Plan Review Details - Permit 03081163
Plan Review Stops For Permit 03081163
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2004-06-01 Cont ID  
Sent By shill Date 2004-06-01 Time 17:04 Rev Time 1.00
Received By shill Date 2004-06-01 Time 17:04 Sent To  
Notes
2004-06-01 00:00:00REVISION

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2004-05-04 Cont ID  
Sent By shill Date 2004-05-04 Time 12:30 Rev Time 2.00
Received By shill Date 2004-05-04 Time 12:30 Sent To  
Notes
2004-05-04 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST.ALL CORRECTIONS
 STILL APPLY.
  
 2.)REGARDING REVIEW OF CERTIFICATE
 OF COMPLIANCE FOR FLEMING DOOR:
 THE PAPERWORK SUBMITTED IS NOT A TEST
 REPORT (ONLY REFERS TO TEST REPORTS)
 AS REQUIRED BY FBC1703.ALSO THE TEST
 STANDARDS USED ARE NOT THE STANDARDS
 REFERRED TO IN FBC CHAPTER 35.
  
 3.)NOTE THAT THIS DOOR WAS TESTED TO
 AN IMPACT STANDARD.MY UNDERSTANDING
 IS THAT ONE DOOR WAS IMPACT, THE OTHER
 DOOR WAS NON IMPACT.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2004-04-27 Cont ID  
Sent By shill Date 2004-04-27 Time 11:27 Rev Time 1.00
Received By shill Date 2004-04-27 Time 11:27 Sent To  
Notes
2004-04-27 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 SUBMITTED WERE:
 2 SETS OF PLANS DATED 4/5/04
 TWO STORM PANEL SBCCI REPORTS
 TWO COPIES OF NOA 02-0523.06, INCOMPLE
 TWO COPIES OF INCOMPLETE NOA02-0523.07
 AND DATA SHEETS
 TWO COPIES OF LETTER DATED 4/19
  
 1.)THE ILLEGIBLE PARTIAL NOA
 SUBMITTED 02-0523.07 IS FOR AN INSWING
 DOOR.PER CONTRACTOR'S REP, ONLY
 OUTSWING DOORS ARE TO BE INSTALLED.
 EITHER SUBMIT THE CORRECT PRODUCT
 APPROVAL OR REVISE THE PLAN.ALSO THIS
 DOOR IS NOT FOR AREAS REQUIRING WATER
 INFILTRATION.ALSO THIS DOOR IS NOT
 A GLAZED DOOR.ALSO THE PRODUCT
 APPROVAL DOES NOT INCLUDE SIDELITES.
 HAVE THE DOOR PRODUCT APPROVALS
 APPROVED BY HISTORIC BEFORE RESUBMITTAL
 TO AVOID CONFUSION.
 THIS COMMENT IS THE SAME AS THE PREVIOUS
 LIST, ITEMS 2, 3, 4, 5, AND 6.
  
 2.)THE OTHER NOA SUBMITTED IS ALSO
 A PARTIAL ILLEGIBLE TEST REPORT.THIS
 IS THE SAME ONE SUBMITTED PREVIOUSLY
 AND DOES NOT INCLUDE SIDELITES AND IS
 RESTRICTED TO 100 SQUARE INCHES OF
 LEXAN, NOT FULLY GLAZED AS DESCRIBED.
  
 3.)THE LETTER SENT INDICATES THAT A
 SHUTTER WILL BE INSTALLED OVER BOTH
 DOORS.ONE IS NOT TO HAVE A SHUTTER
 TO COMPLY WITH FBC1005.4.5 AS DISCUSSED.
 THE LETTER STATES THAT ROLL DOWN
 SHUTTERS WILL BE INSTALLED.PRODUCT
 APPROVALS FOR STORM SHUTTERS ONLY HAVE
 BEEN SUBMITTED.
  
 4.)I HAVE SPOKEN WITH THE
 TECHNICAL REPRESENTATIVE FROM FLEMING
 DOORS TO ATTEMPT TO ASSIST YOU IN
 OBTAINING THE CORRECT PAPERWORK FOR
 THE PRODUCT YOU WOULD LIKE TO INSTALL.
 THE TEST REPORT FOR THE DOOR YOU HAVE
 DESCRIBED TO BE IS A UL REPORT (FRENCH
 DOORS WITH SIDELITES).FOR THE FULLY
 GLAZED SINGLE DOOR, THE TEST REPORT WILL
 BE AVAILABLE MID MAY.ADDRESS.
  
 5.)WHEN SUBMITTING THE PLANS WITH THE
 TEST REPORT, SUBMIT AS A SUBMITTAL (NO
 FEE), NOT A REVISION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2004-04-19 Cont ID  
Sent By alange Date 2004-04-22 Time 12:12 Rev Time 2.00
Received By shill Date 2004-04-12 Time 17:33 Sent To  
Notes
2004-04-12 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)ONE MEANS OF ESCAPE DURING A
 HURRICANE IS TO BE PROVIDED, FBC1005.4.5
 THIS MEANS OF ESCAPE CANNOT BE THROUGH
 A GARAGE.BASED ON A CONVERSATION WITH
 THE CONTRACTOR, ALL EXTERIOR DOORS ARE
 BEING REPLACE WITH GLAZED DOORS
 REQUIRING IMPACT PROTECTION.
  
 2.)THE PRODUCT APPROVAL SUBMITTED
 DOES NOT INCLUDE THE SIDELITES OR
 MULLIONS.THE PRODUCT APPROVAL FOR THE
 OUTSWING DOOR IS LIMITED TO 100 SQ IN
 OF LEXAN (NOT A FULLY GLAZED DOOR), AND
 SIDELITES AND MULLIONS ARE NOT A PART
 OF THE APPROVAL.
  
 3.)IN MY CONVERSATION WITH JAY
 LAWRENCE, HE INDICATED THAT THE DOORS
 ARRIVE WITHOUT GLASS AND WILL BE GLAZED
 ON SITE.THIS DESCRIPTION DOES NOT
 MATCH THE PRODUCT APPROVALS SUBMITTED.
  
 4.)THE PRODUCT APPROVALS ARE
 ILLEGIBLE.ALSO, TWO COPIES ARE NEEDED
 OF THE SAME PRODUCT APPROVAL.ONE WAS
 FOR INSWING, ONE WAS OUTSWING.THE
 PLAN SHOWS OUTSWING ONLY.THE PRODUCT
 APPROVALS ARE TO BE LEGIBLE AND ON
 GOOD QUALITY PAPER.ONE WAS SUBMITTED
 ON THERMAL FAX PAPER.
  
 5.)FYI, THE INSWING DOOR IS NOT FOR
 USE WHERE WATER INFILTRATION
 REQUIREMENTS ARE NEEDED.HOWEVER,
 APPARENTLY THIS PRODUCT APPROVAL WAS
 SUBMITTED IN ERROR.
  
 6.)HAVE THE PRODUCTS APPROVED BY
 HISTORIC BEFORE RESUBMITTAL.
  
 7.)AS DISCUSSED, THE PRODUCT APPROVALS
 FOR THE WINDOWS WILL BE VOIDED AS NO
 WINDOWS ARE BEING REPLACED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2004-03-11 Cont ID  
Sent By csiegber Date 2004-04-06 Time 15:51 Rev Time 1.00
Received By shill Date 2004-03-11 Time 13:41 Sent To  
Notes
2004-03-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)HISTORIC APPROVAL REQUIRED.
  
 2.)CHANGES TO THE PLAN CAN ONLY BE
 DONE BY THE DESIGNER OF RECORD.
  
 3.)THE PRODUCT APPROVALS ARE
 INCOMPLETE.THEY APPEAR TO BE THE
 DRAWINGS ASSOCIATED WITH A DADE COUNTY
 NOA.PROVIDE COMPLETE PRODUCT
 APPROVALS.
  
 4.)PROVIDE PRODUCT APPROVALS FOR THE
 SIDELITES AND MULLIONS, IF YOU ARE
 USING MULLIONS TO JOIN THE DOOR AND
 SIDELITES.THE PRODUCT APPROVAL
 SUBMITTED ARE FOR A DOOR WITH THE
 SIDELITES.IF YOU ARE USING A DOOR
 FROM ANOTHER MANUFACTURER, THIS IS NOT
 COVERED UNDER THE PRODUCT APPROVAL
 SUBMITTED.
  
 5.)IMPACT PROTECTION REQUIRED, SUBMIT
 SHUTTER PRODUCT APPROVALS.
  
 6.)PROVIDE DESIGN PRESSURES FOR THE
 OPENING.
  
 7.)FLORIDA ARCHITECT LICENSE REQUIRED
 TO PRACTICE ARCHITECTURE.
  
 8.)PROVIDE A VALUE FOR THE NEW SCOPE
 OF WORK.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-10-06 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:16 Rev Time 1.00
Received By sthyng Date 2003-10-06 Time 09:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-23 Cont ID  
Sent By pkrauss Date 2003-10-03 Time 06:54 Rev Time 0.50
Received By sthyng Date 2003-09-23 Time 09:57 Sent To  
Notes
2003-09-23 00:00:00*****CORRECTIONS******
  
 1.)SHOW THE NEW ENTRY TO THE GARAGE
 AND NEW STEPS AS PROPOSED ON THE PLAN.
  
 2.)PROVIDE A STRUCTURAL DETAIL FOR THE
 STAIRS.
  
 SAMANTHA THYNG, BUILDING PLANS EXAMINER
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-12-18 Cont ID  
Sent By btrobaug Date 2003-12-18 Time 11:25 Rev Time 0.75
Received By btrobaug Date 2003-12-18 Time 10:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:12 Rev Time 0.33
Received By btrobaug Date 2003-09-30 Time 15:27 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:25 Rev Time 0.50
Received By btrobaug Date 2003-08-25 Time 13:24 Sent To P
Notes
2003-08-25 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE NECESSARY CHANGES TO
 PLANS AND RESUBMIT FOR REVIEW.
  
 1} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210-52C 1,2,3,4,AND 5.
  
 2} CHANGES TO PLANS MUST BE MADE BY THE
 DESIGN PROFESSIONAL.( AIR HANDLER
 RELOCATION).
  
 3} PLEASE NOTE THAT ALL PLANS
 THAT ARE SIGNED AND SEALED BY ARCH/ OR
 ENGINEER ARE REQ`D PER 61G15-23.002 FOR
 ENGINEER AND 61G1-16.004 FOR ARCH.
 SHALL HAVE A TITLE BLOCK.SEE FAC FOR
 REQUIREMENTS ON THE TITLE BLOCK.
  
 4} PLEASE INDICATE WHERE THE PANEL IS TO
 BE RELOCATED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2004-05-25 Cont ID  
Sent By shill Date 2004-05-25 Time 14:16 Rev Time 0.00
Received By shill Date 2004-05-25 Time 14:16 Sent To  
Notes
2004-05-25 00:00:00TO SMH DESK - OLD PACKAGE BROUGHT BACK
 IN

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2004-04-22 Cont ID  
Sent By alange Date 2004-04-22 Time 12:12 Rev Time 0.00
Received By alange Date 2004-04-22 Time 12:12 Sent To B
Notes
2004-04-22 00:00:00TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2004-04-06 Cont ID  
Sent By csiegber Date 2004-04-06 Time 15:51 Rev Time 0.00
Received By csiegber Date 2004-04-06 Time 15:51 Sent To B
Notes
2004-04-06 00:00:00TO SH DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2004-02-27 Cont ID  
Sent By csiegber Date 2004-02-27 Time 14:16 Rev Time 0.00
Received By csiegber Date 2004-02-27 Time 14:16 Sent To B
Notes
2004-02-27 00:00:00TO SH DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-12-17 Cont ID  
Sent By csiegber Date 2003-12-17 Time 16:10 Rev Time 0.00
Received By csiegber Date 2003-12-17 Time 16:08 Sent To E
Notes
2003-12-17 00:00:00TO BT DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-09-30 Cont ID  
Sent By csiegber Date 2003-09-30 Time 08:24 Rev Time 0.00
Received By csiegber Date 2003-09-30 Time 08:24 Sent To E
Notes
2003-09-30 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-21 Cont ID  
Sent By alange Date 2003-08-21 Time 10:04 Rev Time 0.00
Received By alange Date 2003-08-21 Time 10:04 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-10-03 Cont ID  
Sent By pkrauss Date 2003-10-03 Time 06:54 Rev Time 0.20
Received By pkrauss Date 2003-10-03 Time 06:54 Sent To B
Notes
2003-10-03 00:00:00AHU MOVED CONNECTING TO EXISTING
 DUCTWORK IN THE ATTIC.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-15 Cont ID  
Sent By btrobaug Date 2003-09-30 Time 15:40 Rev Time 0.25
Received By pkrauss Date 2003-09-15 Time 08:11 Sent To B
Notes
2003-09-15 00:00:00DENIED:
 PLEASE INDICATE SIZE OF DUCTWORK BEING
 ADDED DUE TO THE RELOCATION OF THE
 AHU.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 1 Status N Date 2003-09-06 Cont ID  
Sent By btrobaug Date 2003-08-25 Time 16:55 Rev Time 0.25
Received By kstevens Date 2003-09-06 Time 14:00 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2004-04-14 Cont ID  
Sent By mmclean Date 2004-04-14 Time 14:50 Rev Time 0.00
Received By mmclean Date 2004-04-14 Time 14:50 Sent To B
Notes
2004-04-14 00:00:00GIVEN TO SAMANTHA HILL MM