-11-12 00:00:00PROVISO - SUBMIT PRODUCT APPROVAL FOR
 MULLIONS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-11-08 Cont ID  
Sent By csiegber Date 2003-11-12 Time 09:09 Rev Time 0.50
Received By sthyng Date 2003-11-08 Time 09:09 Sent To Z
Notes
2003-11-08 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 561-805-6724
  
 NOTE - THE SCOPE OF WORK HAS CHANGED
 SINCE THE ORIGINAL APPLICATION.
  
 1.)IMPACT PROTECTION REQUIRED FOR
 GLAZING, FBC1606.1.4.
  
 2.)PROVIDE TWO COPIES OF PRODUCT
 APPROVALS FOR THE FRENCH DOORS, SINGLE
 HUNG WINDOWS, MULLIONS, EXTERIOR DOOR AT
 THE HWH (IF NOT COVERED BY THE FRENCH
 DOOR PRODUCT APPROVAL), IMPACT
 PROTECTION.ANY PRODUCT APPROVALS NOT
 SUBMITTED AT THE TIME OF ISSUANCE WILL
 NOT BE COVERED UNDER THIS PERMIT AND
 A SEPARATE PERMIT WILL BE REQUIRED.
  
 3.)PROVIDE AN INSTALLATION SCHEDULE
 FOR HURRICANE SHUTTERS, SEE ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-10-27 Cont ID  
Sent By kstevens Date 2003-11-08 Time 05:57 Rev Time 0.50
Received By sthyng Date 2003-10-27 Time 15:54 Sent To  
Notes
2003-10-27 00:00:00****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE PLANS STILL SHOW CHANGES TO
 THE EXTERIOR; DEMOLITION OF THE EXISTING
 STOOP, NEW WINDOWS, CLOSING AN OPENING
 WITH MASONRY.SEE PREVIOUS CORRECTION
 LIST, ITEMS #2 AND 3.EITHER REMOVE
 THESE ITEMS FROM THE PLAN OR SUBMIT A
 SITE PLAN AND SURVEY FOR ZONING REVIEW
 AND GET HISTORIC APPROVAL.
  
 2.)ADDITIONAL PERMITS REQUIRED (GAS).
  
 3.)CHANGES TO THE PLAN IN INK SHOULD
 BE INITIALED BY THE ARCHITECT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-10-15 Cont ID  
Sent By kstevens Date 2003-10-25 Time 10:33 Rev Time 2.00
Received By sthyng Date 2003-10-15 Time 11:39 Sent To  
Notes
2003-10-15 00:00:00*****CORRECTIONS*****
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE NOTICE OF COMMENCEMENT
 SUBMITTED STATES "REMODEL KITCHEN" AS
 THE DESCRIPTION OF IMPROVEMENTS.REVISE
 TO INCLUDE THE ENTIRE SCOPE OF WORK.
  
 2.)ALTHOUGH THE APPLICATION STATES
 "ALL INTERIOR WORK", THERE IS A DETAIL
 FOR A STAIR OUTSIDE THE BREAKFAST
 ROOM, REMOVAL OF EXISTING STOOP. PROVIDE
 A SITE PLAN AND A SURVEY.ZONING AND
 HISTORIC REVIEW REQUIRED FOR EXTERIOR
 CHANGES.
  
 3.)THE PLANS SHOULD REFLECT THE
 SCOPE OF WORK TO BE COVERED UNDER THIS
 PERMIT.IN ADDITION TO THE ITEMS LISTED
 UNDER #2 ABOVE, THERE ARE REFERENCES
 TO REMOVAL OF WINDOWS AND ALTERATION OF
 EXTERIOR WALLS.REVISE THE PLANS TO
 REFLECT THE SCOPE OF WORK TO BE
 COVERED UNDER THIS PERMIT.EXTERIOR
 CHANGES TO BE APPROVED BY HISTORIC
 PRESERVATION DIVISION.
  
 4.)ADDITIONAL PERMITS REQUIRED (GAS).

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2004-01-13 Cont ID  
Sent By dpalmer Date 2004-01-13 Time 13:23 Rev Time 0.50
Received By dpalmer Date 2004-01-13 Time 13:23 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-11-06 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:38 Rev Time 0.33
Received By dpalmer Date 2003-11-06 Time 12:58 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-11-04 Time 10:32 Rev Time 0.50
Received By dpalmer Date 2003-10-24 Time 07:41 Sent To P
Notes
2003-10-24 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE NOW
 COMING BACK ADDING A NEW SERVICE.
 THE NEW SERVICE IS NOT PERMITTED. 230.2
 PLEASE ALSO NOTE, OLD SERVICE WILL BE
 REQ'D TO BE CHANGED IN ORDER TO TAKE OUT
 SECOND METER CAN. ONLY TWO(2) METERS
 TOTAL ARE PERMITTED PER ZONING.
 REMOVAL OF METER ALONE WILL NOT MEET
 REQUIREMENT. PLEASE ADJUST SERVICE.
 A MCB AT MAIN HOUSE IS STILL REQ'D.
 225.31
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-19 Cont ID  
Sent By csiegber Date 2003-10-20 Time 13:45 Rev Time 1.00
Received By dpalmer Date 2003-09-19 Time 07:31 Sent To P
Notes
2003-09-19 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE RISER, SHOWS MAIN
 DISC FOR PANEL "A" AT DETACHED BLDG/
 COTTAGE. PLEASE SEE 225.31 FOR MEANS
 OF DISC REQ'D.
 PLANS DO NOT INDICATE MCB.
  
 2)NOTE: PLEASE SEE PLANS, SHOWS LOCATION
 FOR PANEL 'A' BUT PANEL 'B' IS NOTED
 TO BE IN AREA BUT NOT SHOWN?
 PLEASE SHOW.
  
 3)NOTE: PLEASE CLARIFY/ SHOW COLD WATER
 BOND FOR SERVICE GROUNDING SYSTEM.
 250.50,250.32
  
 4)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS PER 210.12
  
 5)NOTE: PLEASE SEE MISSING RECEPTS IN
 MAST BEDRM. 210.52
  
 6)NOTE: PLEASE SEE PANEL "A", PANEL
 DETAIL INDICATES CIRCUITS 27,29 TO BE
 GFI AND YET 27/29 FEED PANEL "B"?
 PLEASE CLARIFY.
  
 7)NOTE: PLEASE SUBMIT AIC RATING(S) FOR
 NEW MAIN. 110.9/215.5
  
 8)NOTE: PLEASE SEE FAC 61G15-23.002,
 PLEASE PROVIDE CETIFICATE OF AUTHORIZAT-
 -ION # ON TITLE BLOCK. FS 471
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-01-08 Cont ID  
Sent By csiegber Date 2004-01-08 Time 16:38 Rev Time 0.00
Received By csiegber Date 2004-01-08 Time 16:38 Sent To E
Notes
2004-01-08 00:00:00TO DP DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-11-12 Cont ID  
Sent By csiegber Date 2003-11-12 Time 09:09 Rev Time 0.00
Received By csiegber Date 2003-11-12 Time 09:09 Sent To B
Notes
2003-11-12 00:00:00TO ST DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-11-04 Cont ID  
Sent By mmclean Date 2003-11-10 Time 11:12 Rev Time 0.00
Received By csiegber Date 2003-11-04 Time 10:32 Sent To E
Notes
2003-11-04 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-20 Cont ID  
Sent By csiegber Date 2003-10-20 Time 13:45 Rev Time 0.00
Received By csiegber Date 2003-10-20 Time 13:45 Sent To E
Notes
2003-10-20 00:00:00TO DP DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-09-17 Cont ID  
Sent By csiegber Date 2003-09-17 Time 11:57 Rev Time 0.00
Received By csiegber Date 2003-09-17 Time 11:57 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-11-08 Cont ID  
Sent By jleech Date 2003-09-24 Time 20:02 Rev Time 0.00
Received By sthyng Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-11-08 Cont ID  
Sent By kstevens Date 2003-11-08 Time 05:57 Rev Time 0.25
Received By kstevens Date 2003-11-08 Time 05:57 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-10-25 Cont ID  
Sent By dpalmer Date 2003-11-06 Time 12:58 Rev Time 0.50
Received By kstevens Date 2003-10-25 Time 10:24 Sent To B
Notes
2003-10-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) SANITARY RISER DIAGRAM DO NOT MEET
 CODE REQUIREMENTS NOR DO THEY REFLECT
 THE FLOOR PLAN.
 POWDER ROOM: LAV NOT VENTED. "S" TRAPS
 NOT APPROVED SECTION 1002.3(5)
 KITCHEN: ISLAND SINK TO CONNECT ON THE
 HORIZONTAL BLDG DRAIN. DISHWASHER SHALL
 CONNECT TO THE TAILPIECE OF THE SINK.
 BAR SINK: SHALL CONNECT ON THE HORIZONT-
 AL BLDG. DRAIN AND HAVE A SEPARATE STACK
 MASTER BATHS: TUB WITH WATER CLOSETS IS
 NOT VENTED. FIXTURES NOT VENTED ON OTHER
 STACK, LAVS ARE "S" TRAPPED AND BOTH
 LAVS ARE NOT ON THE SAME SIDE OF THE
 WALL.
 2) SUBMIT A RISER DIAGRAM SHOWING ALL
 THE HORIZONTAL BUILDING DRAIN AND SHOW-
 ING WHERE THE STACKS TIE IN.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-24 Cont ID  
Sent By dpalmer Date 2003-10-24 Time 07:42 Rev Time 0.33
Received By jleech Date 2003-09-24 Time 20:02 Sent To M
Notes
2003-09-24 00:00:00NO PLUMBING PLAN REVIEW DONE NOT ENOUGH
 INFORMATION. NO RISER DIAGRAM.

Review Stop Z ZONING
Rev No 1 Status P Date 2003-11-10 Cont ID  
Sent By sthyng Date 2003-11-08 Time 09:09 Rev Time 0.00
Received By mmclean Date 2003-11-10 Time 11:12 Sent To I
Notes
***NONE***