Plan Review Details - Permit 03081679
Plan Review Stops For Permit 03081679
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-11-04 Cont ID  
Sent By rbrown Date 2003-11-04 Time 11:56 Rev Time 0.00
Received By rbrown Date 2003-11-04 Time 11:56 Sent To  
Notes
2003-11-04 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 SUBMITTAL ON 10/23/03 FOR ACCESSIBILITY
 REQUIREMENTS AS PER PROVISOS FROM
 9/04/03 PLAN REVIEW.
  
 --PROVISO--
 THE SUBMITTED MANUFACTURER'S CUT SHEET
 FOR THE 'AQUABATH IS4136BF' TRANSFER
 SHOWER SHOWS A 3/4" EXTERIOR HEIGHT
 DIMENSION AT THE STALL CURB.WHEN THE
 STALL IS INSTALLED, THE CURB SHALL BE NO
 HIGHER THAN 1/2" (SEE FBC 11-4.12.7).
 IT IS NOTED THAT SHEET 2 OF THE
 MANUFACTURERS DETAILS STATES "THE
 IS4136BF 3/4, AS SHOWN, IS NOT ADA
 COMPLIANT".PLEASE NOTE THAT THE CUT
 SHEETS HAVE BEEN REVIEWED FOR COMPLIANCE
 WITH THE FLORIDA BUILDING CODE WHICH
 INCLUDES FLORIDA ACCESSIBILTY CODE.ALL
 WORK IS SUBJECT TO FIELD INSPECTOR'S
 APPROVAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-04 Cont ID  
Sent By csiegber Date 2003-10-24 Time 11:13 Rev Time 0.00
Received By rbrown Date 2003-09-04 Time 16:00 Sent To  
Notes
2003-09-04 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 --PROVISO--
 FBC 11-6.1(1)FOR A PSYCHIATRIC
 FACILITY MIN. 10% OF THE PATIENT ROOMS
 ARE REQUIRED TO BE ACCESSIBLE.THE FOUR
 NEW ROOMS ARE NOT ACCESSIBLE AS THERE IS
 NOT 18" CLEARANCE BETWEEN THE STRIKE
 EDGE OF THE ROOM ENTRY DOOR AND THE
 ADJACENT WALL ON THE PULL-SIDE (REF.
 FIG. 25(A)). CONFIRM THAT A TOTAL OF 10%
 OF THE PATIENT ROOMS ARE ACCESSIBLE (SEE
 ALSO, THE COMMENT BELOW).
  
 --PROVISO--
 FBC* 104.2.1SHEET A2.2, PATIENT
 BATHROOM DETAILS 1 TO 4 STATE "TOILET TO
 MEET FBC 11-4.16", "LAVATORY TO MEET
 FBC 11-4.19" AND SPECIFY "AQUABATH
 C4136BF TRANSFER SHOWER".IF THE NEW
 PATIENT ROOMS ARE REQUIRED TO BE
 ACCESSIBLE (SEE COMMENT ABOVE), THE
 PLANS SHALL NOT SIMPLY CITE THE CODE
 AND THE MANUFACTURER'S REFERENCE, THEY
 SHALL INCLUDE DIMENSIONS/CLEARANCES/
 HEIGHTS FOR THE TOILET, LAVATORY AND
 TRANSFER SHOWER.FOR THE SHOWER,
 SUBMITTAL OF THE MANUFACTURERS DETAILS
 WOULD BE SUFFICIENT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-09 Cont ID  
Sent By dpalmer Date 2003-09-09 Time 17:57 Rev Time 0.75
Received By dpalmer Date 2003-09-09 Time 17:31 Sent To  
Notes
2003-09-09 00:00:00RDLINED NOTE, ATS, SHOWN AS 260A,
 PLEASE SEE 240.6 FOR COMMON OCP SIZES.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-09-03 Cont ID  
Sent By mamini Date 2003-09-03 Time 15:15 Rev Time 0.50
Received By mamini Date 2003-09-03 Time 15:15 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-09-08 Cont ID  
Sent By nmccray Date 2003-09-08 Time 10:42 Rev Time 0.00
Received By nmccray Date 2003-09-08 Time 10:42 Sent To  
Notes
2003-09-08 00:00:00**************PROVISO*******************
 ADDITIONAL SHOP DRAWINGS AND PERMITS ARE
 REQUIRED FOR FIRE ALARM AND FIRE
 SPRINKLER SYSTEMS.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-10-24 Cont ID  
Sent By csiegber Date 2003-10-24 Time 11:13 Rev Time 0.00
Received By csiegber Date 2003-10-24 Time 11:13 Sent To B
Notes
2003-10-24 00:00:00TO RB DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-29 Cont ID  
Sent By csiegber Date 2003-08-29 Time 08:13 Rev Time 0.00
Received By csiegber Date 2003-08-29 Time 08:13 Sent To  
Notes
2003-08-29 00:00:00TO COMM BD #36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-28 Cont ID  
Sent By mmclean Date 2003-08-28 Time 15:50 Rev Time 0.00
Received By dbaxter Date 2003-08-28 Time 11:38 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-29 Cont ID  
Sent By pkrauss Date 2003-09-29 Time 07:26 Rev Time 0.40
Received By pkrauss Date 2003-09-29 Time 07:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-29 Cont ID  
Sent By kstevens Date 2003-09-29 Time 13:18 Rev Time 1.25
Received By kstevens Date 2003-09-29 Time 13:18 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-28 Cont ID  
Sent By dbaxter Date 2003-08-28 Time 11:38 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***