Plan Review Details - Permit 03081533
Plan Review Stops For Permit 03081533
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By hpiskura Date 2003-09-10 Time 16:28 Rev Time 0.00
Received By hpiskura Date 2003-09-10 Time 16:28 Sent To  
Notes
2003-09-10 00:00:00THIS IS A THRESHOLD BUILDING AND WILL
 REQUIRE A THRESHOLD INSPECTION PLAN,
 THRESHOLD INSPECTOR AND THE STATEMENT
 ON THE PLANS AS PROVIDED FOR IN FBC 105.
 13.4.4.
  
 FBC 3401.4 REQUIRES THE ENTIRE BUILDING
 BE ALTERED TO MEET THE CODE WHEN THE
 HEIGHT IS INCREASED.
  
 THE NOTES ON SHEET A3 REFERENCE THE
 1994SBC.FLORIDA IS CURRENTLY USING
 THE 2001 FLORIDA BUILDING CODE WITH THE
 JUNE 2003 REVISIONS.PLEASE REVISE AS
 NECESSARY AND ENSURE COMPLIANCE WITH
 SAME.ALSO, SEE FBC 104.2.1 REGARDING
 QUOTING CODE SECTIONS NOT BEING
 ACCEPTABLE FOR SPECIFIC DESIGN
 INFORMATION.
  
 THE COMMON PATH OF TRAVEL TO THE EXIT
 EXCEEDS THE 50' ALLOWED BY FBC 1027.6.3.
 PLEASE REVISE AS NECESSARY.
  
 PLEASE PROVIDE SKETCHES AND
 CALCULATIONS DEMONSTRATING THAT THE
 PROPOSED AND EXISTING PORTIONS OF THE
 GARAGE MEETS ONE OF THE METHODS FOR AN
 OPEN PARKING GARAGE IN ACCORDANCE WITH
 FBC 411.3.2 OR COMPLY WITH FBC 411.4
 FOR AN ENCLOSED GARAGE.
  
 SHOW THE CLEAR HEIGHT OF THE GARAGE
 THROUGHOUT OF AT LEAST 7'.SEE FBC
 411.2.2.
  
 PROVIDE THE VERTICAL ACCESSIBILITY IN
 ACCORDANCE WITH FBC 11-4.1.5.SEE ALSO
 FBC 11-4.6.2.
  
 THE STRUCTURAL PLANS DO NOT SHOW ANY
 DETAILS OR DIMENSIONS FOR THE WALL
 OPENINGS.
  
 PLEASE PROVIDE STRUCTURAL COMPUTATIONS
 AND THE METHOD OF INVESTIGATION USED
 DEMONSTRATING THAT THE EXISTING
 STRUCTURE WILL SUPPORT THE ADDED
 BUILDING AREA AND MEETS THE CURRENT
 CODE.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-15 Cont ID  
Sent By dbaxter Date 2003-09-03 Time 15:41 Rev Time 1.00
Received By dpalmer Date 2003-09-15 Time 16:11 Sent To  
Notes
2003-09-15 00:00:00************** UNSAT ****************
  
 PLEASE SEE COMMENTS FROM OTHER REVIEWERS
 THAT MAY HAVE AN EFFECT ON ELECTRICAL
 PLANS.
  
 1)NOTE: PLEASE SEE THAT WE ARE NOW UNDER
 2002 NEC AND2001 FBC WHICH WIND LOADS
 ARE AT 140MPH. POLES SHOWN FOR 120MPH.
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002,
 PLEASE INCLUDE ANY CERTIFICATE OF
 AUTHORIZATION #ON TITLE BLOCK WITH ALL
 OTHER INFORMATION AS REQUESTED UNDER FS
 471/
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2003-09-05 Cont ID  
Sent By mamini Date 2003-09-05 Time 09:34 Rev Time 0.50
Received By mamini Date 2003-09-05 Time 09:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-16 Cont ID  
Sent By mcarsill Date 2003-09-16 Time 07:31 Rev Time 0.00
Received By mcarsill Date 2003-09-16 Time 07:31 Sent To  
Notes
2003-09-16 00:00:001) SITE PLAN HAS WRONG STREET NAMES.
 MONGOMERY WAY AND PLACE ARE INCORRECT.
 PLEASE REVISE AS NECESSARY.
  
 2) PLEASE INDICATE ON PLANS THAT THE
 PARKING GARAGE IS EITHER CONSIDERED
 AN OPEN OR CLOSED PARKING GARAGE.
  
 3) PLEASE INDICATE THE EXISTING TWO
 MEANS OF EGRESS IN THE PARKING GARAGE
 ON SP-2.
  
 4) PLEASE INDICATE FIRE RATINGS OF
 NEW STAIRWELL DOORS FOR LEVELS J & K.
 ALSO PLEASE INDICATE SELF-CLOSING
 DEVICES WILL BE PRESENT.
  
 5) STAIRWELL SIGNS ARE REQUIRED
 INDICATING THE STAIR #, TERMINUS AT
 THE TOP OR BOTTOM, ETC. ALSO TACTILE
 SIGNAGE IS REQUIRED AT STAIR DOOR
 OPENINGS.
  
 6) PLAN SHEET MP-2 INDICATES "ADD FIRE
 DEPARTMENT CONNECTION". DO YOU NOT
 MEAN HOSE VALVES INSTEAD OF FDC"S.
 FDC'S ARE CONNECTED TO PUMP TO THE
 SYSTEM, NOT CONNECT HOSES TO FIGHT
 FIRES.
  
 7) PLEASE SHOW EMERGENCY LIGHTING
 EQUIPMENT IN STAIRWELLS AND NEW FLOOR
 LOCATIONS.
  
 8) PLEASE INDICATE PORTABLE FIRE
 EXTINGUISHERS.
  
 9) PLEASE INDICATE IF THE GARAGE IS
 SPRINKLER PROTECTED OR NOT.
  
 10) PLEASE SEE COMMON PATH OF TRAVEL
 NOTE BY BUILDING PLAN REVIEWER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-03 Cont ID  
Sent By dbaxter Date 2003-09-03 Time 15:41 Rev Time 0.00
Received By dbaxter Date 2003-09-03 Time 15:41 Sent To E
Notes
2003-09-03 00:00:00TO COMM BD #2.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-26 Cont ID  
Sent By sgraham Date 2003-08-29 Time 15:42 Rev Time 0.00
Received By dbaxter Date 2003-08-26 Time 13:27 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By hmoser Date 2003-09-23 Time 17:01 Rev Time 1.00
Received By hmoser Date 2003-09-23 Time 17:01 Sent To  
Notes
2003-09-23 00:00:00PLAN DENIED
 1) NO EQUIPMENT SPECIFICATIONS
 2) NEED CALCULATIONS FOR FRESH AIR
 3) NEED DUCT SIZES
 NEED MORE INFORMATION ON MECHANICAL
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-30 Cont ID  
Sent By kstevens Date 2003-09-30 Time 15:46 Rev Time 1.00
Received By kstevens Date 2003-09-30 Time 15:46 Sent To  
Notes
2003-09-30 00:00:00DENIED
 REFERENCE: FLORIDA ADMIN. CODE
  
 61G15-23.002(2) PLEASE SEE ELECTRICAL
 COMMENT #2 CONCERNING CERTIFICATE OF
 AUTHORIZATION REQUIRED BY FLORIDA
 STATUTES.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-29 Cont ID  
Sent By dbaxter Date 2003-08-26 Time 13:27 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***