Plan Review Details - Permit 03081707
Plan Review Stops For Permit 03081707
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-17 Cont ID  
Sent By rbrown Date 2003-10-17 Time 16:32 Rev Time 0.00
Received By rbrown Date 2003-10-17 Time 16:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-08 Cont ID  
Sent By rbrown Date 2003-09-08 Time 08:51 Rev Time 0.00
Received By rbrown Date 2003-09-08 Time 08:51 Sent To  
Notes
2003-09-08 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 11-7.2THE ACCESSIBLE CHECKOUT
 SHALL HAVE A MIN. 36" LONG SECTION OF
 COUNTER AT MAX. 36" ABOVE FINISHED FLOOR

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-10-14 Cont ID  
Sent By dpalmer Date 2003-10-14 Time 20:17 Rev Time 0.25
Received By dpalmer Date 2003-10-14 Time 20:17 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2003-10-08 Cont ID  
Sent By dpalmer Date 2003-10-08 Time 19:56 Rev Time 0.50
Received By dpalmer Date 2003-10-08 Time 19:55 Sent To  
Notes
2003-10-08 00:00:00*********** UNSAT ****************
  
 1)NOTE: PLEASE SEE THAT TITLE BLOCK FOR
 ENGINEERS AHS BEEN REMOVED AND ARCH IS
 NOW PRESENT.
 PLEASE SEE FS 471.003H2AAND SEE
 FBC 104.4.1.3. ELECTRICAL SYSTEMS OF
 277/480V MUST BE DESIGNED, SIGNED,DATED
 AND SEALED BY AN ENGINEER. ORIG PLANS
 HAD ENGINEER TITLE BLOCK WHICH LETTER
 EXPLAINS IT WAS SUBMITTED IN ERROR.
 PLANS WILL STILL BE REQ'D TO HAVE A
 TITLE BLOCK FOR ENGINEER WHICH MAY OR
 MAY NOT INCLUDE A CA #.
 61G15-23.002/ 471.025
  
 PLEASE SEE THAT ELECTRICAL COMMENTS
 SEEM TO BE ADDRESSED. PLANS WILL BE
 GOING BACK TO BLDG AND MECH PLAN REVIEW
 DUE TO REVISED B&M SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-10-03 Time 12:38 Rev Time 1.00
Received By dpalmer Date 2003-09-08 Time 08:05 Sent To  
Notes
2003-09-08 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE COPY OF FAC 61G1-16.
 004.PLEASE SEE THAT FIRM'S AA# IS REQ'D
 ON TITLE BLOCK ALSO. PER FS 481
 **ALL SHEETS, NOT ONLY ELECTRICAL.
 2)NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%. 215.3/
 230.42 ETC.
  
 3)NOTE: PLEASE SHOW CALCULATIONS FOR
 TRACK LIGHTING PER 220.12B
  
 4)NOTE: PLEASE SEE CODES REFERENCED ON
 PLANS, THEY ARE FROM THE 1996 NEC,
 PLEASE SEE THAT WE ARE NOW UNDER 2002
 NEC AND ALL CODES REF. SHOULD CORRELATE.
  
 5)NOTE: PLEASE SUBMIT AIC RATING FOR
 NEW MAIN ALSO. 110.9/215.5
  
 6)NOTE: PLEASE SHOW GROUNDING ATTACH-
 -MENT FOR TRANSFORMER PER 250.30
  
 7)NOTE; PLEASE SEE NEC FOR TRANSFORMER
 CONNECTIONS, PLAN SHOW EMT TO AND FROM
 X-FORMER, PLEASE NOTE, THESE ARE TO BE
 FLEXIBLE CONNECTIONS W/ EQUIPMENT
 GROUNDING CONDUCTORS. 250.110, 450.10,
 300.10 ETC DUE TO VIBRATION OF TRANS-
 FORMER.
  
 8)NOTE: PLEASE ALSO SHOW LARGEST MOTOR
 LOAD AT 125%.
  
  
 PLEASE REMOVE ALL OLD VOIDED SHEEST AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. ONE SET OF OLD
 SHEETS MAY NEED TO BE RESUBMITTED FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-09-05 Cont ID  
Sent By nmccray Date 2003-09-05 Time 14:52 Rev Time 0.00
Received By nmccray Date 2003-09-05 Time 14:52 Sent To  
Notes
2003-09-05 00:00:00*************PROVISO********************
 WALLS INTERIOR FINISH SHALL BE CLASS "A"
 OR CLASS "B".
 ADDITIONAL PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS REMODEL.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-09 Cont ID  
Sent By csiegber Date 2003-10-09 Time 08:22 Rev Time 0.00
Received By csiegber Date 2003-10-09 Time 08:22 Sent To  
Notes
2003-10-09 00:00:00TO COMM BD#50

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-03 Cont ID  
Sent By csiegber Date 2003-10-03 Time 12:38 Rev Time 0.00
Received By csiegber Date 2003-10-03 Time 12:38 Sent To E
Notes
2003-10-03 00:00:00TO DP DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-29 Cont ID  
Sent By csiegber Date 2003-08-29 Time 08:42 Rev Time 0.00
Received By csiegber Date 2003-08-29 Time 08:41 Sent To  
Notes
2003-08-29 00:00:00TO COMM BD #49

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By pkrauss Date 2003-10-10 Time 12:21 Rev Time 0.45
Received By pkrauss Date 2003-10-10 Time 12:21 Sent To  
Notes
2003-10-10 00:00:00PROVISO:
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 REQUIRED AS PER 2001 FBC(M) 606.2.1 AND
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS AS PER NFPA
 90A 4-4.4.3.PLEASE NOTE, DUCT SMOKE
 DETECTORS SHALL BE INSTALLED IN THE
 SUPPLY DUCT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-30 Cont ID  
Sent By pkrauss Date 2003-09-24 Time 10:42 Rev Time 0.40
Received By pkrauss Date 2003-09-24 Time 10:42 Sent To  
Notes
2003-09-24 00:00:00PROVISO:
 1.PLEASE NOTE OUTSIDE AIR INTAKE
 SHALL BE LOCATED A MINIMUM OF 10 FT FROM
 LOT LINES OR BUILDINGS ON THE SAME LOT.
 WHERE OPENINGS FROM ON A STREET OR
 PUBLIC WAY, THE DISTANCE SHALL BE
 MEASURED TO THE CENTERLINE OF STREET OR
 WALKWAY.
  
 2.FAN SHUTDOWN REQUIRED WITH NOTIFICAT
 NOTIFICATION TO ALARM/STROBE AS PER
 2001 FBC(M) 606.2.1 & NFPA 90A 4-4.4.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 15:15 Rev Time 0.25
Received By kstevens Date 2003-09-30 Time 15:15 Sent To  
Notes
2003-09-30 00:00:00NO PLUMBING WORK BEING DONE. MINIMUM
 FIXTURE FACILITIES PER TABLE 403.1 ARE
 MET.