Plan Review Details - Permit 03081504
Plan Review Stops For Permit 03081504
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-08 Cont ID  
Sent By jwitmer Date 2003-10-08 Time 15:27 Rev Time 1.11
Received By jwitmer Date 2003-10-08 Time 15:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-08-28 Cont ID  
Sent By jwitmer Date 2003-08-28 Time 14:02 Rev Time 1.50
Received By jwitmer Date 2003-08-28 Time 14:02 Sent To  
Notes
2003-08-28 00:00:00BUILDING PLAN REVIEW
 PERMIT:03081504
 ADD: 2901 OKEECHOBEE BLVD
 CONT: ROEPNACK CORP
 TEL: (954)444-2995
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 ACTION: DENIED
 1)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORT, SBCCI OR DADE COUNTY
 REPORT ARE ACCEPTED. MISSING REPORTS:
 A) ENTRY DOOR
 B) ROOFING ASSEMBLY
  
 3) 1707.4.3 EACH EXTERIOR DOOR
 ASSEMBLY NOT COVERED BY 1707.4.2
 (GLAZED DOORS) SHALL BE LISTED AND TEST-
 ED FOR A PERIOD EQUAL TO THE QUANITY
 3600/ V WHERE THE TIME PERIOD IS IN
 SECTIONS AND V IS IN MILES PER HR TAKEN
 FROM FIGURE 1606. THE TIME PERIOD SHALL
 ALSO INCLUDE A 10 SECOND PERIOD AT A
 LOAD EQUAL TO 1.5 TIMES THE DESIGN
 PRESSURE. DADE COUNTY & SBCCI REPORTS
 ARE ACCEPTED.
  
 4)1707.4.4.1 ANCHOR REQUIREMENTS:
 WINDOW & DOOR ASSEMBLIES SHALL BE ANCHOR
 ED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER'S RECOMMENDATIONS TO
 ACHIEVE THEDESIGN PRESSURE SPECIFIED.
 SUBSTITUTE ANCHORING SYSTEM USED FOR
 THE SUBSTRATE NOT SPECIFIED BY THE
 FENESTRATION MANUFACTURER SHALL PROVIDE
 EQUAL OR GREATER ANCHORING AS DEMONSTRA-
 TED BY ACCEPTED ENGINEERING PRACTICES.
  
 5)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 THE ROOF FRAMING PLAN INDICATES THE USE
 OF 3/4" A. B. @ 30" O. C., THERE IS NO
 LENGHT GIVEN?
  
 6)1511.7 ROOF MOUNTED MECHANICAL UNIT
 S SHALL BE MOUNTED ON CURBS RAISED A
 MINIMUM OF 8 INCHES ABOVE THE ROOF SUR-
 FACE, OR WHERE ROOFING MATERIALS EXTEND
 BENEATH THE UNIT, ON RAISED EQUIPMENT
 SUPPORTS PROVIDING A MINIMUM CLEARENCE
 HEIGHT IN ACCORDANCE WITH TABLE 1511.7.
 MECH. 301.13 WIND RESISTANCE
 MECHANICAL EQUIPMENT, APPLIANCES AND SUP
 PORTS THAT ARE EXPOSED TO WIND SHALL BE
 DESIGNED AND INSTALLED TO RESIST THE
 WIND PRESSURES ON THE EQUIPMENT & THE
 SUPPORTS AS DETERMINED IN ACCORDANCE
 WITH THE FL BLD CODE. THIS MAY BE ACCOMP
 LISHED BY DESIGN OR BY APPLICATION OF
 SECTION 301.13.1.
 NO INFORMATION ON THE ROF TOP EXHAUST
 FAN?
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-10-10 Cont ID  
Sent By dpalmer Date 2003-10-10 Time 07:19 Rev Time 0.50
Received By dpalmer Date 2003-10-10 Time 07:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-02 Cont ID  
Sent By dpalmer Date 2003-09-02 Time 19:18 Rev Time 1.50
Received By dpalmer Date 2003-09-02 Time 19:18 Sent To  
Notes
2003-09-02 00:00:00************** UNSAT **************
  
 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR
 INFORMATION REQ'DON TITLE BLOCK.
 PLEASE PROVIDE CERTIFICATE/AUTH #.
  
 2)NOTE: PLANS NOTE ON AES-2 TO SEE RISER
 FOR SERV. BAY BLDG? PLEASE CLARIFY
 WHERE THIS RISER IS SHOWN?
 215.5
  
 3)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125% PER 215.3, 230.42 ETC.
  
 PLEASE NOTE:: AS PER LOCAL AMENDMENTS:
 COLOR CODING OF FEEDERS FOR 277/480V
 IS BR/PURP/YELLOW.215 LOCAL.
 JUSTA NOTE;NOT REQ'D ON THIS SYSTEM
 BEING 120/208V
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-10-09 Cont ID  
Sent By mcarsill Date 2003-10-09 Time 17:34 Rev Time 0.00
Received By mcarsill Date 2003-10-09 Time 17:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2003-09-05 Cont ID  
Sent By mcarsill Date 2003-09-05 Time 16:10 Rev Time 0.00
Received By mcarsill Date 2003-09-05 Time 16:10 Sent To  
Notes
2003-09-05 00:00:001) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2000 LIFE SAFETY DOOR.
  
 2) PLEASE PROVIDE SIGNS ON EXTERIOR
 OF DOORS OF DURABLE CONSTRUCTION,
 ELECTRICAL ROOM, NO STORAGE ALLOWED
 BY ORDER OF THE FIRE MARSHAL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 12:18 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 12:18 Sent To  
Notes
2003-09-30 00:00:00TO COMM BD#33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-26 Cont ID  
Sent By csiegber Date 2003-08-26 Time 09:55 Rev Time 0.00
Received By csiegber Date 2003-08-26 Time 09:54 Sent To  
Notes
2003-08-26 00:00:00TO COMM BD #35

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-14 Cont ID  
Sent By pkrauss Date 2003-10-14 Time 13:05 Rev Time 0.55
Received By pkrauss Date 2003-10-14 Time 13:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-24 Cont ID  
Sent By pkrauss Date 2003-09-24 Time 07:45 Rev Time 0.35
Received By pkrauss Date 2003-09-24 Time 07:43 Sent To  
Notes
2003-09-24 00:00:00DENIED:
 PLEASE CLARIFY AIR MAKE UP FOR THE
 ELECTRICAL ROOM.PLAN SHEET AM-1
 INDICATES AN EXHAUST FAN RATED AT 400
 CFM, INDICATE WHERE THE MAKE-UP AIR
 WILL BE PROVIDED.PLAN SHEET A.A-1
 DOES NOT INDICATE ANY LOUVERED DOORS
 OR LOUVERS TO ACCOMMODATE FOR THE AIR
 MAKE UP.
  
 SEE ALSO COMMENT BY BUILDING, HEIGHT
 REQUIREMENT FOR THE CURB TO THE EXHAUST
 FAN.

Review Stop P PLUMBING
Rev No 1 Status P Date 2003-09-29 Cont ID  
Sent By kstevens Date 2003-09-29 Time 09:58 Rev Time 0.50
Received By kstevens Date 2003-09-29 Time 09:58 Sent To  
Notes
2003-09-29 00:00:00ROOF DOWNSPOUT AND SCUPPER OK - NO PLUM.
 PERMIT REQUIRED