Plan Review Details - Permit 03081490
Plan Review Stops For Permit 03081490
Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-25 Time 16:08 Rev Time 0.00
Received By csiegber Date 2003-08-25 Time 16:08 Sent To M
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2003-09-03 Cont ID  
Sent By pkrauss Date 2003-09-03 Time 10:55 Rev Time 0.30
Received By pkrauss Date 2003-09-03 Time 10:55 Sent To  
Notes
2003-09-03 00:00:00PROVISO:
 PLEASE NOTE THE FOLLOWING REVISION TO
 THE 2001 FBC(M) EFFECTIVE JUNE 30,2003:
  
 2001 FBC(M) 601.4
 BALANCE AIR RETURN - RETURN TRANSFER
 SHALL BE 1 1/2 TIMES THE CROSS SECTIONAL
 AREA (SQ INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM IT'S SERVING & THE
 DOOR HAVING AN UNRESTRICTED 1" UNDERCUT.
  
 ALL SUPPLY AIR INTO THE MASTER SUITE
 SHALL BE INCLUDED.
  
 A MINIMUM CLEARANCE OF 4" IS REQUIRED
 AROUND THE AIR HANDLER AS PER 2001
 FBC(M)603.1.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.