Plan Review Details - Permit 03081161
Plan Review Stops For Permit 03081161
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2005-03-25 Cont ID  
Sent By alange Date 2005-03-25 Time 09:52 Rev Time 0.33
Received By alange Date 2005-03-25 Time 09:52 Sent To  
Notes
2005-03-25 00:00:00DOORS PRODUCT APPROVAL SUBMITTALS OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2003-11-26 Cont ID  
Sent By lmartine Date 2003-11-26 Time 14:20 Rev Time 2.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2003-09-03 Cont ID  
Sent By hpiskura Date 2003-09-03 Time 10:03 Rev Time 0.00
Received By hpiskura Date 2003-09-03 Time 10:03 Sent To  
Notes
2003-09-03 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-11-03 Cont ID  
Sent By dpalmer Date 2003-11-03 Time 11:40 Rev Time 1.00
Received By dpalmer Date 2003-11-03 Time 11:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2003-09-10 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 13:20 Rev Time 1.50
Received By dpalmer Date 2003-09-10 Time 07:00 Sent To  
Notes
2003-09-10 00:00:00*********** UNSAT *****************
  
 1)NOTE: PLEASE SEE COPIES OF BOTH FAC`S
 ATTACHED, 61G15-23.002 FOR ENGINEERS AND
 61G1-16.004 FOR ARCHS. PER FS`S 471 AND
 481. PLEASE SEE MISSING LICENSE #`S
 REQUIRED ON TITLE BLOCKS FOR DESIGNERS
 OF RECORD, INCLUDING ANY FIRM LICENSE
 #'S AND/OR CERTIFICATE OF AUTHORIZATION
 #'S ALSO. PLEASE SEE THAT THIS WILL BE
 REQ'D ON AL SHEETS WHEN SUBMITTTING
 PLANS FOR PERMIT AND SUBMITTED FOR
 RECORD.
  
 2)NOTE: PLEASE SEE THAT PLANS SHOW
 REFERENCE TO THE 1999 NEC. PLEASE NOTE:
 WE ARE NOW UNDER THE 2002 NEC AS OF
 JULY 1ST, 2003. PLEASE ADJUST.
  
 3)NOTE: PLEASE CLARIFY ON E-2, DATA/ELEC
 RM APPEARS TO SHOW A TRANSFORMER ON FLR
 LAYOUT? PLEASE NOTE . THIS IS NOT SHOWN
 ON RISER AND MAY JUST BEMISPRINT?
  
 4)NOTE: PLEASE SEE NOTES TO GROUNDING
 ELECTRODE CONNECTIONS ON RISER, MENTIONS
 ATTACHED TO BLDG STEEL. PLEASE CLARIFY
 THIS AS ACTUALLY BEING FOOTER STEEL AS
 REQUIRED UNDER 250.50.
 PLEASE NOTE: ANY "BUILDING STEEL" MUST
 ALSO BE A POINT OF ATTACHMENT DEPENDING
 ON BLDG CONSTRUCTION TYPE.
  
 5)NOTE: PLEASE CLARIFY LOADS FOR TRACK
 LIGHTING. PLEASE SHOW IN LOAD CALCS
 OR BY NOTE THAT TRACK LIGHTING FIGURED
 PER 220.12B
  
 6)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 NEW MDP AND PANELS. IT IS NOTED THAT
 PANELS REFERENCE :NOTE 9: HOWEVER THIS
 IS REQUIRED AT TIME OF PLAN REVIEW AND
 APPLICATION FOR PERMIT. 110.9/ 215.5
  
 7)NOTE: PLEASE SEE THAT THIS IS JUST A
 NOTE: MDP SHOWS 100A OCP FOR SUB PANELS
 AND 3/0'S FOR CONDUCTOR SIZE ON RISER.
 IT IS UNDERSTOOD THAT THERE IS NO NEC
 VIOLATION FOR INSTALLING LARGER CONDUCT-
 ORS THAN REQ'D FOR MIN, HOWEVER, IT IS
 THE BEST OF MY KNOWLEDGE THAT 100A BRKR
 WILL ONLY ACCEPT UP TO 1/0'S?
 THIS IS JUST A NOTE AND IF 3/0'S ARE
 SHOWN THEN THEY WILL BE REQ'D TO BE
 INSTALLED. (MAC ADAPTERS) ETC. MAY BE
 USED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW WITH THE EXCEPTION OF NOTE:7.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2003-11-26 Cont ID  
Sent By mamini Date 2003-11-26 Time 15:05 Rev Time 1.00
Received By mamini Date 2003-11-26 Time 15:04 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2003-11-07 Cont ID  
Sent By mamini Date 2003-11-07 Time 09:26 Rev Time 1.00
Received By mamini Date 2003-11-07 Time 09:25 Sent To  
Notes
2003-11-07 00:00:00FAILED:
 1. PLEASE NOTE THATA SEPARATE PERMIT
 APPLICATION AND FEES FOR "UNDERGROUND
 UTILITIES AND SITE WORK " PERMIT IS
 REQUIRED, SUBMIT TWO SETS OF CIVIL PLANS
 ONLY SIGNED AND SEALED.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2003-08-28 Cont ID  
Sent By mamini Date 2003-08-28 Time 14:17 Rev Time 1.00
Received By mamini Date 2003-08-28 Time 14:16 Sent To  
Notes
2003-08-28 00:00:00FAILED:
 1. PLEASE NOTE THAT A SEPARATE PERMIT
 APPLICATION AND FEES FOR UNDERGROUND
 UTILITIES AND SITE WORK IS REQUIRED,
 PLEASE SUBMIT CIVIL PLANS SIGNED AND
 SEALED ONLY.
 2. PLEASE PROVIDE STORM WATER
 CALCULATION FOR OUR REVIEW AND APPROVAL,
 STORM WATER MUST BE DESIGNED PER CITY
 OF WEST PALM BEACH CRITERIA.
 3. PLEASE PROVIDE A COPY OF THE SFWMD
 PERMIT DUE TO THE PROPOSED PROJECT.
 4. PLEASE NOTE THAT ALL PARKING STALLS
 MUST BE PAINTED WITH DOUBLE 4" WIDE
 WHITE STRIPING PAINT, PER CITY OF WPB
 REQUIREMENT.
 IF ANY QUESTION PLEASE CONTACT 805-6723
 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-11-04 Cont ID  
Sent By mcarsill Date 2003-11-04 Time 16:00 Rev Time 0.00
Received By mcarsill Date 2003-11-04 Time 16:00 Sent To  
Notes
2003-11-04 00:00:001) NOTE # 1 ON C-5 SHOULD BE REMOVED
 FROM THE DRAWINGS SINCE NO FIRE
 LANE SIGNS ARE PLANNED FOR THE SITE.
  
 2) LOCKING DEVICES ON EXIT DOORS SHALL
 COMPLY WITH EITHER DELAYED EGRESS OR
 ACCESS CONTROLLED EGRESS PER CHAPTER
 7 OF THE LSC, 2000 EDITION.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2003-09-05 Cont ID  
Sent By mcarsill Date 2003-09-05 Time 16:13 Rev Time 0.00
Received By mcarsill Date 2003-09-05 Time 16:13 Sent To  
Notes
2003-09-05 00:00:001) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
  
 2) SUITABLE ROADS ARE TO BE PROVIDED
 DURING CONSTRUCTION FOR FIRE AND
 PARAMEDICAL EQUIPMENT.
  
 3) PLEASE INDICATE LOCATIONS OF ALL
 EXISTING OR NEW FIRE HYDRANTS.
  
 4) NOTE # 1 ON C-5 INDICATES WORDING
 FOR FIRE LANE(S). PLEASE INDICATE
 LOCATIONS OF THESE SIGNS.
  
 5) CODES NOTES ON G-1 INDICATES THAT
 THE BUILDING WILL BE FIRE SPRINKLER
 PROTECTED BUT THE F.D. NOTES ON SAME
 PAGE INDICATES THE BUILDING IS NON
 FIRE SPRINKLER PROTECTED. PLEASE
 CLARIFY.
  
 6) MAGLOCKS NOTED ON VESTIBULE ENTRY
 DOORS ON PAGE C-5. PLEASE EXPLAIN
 OBVIOUS PURPOSE AND FUNCTION.
  
 7) BUILDING ADDRESS LOCATION COULD NOT
 BE SEEN ON ELEVATION DRAWING. BUILDING
 ADDRESS IS REQUIRED TO BE 6" HIGH.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATIONS FOR WALLS AND CEILINGS.
  
 9) FIRE EXTINGUISHER(S) ARE MENTIONED
 DURING CONSTRUCTION BUT COULD NOT BE
 SEEN ON THE FINISHED FLOOR PLAN.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2005-03-02 Cont ID  
Sent By adarroug Date 2005-03-02 Time 15:47 Rev Time 0.00
Received By adarroug Date 2005-03-02 Time 15:47 Sent To B
Notes
2005-03-02 00:00:00TO LMARTINEZ DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status   Date 2003-10-31 Cont ID  
Sent By lsmith Date 2003-10-31 Time 12:31 Rev Time 0.00
Received By lsmith Date 2003-10-31 Time 12:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-27 Cont ID  
Sent By dbaxter Date 2003-08-27 Time 13:19 Rev Time 0.00
Received By dbaxter Date 2003-08-27 Time 13:19 Sent To E
Notes
2003-08-27 00:00:00TO COMM BD. NO. 43.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-20 Cont ID  
Sent By mmclean Date 2003-08-27 Time 10:46 Rev Time 0.00
Received By csiegber Date 2003-08-20 Time 16:31 Sent To Z
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-11-18 Cont ID  
Sent By pkrauss Date 2003-11-18 Time 13:20 Rev Time 0.35
Received By pkrauss Date 2003-11-18 Time 13:20 Sent To  
Notes
2003-11-18 00:00:00PROVISO:
 DUCT SMOKE DETECTOR SHALL BE INSTALLED
 IN THE SUPPLY AIR DUCT AS PER 2001 FBC,
 MECHANICAL 606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2003-09-28 Cont ID  
Sent By pkrauss Date 2003-09-28 Time 14:23 Rev Time 0.55
Received By pkrauss Date 2003-09-28 Time 14:23 Sent To  
Notes
2003-09-28 00:00:00DENIED:
 1. HEIGHT REQUIREMENT FOR THE CONDENSING
 UNIT STAND & CURBS FOR THE RTU'S SHALL
 COMPLY WITH 2001 FBC 1511.7.
  
 2. PLEASE NOTE THE LOCATION OF C.U. 1
 IN RESPECT TO THE O.A. INTAKE OF THE
 RTU.
  
 3.PLAN SHEET P-3 DETAIL F10, INDICATES
 CONDENSATE TERMINATING ON TO SPLASH
 BLOCK.CONSENSATE SHALL TERMINATE AS
 NOT TO CREATE A NUISANCE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-11-26 Cont ID  
Sent By pschmitz Date 2003-11-26 Time 08:27 Rev Time 1.50
Received By lmartine Date 2003-11-26 Time 08:27 Sent To B
Notes
2003-11-26 00:00:00NSF SHT ATTACHED.
 APPROVED BY PAUL SCHMITZ ON 11/25/03 SEE
 PLANS FOR HIS SIGNATURELM

Review Stop P PLUMBING
Rev No 1 Status F Date 2003-09-24 Cont ID  
Sent By kstevens Date 2003-09-24 Time 17:00 Rev Time 1.50
Received By kstevens Date 2003-09-24 Time 17:00 Sent To  
Notes
2003-09-24 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMIN. CODE
 W.P.B. CITY CODE
  
 1) SHTS C-4 & IR-1. C-4 CALLS OUT A
 WATER METER AND AN RPBF, BUT IR-1 CALLS
 OUT A WELL AND PUMP. PLEASE CLAIRFY.
 SECTION 104.2.1.
 2) SHT A-10.7 DETAIL G10 CANOPY SCUPPER
 DRAIN. INDICATE THE HEIGHT OF SCUPPER
 DETAIL. SEC 104.2.1.
 3) SHT A-10.7 SUBMIT CALCULATIONS FOR
 PRIMARY AND SECONDARY ROOF DRAINS PER
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 SHOW ADDED SF FOR ALL VERTICAL WALLS IN-
 CLUDING PARAPET. SHOW ALL ADD SF FOR ALL
 ROOF THAT DRAIN ONTO THE ROOF FROM ABOVE
 4) SUBMIT A STORM RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND SF AS IT ACCUMULATES.
 SECTION 104.2.1.
 5) SHT P-3 DETAIL A6. CONDENSATE SHALL
 NOT DRAIN INTO THE SANITARY SEWER SYSTEM
 SEC 90-125(5) WPB CITY CODE. CONDENSATE
 SHALL DRAIN SEPARATELY OUT OF BLDG. AND
 TIE INTO A CATCH BASIN, DRYWELL OR STORM
 LINE. A RELIEF VENT IS REQUIRED ON COND.
 LINE AS IT EXITS THE BLDG.
 6) SUBMIT A CONDENSATE A CONDENSATE
 RISER DIAGRAM. 104.2.1.
 7) SHT P-3 DETAIL A10, WATER FILTER TO
 BE NSF CERTIFIED. SUBMIT MANUF. SPECIFI-
 CATION SHEETS.
 8) 61G15-23.002(2) ENGINEERS SHALL LEG-
 IBLY INDICATE THEIR NAME, ADDRESS AND
 LICENSE NUMBER ON EACH SHEET. IF PRACT-
 ICING THROUGH A DULY AUTHORIZED ENGIN-
 EERING BUSINESS, CERTIFICATE OF AUTHOR-
 IZATION NUMBER IS REQUIRED.
 9) LANDSCAPE/IRRIGATION SHEETS. THE PER-
 SONAL SEAL, SIGNATURE AND DATE OF THE
 ARCHITECT SHALL APPEAR ON ALL SHEETS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-27 Cont ID  
Sent By csiegber Date 2003-08-20 Time 16:34 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
***NONE***