Review Stop P PLUMBING
Rev No 2 Status P Date 2003-09-06 Cont ID  
Sent By kstevens Date 2003-09-06 Time 17:46 Rev Time 0.50
Received By kstevens Date 2003-09-06 Time 17:46 Sent To  
Notes
2003-09-06 00:00:00 
  
  
  
  
 PER N. MELICK MANUFACTURE INFO
 NOT REQUIRED FOR 1 & 2 FAMILY HOMES.
 JULY 17, 2002 OFFICAL INTERPRETATION.
 THE FIELD INSPECTOR SHALL VERIFY THE
 INSTALLED EQUIPMENT INPUT DOES NOT EX-
 CEED THE PIPE SIZING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-08-23 Cont ID  
Sent By alange Date 2003-08-21 Time 12:44 Rev Time 1.00
Received By kstevens Date 2003-08-23 Time 13:45 Sent To  
Notes
2003-08-23 00:00:00DENIED
 REFERENCE: FBC-2001 FUEL GAS
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2001
 FUEL GAS CODE.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES.
 - CSST NOT APPROVED FOR EXTERNAL GAS
 PIPING PER SECTION 403.2.4.5 -
 3. TYPE OF GAS, (LP OR NATURAL)
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2001 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 REVIEW BY KEN STEVENS