Plan Review Details - Permit 03081857
Plan Review Stops For Permit 03081857
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-08 Cont ID  
Sent By sthyng Date 2003-10-08 Time 07:39 Rev Time 1.00
Received By sthyng Date 2003-10-08 Time 07:39 Sent To  
Notes
2003-10-08 00:00:00NOTE - CONTRACTOR ON ORIGINAL PLAN
 SHOWED AN EX. PORCH W/EXTERIOR WALLS.
 THIS WAS ACTUALLY LIVING SPACE, NO
 IMPACT OR ENERGY CALCS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-10-06 Time 16:49 Rev Time 0.50
Received By sthyng Date 2003-09-24 Time 09:42 Sent To  
Notes
2003-09-24 00:00:00*****CORRECTIONS******
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THERE IS AN EXISTING WINDOW ON THE
 EXTERIOR WALL AT THE PROPOSED BATHROOM
 TO COMPLY WITH THE MECHANICAL PROVISO
 (AS PER CONVERSATION WITH CONTRACTOR).
 SHOW ON THE PLAN.
  
 2.)PROVIDE AREA CALCULATION ON THE
 PLAN - EXISTING, PROPOSED, NEW TOTALS
 FOR A/C AND UNCONDITIONED SPACE.
  
 3.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025
  
 4.)THE PLAN SHOWS "EXISTING ENCLOSED
 PORCH".PROVIDE A WALL DETAIL WITH
 STRUCTURAL INFORMATION, INCLUDING
 ATTACHMENTS CONTINUOUS FROM FOUNDATION
 THROUGH THE ROOF FBC104.3.1.1. (EXTERIOR
 WALL), TO COMPLY WITH FBC.
  
 5.)ENERGY CALCS REQUIRED, FBC13-103.1.
 2.
  
 6.)PROVIDE A WALL SECTION FOR THE
 INTERIOR PARTITION WALL, INCLUDING
 FIRESTOP AND INSULATION.
  
 7.)SHOW EMERGENCY EGRESS FOR THE
 BEDROOM, FBC1005.4.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-09-02 Time 12:12 Rev Time 0.25
Received By btrobaug Date 2003-09-04 Time 13:52 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-10-06 Cont ID  
Sent By csiegber Date 2003-10-06 Time 16:48 Rev Time 0.00
Received By csiegber Date 2003-10-06 Time 16:48 Sent To B
Notes
2003-10-06 00:00:00TO ST DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-03 Cont ID  
Sent By mmclean Date 2003-10-06 Time 16:08 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 15:55 Sent To Z
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-02 Cont ID  
Sent By mmclean Date 2003-09-24 Time 14:14 Rev Time 0.00
Received By csiegber Date 2003-09-02 Time 12:12 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-29 Cont ID  
Sent By mmclean Date 2003-09-02 Time 11:35 Rev Time 0.00
Received By dbaxter Date 2003-08-29 Time 15:29 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2003-09-15 Cont ID  
Sent By kstevens Date 2003-09-09 Time 13:22 Rev Time 0.15
Received By pkrauss Date 2003-09-15 Time 12:29 Sent To B
Notes
2003-09-15 00:00:00PROVISO:
 AS PER 2001 FBC(M) 402.3.1 REVISION
 EFFECTIVE JUNE 30, 2003:
  
 RESIDENTIAL BATHROOMS SHALL HAVE A
 WINDOW WITH A MINIMUM OF 3 SQ FT OF OPEN
 SPACE OR BE MECHANICALLY VENTILATED.
  
 NO MECHANICAL PLANS OR INFORMATION
 SUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-09 Cont ID  
Sent By pkrauss Date 2003-09-15 Time 12:29 Rev Time 0.25
Received By kstevens Date 2003-09-09 Time 13:21 Sent To M
Notes
2003-09-09 00:00:00NO PLUMBING PLANS SUBMITTED

Review Stop Z ZONING
Rev No 2 Status P Date 2003-10-06 Cont ID  
Sent By mmclean Date 2003-10-06 Time 16:08 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2003-09-24 Cont ID  
Sent By csiegber Date 2003-10-03 Time 15:56 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-09-24 00:00:009/24/03 DENIED, NEED TO PROVIDE 2 COPY
 OF SURVEY CALLED CONTR MM