Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-03 Cont ID  
Sent By hpiskura Date 2003-09-03 Time 14:10 Rev Time 0.00
Received By hpiskura Date 2003-09-03 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-28 Cont ID  
Sent By dpalmer Date 2003-10-28 Time 06:48 Rev Time 0.33
Received By dpalmer Date 2003-10-28 Time 06:48 Sent To  
Notes
2003-10-28 00:00:00ALL OLD/VOIDED SHEETS NEED TO BE REMOVED

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-09-08 Cont ID  
Sent By csiegber Date 2003-10-21 Time 15:39 Rev Time 0.50
Received By dpalmer Date 2003-09-08 Time 10:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-30 Cont ID  
Sent By mcarsill Date 2003-10-30 Time 16:37 Rev Time 0.00
Received By mcarsill Date 2003-10-30 Time 16:37 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-04 Cont ID  
Sent By mcarsill Date 2003-09-04 Time 16:24 Rev Time 0.00
Received By mcarsill Date 2003-09-04 Time 16:24 Sent To  
Notes
2003-09-04 00:00:001) FIRE ALARM NOTES # 13 IS INCORRECT.
 DUCT SMOKE DETECTORS SHALL CAUSE A
 BUILDING ALARM NOT A SUPERVISORY SIGNAL.
  
 2) SEPARATE PLANS REQUIRED FOR NEW
 FIRE ALARM EQUIPMENT.
  
 3) IF EXISTING OFFICE/BEDROOMS ARE
 BEING USED FOR SLEEPING PURPOSES, THEN
 ELECTRIC POWERED SMOKE DETECTORS ARE
 REQUIRED INSIDE AND OUTSIDE OF THEM.
 PLEASE ADVISE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-10-27 Cont ID  
Sent By mmclean Date 2003-10-29 Time 09:53 Rev Time 0.00
Received By csiegber Date 2003-10-21 Time 15:38 Sent To  
Notes
2003-10-21 00:00:00TO CMM BD#11

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-26 Cont ID  
Sent By dbaxter Date 2003-08-26 Time 10:58 Rev Time 0.00
Received By dbaxter Date 2003-08-26 Time 10:58 Sent To E
Notes
2003-08-26 00:00:00TO COMM. BD.#14.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-05 Cont ID  
Sent By pkrauss Date 2003-11-04 Time 16:57 Rev Time 0.45
Received By pkrauss Date 2003-11-04 Time 16:57 Sent To  
Notes
2003-11-04 00:00:00PROVISO:
 AS PER REVISION TO THE 2001 FBC(M) 601.4
 EFFECTIVE JUNE 30,2003:
 EXCEPTION:
 2. TRANSFER GRILLES SHALL USE 50 SQ INCH
 TO 100 CFM OF SUPPLY AIR WITH A 1 INCH
 UNRESTRICTED DOOR UNDERCUT.SOME OF THE
 TRANSFER GRILLES ARE INADEQUATE, PLEASE
 REVISE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-17 Cont ID  
Sent By pkrauss Date 2003-09-17 Time 07:02 Rev Time 0.45
Received By pkrauss Date 2003-09-17 Time 07:02 Sent To  
Notes
2003-09-17 00:00:00DENIED:
 PLEASE CLARIFYMECHANICAL ROOM 211.
 PLANS INDICATE AHU-3 PLENUM UNDER AHU.
 PLEASE INDICATE RETURN AIR DUCT &
 GRILLES FOR AHU-3 & AHU-2.PLANS DO
 NOT INDICATE HOW THE AIR WILL BE
 TRANSFERED FROM THE ADJOINING SPACE
 BACK TO AHU-2 & 3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-24 Cont ID  
Sent By pkrauss Date 2003-09-24 Time 11:22 Rev Time 0.00
Received By pkrauss Date 2003-09-24 Time 11:22 Sent To  
Notes
2003-09-24 00:00:00NO PLUMBING PLANS SUBMITTED FOR REVIEW

Review Stop Z ZONING
Rev No 1 Status P Date 2003-10-29 Cont ID  
Sent By mmclean Date 2003-10-29 Time 09:52 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-10-29 00:00:0010/29/03 OK DMP JUST INTERIOR WORK MM