Plan Review Details - Permit 03081098
Plan Review Stops For Permit 03081098
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2004-03-12 Cont ID  
Sent By jgomez Date 2004-03-12 Time 09:38 Rev Time 0.50
Received By jgomez Date 2004-03-12 Time 09:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2003-09-09 Cont ID  
Sent By csiegber Date 2004-03-04 Time 16:44 Rev Time 1.50
Received By jgomez Date 2003-09-09 Time 14:50 Sent To PC
Notes
2003-09-09 00:00:00BUILDING CHECKLIST:
 1-PROVIDE ENERGY CALCULATIONS AS REQ'D.
 SEC. 101.2.2 CHAPTER 13 FBC 2001.
 2-PROVIDE FLOOR PLAN TO SCALE AND WITH
 DIMENSIONS. IDENTIFY ROOM TO BE USED
 FOR WHAT PURPOSE. SLEEPING, DINING OR
 FAMILY AREA. AND IDENTIFY ROOM
 ADJACENT TO THIS ROOM TO VERIFY EGRESS
 FOR BEDROOMS. SEC. 1005.4 FBC 2001.
 3-SPECIFY DESIGN CRITERIA AS REQUIRED
 BY SEC. 1606.1.7 FBC 2001.
 4-PROVIDE DETAILS AND SPECS FOR FRAMING
 FOR EXTERIOR DOORS AND WINDOWS. AND TO
 PROVIDE REINFORCING TO RECEIVE STORM
 SHUTTERS. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-FINISH FLOOR LEVEL NEED TO BE 4" MIN.
 ABOVE FINISH GRADE. SEC. 1804.1.7 CITY
 AMENDMENTS TO FBC 2001.
 6-CLARIFY HOW IS THE 5" CONCRETE RETURN
 WALL ATTACHED TO THE SLAB. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-SPECIFY CONNECTION OF 2X4 TO CONCRETE
 COLUMNS AND AT THE ENDS OF WALL. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 8-SPECIFY CONNECTION AT TOP AND BOTTOM
 OF WALL.SEC. 104.2.1.2 CITY AMENDMENTS
 9-NEED 2X4 PRESSURE TREATED SILL AT
 BOTTOM OF WALL. SEC. 104.2.1.2.
 10-SPECIFY PLYWOOD THICKENSS AND NAIL
 TYPE AND SPACING. SEC. 2306 CITY
 AMENDMENTS TO FBC 2001.
 11-STUCCO TO BE 7/8" MIN. THICKNESS.
 AS REQUIRED BY ASTM C-926.
 12-SPECIFY INSULATION IN ROOF AND WALL.
 13-CLARIFY IF SPACE IS GOING TO BE
 AIR CONDITIONED. OTHERWISE, ENOUGH
 WINDOW AREA NEED TO BE CALCULATED TO
 SATISFY VENTILATION REQUIREMENTS.
 SEC. 1203 FBC 2001.
 14-SPECIFY VENTILATION FOR ROOF. SEE
 SEC. 2309.7.2 FBC 2001.
 15-CLARIFY WHY SUBMITTING PRODUCT
 APPROVAL FOR ROOF SHINGLES. DRAWINGS
 CALL FOR FLAT ROOF AND SHINGLES CANN'T
 BE USED ON FLAT ROOFS.
 16-PROVIDE PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW.
 B)EXTERIOR DOOR.
 C)STORM SHUTTERS.
  
 17-CONSTRUCTION VALUE DECLARED ON THE
 PERMIT APPLICATION IS TOO LOW. VALUE
 SHALL INCLUDE ALL MATERIALS AND LABOR.
 DECLARED A MORE REALISTIC VALUE OR
 ESTIMATED VALUE WILL BE CALCULATED
 USING THE MARSHALL & SWIFT COST
 ESTIMATING BOOK.
 18-TAKE REVISE DRAWINGS TO PALM BEACH
 COUNTY TO VERIFY IF IMPACT FEES ARE
 DUE OR NOT. THEY WILL STAMP DRAWINGS
 AND GIVE YOU A RECEIPT.
 19-NEED TO GO TO THE COURTHOUSE TO
 RECORD A NOTICE OF COMMENCEMENT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2003-08-25 Cont ID  
Sent By csiegber Date 2003-08-22 Time 10:45 Rev Time 0.33
Received By btrobaug Date 2003-08-25 Time 17:45 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2004-03-04 Cont ID  
Sent By csiegber Date 2004-03-04 Time 16:44 Rev Time 0.00
Received By csiegber Date 2004-03-04 Time 16:44 Sent To B
Notes
2004-03-04 00:00:00TO JG DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-08-22 Cont ID  
Sent By csiegber Date 2003-08-22 Time 10:45 Rev Time 0.00
Received By csiegber Date 2003-08-22 Time 10:45 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-08-19 Cont ID  
Sent By mmclean Date 2003-08-21 Time 12:23 Rev Time 0.00
Received By csiegber Date 2003-08-19 Time 16:33 Sent To Z
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2003-08-21 Cont ID  
Sent By csiegber Date 2003-08-19 Time 16:33 Rev Time 0.00
Received By mmclean Date   Time   Sent To I
Notes
2003-08-21 00:00:008/21/03 PASS ZOING MM